Napoleon Fireplaces GD82PT-PA, GD82NT-PA manual Venting, Supplier

Page 6

6

VENTING

VENT LENGTHS

For safe and proper operation of the fireplace follow the venting instruction exactly.

Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning.

Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed.

Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to minimize condensation.

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or American Metal Amerivent venting components.

Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent venting systems must not be combined.

Follow the installation procedure provided with the venting components.

For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using a red high temperature silicone (RTV). This same sealant maybe used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the fireplace flue collar which must be sealed using the black high temperature sealant MillPac. A starter adaptor must be used and may be purchased from the corresponding supplier:

Supplier

4 / 7

Duravent

W175-0053

Amerivent

4DSC-N2

Direct Temp

4DT-AAN

For Simpson Dura-Vent, Selkirk Direct Temp and American Metal Amerivent, follow the installation procedure found on the website

for your venting supplier:

 

VENTING SUPPLIER

WEBSITE ADDRESS

Simpson Dura-Vent

www.duravent.com

Selkirk Direct Temp

www.selkirkcorp.com

American Metal Amerivent

www.americanmetalproducts.com

When using Napoleon® venting components, use only approved Wolf Steel Ltd. rigid / flexible vent components with the following termination kits: wall terminal kit GD222 and GD222R, or 1/12 to 7/12 pitch roof terminal kit GD110, 8/12 to 12/12 roof terminal kit GD111, flat roof terminal kit GD112 or periscope kit GD201 (for wall penetration below grade). With flexible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330. These vent kits allow for either horizontal or vertical venting of the fireplace.

The maximum number of allowable 4” vent connections is three horizontally or vertically (excluding the fireplace and the air terminal connections).

For optimum flame appearance and fireplace performance, keep the vent length and number of elbows to a minimum.

Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition.

The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.

Horizontal runs may have a 0” rise per foot in all cases using Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, or American Metal Amerivent rigid vent components and Wolf Steel flexible vent components.

For optimum performance, it is recommended that horizontal runs have a minimum 1/4” rise per foot when using Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, or American Metal Amerivent rigid vent components and a minimum of 1” rise per foot when using Wolf Steel flexible vent components.

When venting, the horizontal run must be kept to a maximum of 20 feet. If a 20 foot horizontal run is required, the fireplace must have a minimum vertical rise immediately off the fireplace of 57”. When terminating vertically, the vertical rise is a minimum 3 feet and a maximum 40 feet above the fireplace.

FIGURES 3a-b

FIGURE 4

24” MAXIMUM

16”

 

 

MINIMUM

10”

 

MINIMUM

 

56”

* FIRST

PLUS RISE*

2 FEET

 

REQUIRES

 

INSULATION

 

SLEEVE

* REFER TO “VENTING” SECTION

INSULATION

SLEEVE

3 FEET

MINIMUM

40 FEET

MAXIMUM

12 MINIMUM 30”

MINIMUM

MAXIMUM 10 FOOT VENT LENGTH

CAN BE USED WITH GD201 PERISCOPE KIT

HORIZONTAL VENT SECTIONS: A minimum clearance of 2” all around the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1799 (supplied).

VERTICAL VENT SECTIONS: A minimum of 1” all around the vent pipe on all vertical runs to combustibles is required except for clearances in

replace enclosures. Use fi restop spacer W500-0096 (not supplied).

!WARNING

* The first 2 feet of outer 7 “ diameter vent pipe from the appliance must be wrapped in the 1” thick insulation sleeve (supplied). Make sure the insulation is pulled down tight to the fi replace when installed. There after, a 2” clearance all around the vent pipe from combustible materials on all horizontal vent sections is required.

W415-0665 / B / 02.11.08

Image 6
Contents Installation Operation Instructions Table of Contents W415-0665 / B Fireplace Dimensions Installation OverviewGeneral Instructions Venting SupplierHorizontal Termination DefinitionsElbow Vent Length Values = .03 two 90 elbows 90 = .03180 90 = = .03 four 90 elbows 90 = .03360 90 = 8.1 ftVertical Termination Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Minimum AIR Terminal Location Clearances Installation Wall and Ceiling Protection Using Flexible Vent Components Using Rigid Vent Components Atención Minimum Enclosure Height Minimum Enclosure Clearances Non-combustible fireplace finishingCombustible fireplace finishing Electrical Connection Hard Wiring ConnectionElectrical Schematic Minimum Mantel and Enclosure ClearancesLOG Shipping Bracket FinishingDoor Removal StepLOG Placement Glowing EmbersGLASS/DOOR Replacement Blower ReplacementBurner and Valve Replacement General Transmitter Layout Fireplace Operation With a clean dry clothOperation Bulb with bare fingers, protectSmart Thermostat Temperature DisplayHand Held Remote Operations Flame HeightChild Proof Function LOW Battery / Manual BypassFAN Speed Remote Auxiliary OutletLighting Instructions Operating InstructionsWhat to do if YOU Smell GAS To Turn OFF GASFlame Characteristics AdjustmentsPilot Burner Adjustment Venturi AdjustmentReplacements W415-0665 / B Trouble Shooting Guide Symptom Problem Test SolutionThemostat or switch is de Fireplace Service History W415-0665 / B