FireplaceXtrordinair 864 HH Vent Requirements, Vent Clearances, Altitude Considerations

Page 21

Installation (for qualified installers only)

21

Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use it's own separate vent system.

In addition to the requirements listed here, follow the requirements provided with the vent.

A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing members). Horizontal vent less than 48" above the fireplace must use the Travis Firestop (sku 93006094 - it incorporates a 3" clearance above, 1" clearance below and to the sides of the vent). Other penetrations only require a 1" clearance and may use a standard firestop (make sure the required 1" clearance is met).

Always use the high-wind termination (if available from the vent manufacturer).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air spaces with insulation.

 

Before 48" Rise

After 48" Rise

Sides

1"

1"

Above

3"

1"

Below Horizontal or 45° Section

1"

1"

Vertical Termination

Use a roof flashing and storm collar whenever passing through the roof

Use a firestop whenever passing through a ceiling

Use a support box on exposed vent

Required Firestop

Min. 1"

Horizontal

Termination

Min. 3"

(1" if a minimum 48" above the fireplace)

Min. 1"

Min. 1"

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet. In this testing we have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.

Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.

© Travis Industries

4080214

100-01182_003

Image 21
Contents HH Fireplace Listing Details OverviewIAS Icbo Approval Massachusetts ApprovalTable of Contents Safety Warnings Safety PrecautionsSafety Precautions Installation Options Heating SpecificationsDimensions Recommended Installation Procedure Installation OverviewPacking List Additional Items RequiredRequirements for the Commonwealth of Massachusetts Massachusetts RequirementsConverting Fireplace to Top Vent Configuration Top Vent or Rear Vent ConfigurationDo not Over Tighten Screws Converting the Fireplace to Top VentFireplace Placement Requirements ClearancesRaised Fireplaces Minimum 49 Fireplace Enclosure Height Minimum Framing Dimensions Rear Vent ConfigurationMinimum Framing Dimensions Top Vent Configuration Nailing Brackets TOP ViewCorner Installations Rear Vent Configuration Corner Installations Top Vent Configuration Fuel Gas Line RequirementsGas Line Connection Gas Inlet PressureLeft Side Gas Inlet preferred Gas Line LocationElectrical Connection required Wall Switch or Thermostat Installation Wiring Diagram Millivolt SystemWall Switch Installation Vent Requirements Vent ClearancesAltitude Considerations Approved Vent Vent InstallationApproved Vent Configurations Exhaust Restrictor AdjustmentRestrictor Position Intake Restrictor Adjustment Diffuser Side View Diffuser Plate AdjustmentExhaust Restrictor Removal 0feet 5feet 22 max Feet 10feet 15feet Rear Vent Configuration with Vertical Termination Feet 21 max 5feet 10feet 15feet Top Vent Configuration with Horizontal TerminationTop Vent Configuration with Vertical Termination Termination Requirements Floor Mounted Fireplaces Hearth RequirementsFacing Requirements Drywall InstallationFacing Overview Optional Faceplates Sizing ChartFront View Raised Fireplace with no Hearth Front View Thick Facing with Fireplace Xtrordinair FPX Arched Faces Floor-Mounted Fireplace with Hearth Thick Facing Installation SideMantel Requirements Side View Installation Example Build-In with Horizontal Termination Steps for Finalizing the Installation Starting the Pilot FlamePilot Flame Inspection Air Shutter Adjustment Finalizing the Installation for qualified installers onlyRe-Attaching the Glass Frame Glass Frame Removal and InstallationFinalizing the Installation for qualified installers only Fireback and Grate Installation Log Set Installation Rear Log InstallationRight Log Installation Left Log Installation Verify Rear LOG Position Right Twig InstallationCenter Twig Installation Front Twigs InstallationEmber Installation LP Conversion Instructions Follow the directions below to replace the orifices Slotted Screwdriver Or T-20 Torx Upper Grill Installation Grill InstallationRemote Control Receiver Installation 2 Options Option # 1 Remote ThermostatOption # 2 Remote Thermostat Extra Room Power Heat Duct sku New Wire Hook-UpSpecial Instructions for 864 HH Installation Overview Maximum DuctLength = Length Duct Installation InstructionsFloor Mounting Attach the grill and wall adapter, if necessary Follow the directions below to wire the blower box Wiring Diagram -864TRVOFF Operating InstructionsAccent Light Installation sku Optional Equipment for qualified installers only Accent Light Operation Optional Wall-Mounted RheostatOptional Equipment for qualified installers only Index 68Index