Heat & Glo LifeStyle 8000TRD manual Venting with ONE 1 90 Elbow, Venting with One 90 Elbow

Page 15

VENTING WITH ONE (1) 90° ELBOW

V

 

H

 

1' MIN. (305mm)

2'

MAX. (610mm)

2' MIN. (610mm)

4'

MAX.

(1.22m)

3' MIN. (914mm)

6'

MAX.

(1.86m)

4' MIN. (1.22m)

8'

MAX.

(2.4m)

V+H=40' MAX. (12.4m)

H = 8' MAX. (2.4m)

NOTE: On vertical venting configurations where the vertical component is over 10 feet, you may want to install the vertical baffle included in the manual bag assembly to improve flame appearance.

Figure 11. Venting with One 90° Elbow

VENTING WITH ONE (1) 90° ELBOW

V (FT.)

H (FT.)

1' MIN. (305mm)

5' MAX. (1.52m)

2' MIN. (610mm)

10' MAX. (3.1m)

3' MIN. (914mm)

15' MAX. (4.65m)

4' MIN. (1.22m)

20' MAX. (6.2m)

V+H= 40’ MAX. (12.4MM) H = 20' MAX. (6.2m)

H

V

 

 

 

 

 

 

 

 

 

 

 

NOTE: For corner installations: A 6-inch (152mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

section of straight pipe may need to be attached to

 

 

 

 

 

 

 

 

 

 

 

the fireplace before a 90o elbow, to allow the vent

 

 

 

 

 

 

 

 

 

 

 

pipe to clear the top standoffs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If a 90o elbow is first attached to the unit,

 

 

 

 

 

 

 

 

 

 

 

Figure 12. Venting with One 90° Elbow

the maximum horizontal run is 3-feet (914mm).

 

 

 

 

 

 

 

 

 

 

 

 

15

Image 15 Contents
What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents 8000TRD 18 9 Log Set AssemblyIPI Ignition Allumage IPI Service Parts List / Liste des pièces de rechange 8000TRDCommon Parts / Piéces Communes Standing Pilot Ignition / D’ALLUMAGE PAR VeilleuseCertification Installation CodesHigh Altitude Installations Appliance CertificationPre-install Preparation Introducing the Heat-N-Glo Gas FireplacesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the 8000TRD Space Requirements Constructing the Fireplace ChaseLocating the Fireplace Clearance RequirementsFraming the Fireplace Framing Dimensions187mm 149mm 220mm DV-90D 164mm 216mm Terminations Kits Installing the Vent SystemVent System Approvals Identifying Vent ComponentsBreak Here Flue Restrictor InstructionsVertical Venting MAX .4 MChart Venting with One 90 Elbow Venting with ONE 1 90 ElbowVenting with TWO Elbows MIN MAX mm 610mm MAX .22m 914mm MAX .86m MAX .4m Venting with three 90 elbows Venting with Three 3 90 Elbows+ H 1 FT Installing Vent Components Stove Cement Must be Placed around5 Inch 127 MM Fireplace Starting COL To Install the Heat Shield Install Support BracketsContinue Adding Vent Components 12 Hole and Vent Pipe Vent Termination Positioned SO That the Arrow is Pointing UP4 184mm Vent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Standing Pilot Ignition System Vice Must be Wired Directly to the FIRE- Place Junction BOXPositioning, Leveling, and Securing the Fireplace Gas Control SystemsNatural Gas Propane Gas Supply LineGas Pressure Requirements Check for GAS LeaksPosition the wall switch in the desired position on a wall Wiring the FireplaceOptional Accessories Optional fan and remote control kits require thatBlack Optional Battery BACK-UP RED Brown Operation using Battery PowerSealant Material Hearth Extensions FinishingOutlet Grilles in ANY Manner Installing Trim, Logs, and Ember MaterialInstalling the Trim Shutter Settings Burner Placing the Ember MaterialBefore Lighting the Fireplace After the InstallationGlass Specifications 8000TRD 26 1/2 X 42 1/2 Tempered Double-check for faulty componentsReplacing old ember material Fireplace MaintenanceCleaning Glass Door Important Turn OFF the GAS Before Servicing Your Fireplace