Heat & Glo LifeStyle 8000TRD manual Constructing the Fireplace Chase, Locating the Fireplace

Page 9

Installing the Fireplace

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the gas fireplace and/or its vent system. Vertical vents that run on the outside of a building may be, but are not required to be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND CONSTRUCTION OF THE CHASE MAY VARY WITH THE TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES. THEREFORE, YOUR LOCAL BUILD- ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner.

This means that the walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltra- tion barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, Heat-N-Glo rec- ommends that the inside surfaces be sheetrocked and taped for maximum air tightness.

To further prevent drafts, the firestops should be caulked to seal gaps. Gas line holes and other openings should be caulked or stuffed with insulation. If the unit is being in- stalled on a cement slab, we recommend that a layer of plywood be placed underneath to prevent conducting cold up into the room. Be sure to include spark arrestors for woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL CLEARANCES TO THE FIREPLACE ARE MAINTAINED AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

Step 1. Locating the Fireplace

The following diagram shows space and clearance require- ments for locating a fireplace within a room.

Clearance Requirements

The top, back, and sides of the fireplace are defined by stand-offs. The minimum clearance to a perpendicular wall extending past the face of the fireplace is one inch (25 mm). The back of the fireplace may be recessed 21 1/2 inches (546 mm) into combustible construction.

1” MIN. (25mm)

 

B

 

A

 

E

D

 

C

 

1/2” MIN. (13mm)

 

A

B

C

D

E

49”

22”

39 1/2”

56”

79”

Figure 2. Fireplace Dimensions, Locations,

 

and Space Requirements

 

Minimum Clearances

 

from the Fireplace to Combustible Materials

 

 

Inches

mm

Glass Front

........................

36

914

Floor

0

0

Rear

1/2

13

Sides

1/2

13

Top

3 1/2

89

Ceiling**

31

787

*See Figure 3.

**The clearance to the ceiling is measured from the top of the unit, excluding the standoffs (see Figure 40).

The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the combustible construction, NOT from the screw heads that secure the unit together.

Minimum Clearances

from the Vent Pipe to Combustible Materials

 

Inches

mm

Vertical Sections

1

25

Horizontal Sections

 

 

Top

3

75

Bottom

1

25

Sides

1

25

At Wall Firestops

 

 

Top

2 1/2

63.7

Bottom

1/2

13

Sides

1

25

For minimum clearances, see the direct vent termination clearance diagrams on pages 23 and 24 in this manual.

9

Image 9
Contents What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents 8000TRD 18 9 Log Set AssemblyCommon Parts / Piéces Communes Service Parts List / Liste des pièces de rechange 8000TRDStanding Pilot Ignition / D’ALLUMAGE PAR Veilleuse IPI Ignition Allumage IPIHigh Altitude Installations Installation CodesAppliance Certification CertificationPre-install Preparation Introducing the Heat-N-Glo Gas FireplacesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the 8000TRD Locating the Fireplace Constructing the Fireplace ChaseClearance Requirements Space RequirementsFraming the Fireplace Framing Dimensions187mm 149mm 220mm DV-90D 164mm 216mm Vent System Approvals Installing the Vent SystemIdentifying Vent Components Terminations KitsVertical Venting Flue Restrictor InstructionsMAX .4 M Break HereChart Venting with One 90 Elbow Venting with ONE 1 90 ElbowVenting with TWO Elbows MIN MAX mm 610mm MAX .22m 914mm MAX .86m MAX .4m Venting with three 90 elbows Venting with Three 3 90 Elbows+ H 1 FT Installing Vent Components Stove Cement Must be Placed around5 Inch 127 MM Fireplace Starting COL To Install the Heat Shield Install Support BracketsContinue Adding Vent Components 12 Hole and Vent Pipe Vent Termination Positioned SO That the Arrow is Pointing UP4 184mm Vent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Positioning, Leveling, and Securing the Fireplace Vice Must be Wired Directly to the FIRE- Place Junction BOXGas Control Systems Standing Pilot Ignition SystemGas Pressure Requirements Gas Supply LineCheck for GAS Leaks Natural Gas PropaneOptional Accessories Wiring the FireplaceOptional fan and remote control kits require that Position the wall switch in the desired position on a wallBlack Optional Battery BACK-UP RED Brown Operation using Battery PowerSealant Material Hearth Extensions FinishingInstalling the Trim Installing Trim, Logs, and Ember MaterialShutter Settings Burner Placing the Ember Material Outlet Grilles in ANY MannerGlass Specifications 8000TRD 26 1/2 X 42 1/2 Tempered After the InstallationDouble-check for faulty components Before Lighting the FireplaceCleaning Glass Door Fireplace MaintenanceImportant Turn OFF the GAS Before Servicing Your Fireplace Replacing old ember material