Heat & Glo LifeStyle 8000TRD Gas Supply Line, Gas Pressure Requirements, Check for GAS Leaks

Page 27

Step 6. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer ap- proved and/or licensed as required by the locality. (In the state of Massachusetts installation must be performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch

(13 mm) gas supply line. To install the gas supply line:

• A listed (and State of Massachusetts approved) 1/2 inch

(13mm) tee-handle manual shut-off valve and a listed

flexible gas connector are connected to the 1/2 inch

CONTROL

VALVE

GAS LINE

ACCESS HOLE

Use a wrench on shut-off valve when tightening gas line.

MANUAL

SHUT-OFF

VALVE

GAS

VALVE

FLEX

CONNECTOR

(13mm) inlet of the control valve. NOTE: If substituting

for these components, please consult local codes for

compliance.

• Locate the gas line access hole in the outer casing of

the fireplace.

• The gas line may be run from either side of the fireplace

provided the hole in the outer wrap does not exceed 2 1/2”

in diameter and it does not penetrate the actual firebox.

• The gap between the supply piping and gas access hole

can be plugged with non-combustible insulation to pre-

vent cold air infiltration.

• Open the fireplace lower grille, insert the gas supply line

through the gas line hole, and connect it to the shut-off valve.

• When attaching the pipe, support the control so that the

lines are not bent or torn.

• After the gas line installation is complete, use a soap

solution to carefully check all gas connections for leaks.

WARNING: DO NOT USE AN OPEN FLAME TO

!CHECK FOR GAS LEAKS.

At the gas line access hole, use insulation to re-pack the space around the gas pipe.

Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.

Figure 36. Gas Supply Line

Step 7. Gas Pressure Requirements

Pressure requirements for Heat-N-Glo gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

27

Image 27 Contents
What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents 8000TRD 18 9 Log Set AssemblyIPI Ignition Allumage IPI Service Parts List / Liste des pièces de rechange 8000TRDCommon Parts / Piéces Communes Standing Pilot Ignition / D’ALLUMAGE PAR VeilleuseCertification Installation CodesHigh Altitude Installations Appliance CertificationPre-install Preparation Introducing the Heat-N-Glo Gas FireplacesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the 8000TRD Space Requirements Constructing the Fireplace ChaseLocating the Fireplace Clearance RequirementsFraming the Fireplace Framing Dimensions187mm 149mm 220mm DV-90D 164mm 216mm Terminations Kits Installing the Vent SystemVent System Approvals Identifying Vent ComponentsBreak Here Flue Restrictor InstructionsVertical Venting MAX .4 MChart Venting with One 90 Elbow Venting with ONE 1 90 ElbowVenting with TWO Elbows MIN MAX mm 610mm MAX .22m 914mm MAX .86m MAX .4m Venting with three 90 elbows Venting with Three 3 90 Elbows+ H 1 FT Installing Vent Components Stove Cement Must be Placed around5 Inch 127 MM Fireplace Starting COL To Install the Heat Shield Install Support BracketsContinue Adding Vent Components 12 Hole and Vent Pipe Vent Termination Positioned SO That the Arrow is Pointing UP4 184mm Vent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Standing Pilot Ignition System Vice Must be Wired Directly to the FIRE- Place Junction BOXPositioning, Leveling, and Securing the Fireplace Gas Control SystemsNatural Gas Propane Gas Supply LineGas Pressure Requirements Check for GAS LeaksPosition the wall switch in the desired position on a wall Wiring the FireplaceOptional Accessories Optional fan and remote control kits require thatBlack Optional Battery BACK-UP RED Brown Operation using Battery PowerSealant Material Hearth Extensions FinishingOutlet Grilles in ANY Manner Installing Trim, Logs, and Ember MaterialInstalling the Trim Shutter Settings Burner Placing the Ember MaterialBefore Lighting the Fireplace After the InstallationGlass Specifications 8000TRD 26 1/2 X 42 1/2 Tempered Double-check for faulty componentsReplacing old ember material Fireplace MaintenanceCleaning Glass Door Important Turn OFF the GAS Before Servicing Your Fireplace
Related manuals
Manual 33 pages 3.26 Kb