OPERATIng fireplace

Continued

Key Pad Lock Feature

This feature allows the user to lock/unlock the keypad on the hand-held remote in the MANU or AUTO mode to prevent inadvertent operation (i.e. children operating the hand-held remote control, etc.). The keypad is locked in either on or off. Press the POWER and LOCK buttons together to turn the unit on or off.

Operating optional

GWMT1 - Wall Mounted

Thermostat

WARNING: Do not con- nect the thermostat to a power source. Electrical shock and/or a fire hazard will occur.

Light the fireplace as instructed in Lighting Instructions on page 27. Set wall thermostat to desired temperature.

This thermostat has been electronically cali- brated at the factory and requires no adjust- ment or leveling.

Upon installation, the thermostat must be al- lowed to stabilize at room temperature for a minimum of 30 minutes for proper operation. To turn the fireplace off, adjust thermostat to the lowest setting and turn the gas control knob back to PILOT. The pilot will remain lit.

IMPORTANT: To turn the pilot off, turn the gas control knob on the heater to the OFF position.

operating optional blower accessory

Locate the blower controls by opening the lower louver panel on the fireplace. Blower controls are located on the right side of the switch bracket to the left just inside the louver panel. The BK manual blower and the BKT thermo- statically-controlled blower have an ON setting and an OFF setting. The blower will only run when the switch is in the ON position. In the OFF position, the blower will not operate.

Note for BKT Only: If you are using BKT blower with optional thermostat (wall mounted or remote control) for the fireplace, your fire- place and blower will not turn on and off at the same time. The fireplace may run for several minutes before the blower turns on. After the heater modulates to the pilot position, the blow- er will continue to run. The blower will shut off after the firebox temperature decreases.

The blower helps distribute heated air from the fireplace. Periodically check the louvers of the firebox and remove any dust, dirt or other obstructions that will hinder the flow of air.

Inspecting Burners

Check pilot flame pattern and burner flame pat- terns often.

Pilot assembly

The pilot assembly is factory preset for the proper flame height. Alterations may have occurred dur- ing shipping and handling. Call a qualified service person to readjust the pilot if necessary.

The height of the thermopile must be 3/8" to 1/2" above the pilot flame as shown in Figure 49. The thermocouple must be at a height of about 1/8" above the pilot flame. The flame from the pilot burner must extend beyond both the thermocouple and thermopile.

If you pilot assembly does not meet these require- ments:

turn fireplace off (see To Turn Off Gas to Ap- pliance, page 28)

see Troubleshooting, page 33

Thermopile

3/8" to 1/2"

Pilot Burner 1/8"

Thermocouple

Piezo Ignitor

Figure 48 - Pilot Assembly

30

www.desatech.com

116236-01G

Image 30
Contents What to do if YOU Smell GAS Patent PendingTable of Contents Safety InformationSafety Information Product Identification Local CodesHigh traffic areas Location and space requirements Product FeaturesPre-Installation Preparation This fireplace does not require electricity to operate42 1067 mm ClearancesMinimum clearances to combustibles for Front 36 914 mm Top of Standoffs VentFraming and finishing Noncombustible mantels at any height aboveFireplace Location of Termination Cap Balcony with Perpendicular Side WallVenting Installation Instructions Installation PrecautionsInstallation Planning Installing Horizontal Vent Cap Noncombustible Exterior Ground Floor Installation Round TerminationCorner Installation Recommended Applications Corner ground floor installationHorizontal System Installation Using TWO 90 Elbows Installation for vertical termination Flat Ceiling InstallationConnect a section of pipe and extend up through the hole Twist-lock the vent cap onto the last section of vent pipe High Altitude Installation Vertical VentingParts list for venting kits and components Desa 5/8 Pipe & Vent Kits Number DescriptionModel BK Installation Fireplace InstallationInstalling optional blower accessories Plug in blower power cordModel BKT Installation Blower Model BKTInstalling Gas Piping to Fireplace Location Blower Wiring DiagramInstallation Items Needed Connecting Fireplace to GAS Supply Propane/LP FromChecking GAS Connections Test Pressures Equal To or Less Than Psig 3.5 kPaPressure Testing Fireplace Gas Connections Installing Remote ReceiverRemoving Louver Panels Replace battery cover onto remote control unitRemoving/Replacing Glass Door Removing Glass DoorReplace screen/rod assembly by reversing step Installing lava rock and glowing embersInstalling Brick liner Models BL42DASA and BL42DHASA Cleaning Glass DoorLighting Instructions For your safety Read before lightingOperating Fireplace Close top and bottom louversTo Turn OFF GAS To Appliance Manual Lighting Procedure Optional Hand-HeldRemote Operation On/Off Series Model HRC100 Thermostat Series Model HRC200Key Pad Lock Feature Operating optional blower accessoryPilot assembly Inspecting BurnersCleaning Maintenance Burner Flame PatternGlass Door Pilot and burners LogsVenting system Troubleshooting Observed Problem Possible Cause RemedyAfter pilot lights, keep gas Problem could be caused by Replace pilot assemblyBurner orifice clogged Clean burner see Cleaning Is lit Long enough Control knob pressedTurning gas control knob to When burner is lit HI position when burner isTery power is low Cold Minute Air in gas line Operate burner until air isGas leak. See Warning Statement aboveTechnical Service Replacement PartsService Hints SpecificationsIllustrated Parts Breakdown Parts List 19 18 116236-01G Burner Pan Assembly Accessories Wall mounted on/off switch Wall mounted thermostat control kit gwmt1GwmS2 Not Shown Warranty Information Keep this WarrantyLimited Warranty DIRECT-VENT Fireplace