Vermont Casting DVT38S2IN General Venting Information Termination Location

Page 15

Chateau™ Direct Vent Gas Fireplace

General Venting Information - Termination Location

INSIDE

CORNER DETAIL

D

E V L

C

G

V

A

B

H N N

B

CFM145a

V�����

������

F

V

Operable

 

B

V

 

B

V

 

Operable

Fixed

 

 

 

Closed

 

 

 

 

 

 

 

V J

B

M

B

X

V K X

 

A

 

I

 

 

 

 

CFM145 V VENT TERMINATION X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED

 

 

Canadian Installations1

US Installations2

A =

Clearance above grade, veranda, porch,

12” (30 cm)

12” (30 cm)

 

deck, or balcony

 

 

B = Clearance to window or door that may be

6” (15 cm) for appliances

6” (15 cm) for appliances

 

opened

< 10,000Btuh (3kW), 12” (30 cm)

< 10,000 Btuh (3kW), 9”

 

 

for appliances > 10,000 Btuh (3kW) and

(23 cm) for appliances > 10,000

 

 

< 100,000 Btuh (30kW), 36” (91 cm)

Btuh (3kW) and < 50,000 Btuh

 

 

for appliances > 100,000 Btuh (30kW)

(15kW), 12” (30 cm) for

 

 

 

appliances > 50,000 Btuh (15kW)

C* =Clearance to permanently closed window

12” (305 mm) recommended to

12” (305 mm) recommended to

 

 

prevent window condensation

prevent window condensation

D* =Vertical clearance to ventilated soffit located

 

 

 

above the terminal within a horizontal

18” (458 mm)

18” (458 mm)

 

distance of 2’ (610mm) from the center

*CAUTION: Clearances to soffit do not apply to “vinyl soffits”.

 

line of the terminal

 

 

 

E = Clearance to unventilated soffit

24” (610 mm)

24” (610 mm)

F =

Clearance to outside corner

see next page

see next page

G = Clearance to inside corner (see next page)

see next page

see next page

H = Clearance to each inside of center line

3’ (91 cm) within a height of 15’ (5m)

3’ (91 cm) within a height of 15’

 

extended above meter/regulator assembly

above the meter/regulator assembly

(5 m) above the meter/regulator

 

 

 

assy

I =

Clearance to service regulator vent outlet

3’ (91 cm)

3’ (91 cm)

J =

Clearance to nonmechanical air supply inlet

6” (15 cm) for appliances < 10,000

6” (15 cm) for appliances

 

to building or the combustion air inlet to any

Btuh (3kW), 12” (30 cm) for

< 10,000 Btuh (3kW), 9”

 

other appliances

appliances > 10,000 Btuh (3kW) and <

(23 cm) for appliances > 10,000

 

 

100,000 Btuh (30kW), 36” (91 cm)

Btuh (3kW) and < 50,000 Btuh

 

 

for appliances > 100,000 Btuh (30kW)

(15kW), 12” (30cm) for

 

 

 

appliances > 50,000 Btuh (15kW)

K =

Clearance to a mechanical air supply inlet

6’ (1.83 m)

3’ (91 cm) above if within 10’

 

 

 

(3 m) horizontally

L =

Clearance above paved sidewalk or paved

7’ (2.13 m)†

7’ (2.13 m)†

 

driveway located on public property

 

 

M = Clearance under veranda, porch, deck or

12” (30 cm)‡

12” (30 cm)‡

 

balcony

 

 

N = Clearance above a roof shall extend a minimum of 24” (610 mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18” (450 mm).

1 In accordance with the current CSA-B149 Installation Codes

2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes

A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings

‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor: NOTE: 1. Local codes or regulations may require different clearances.

2.The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and approved by the listing agency.

3.CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.

Fig. 10 Vent termination clearances.

20011957

15

Image 15
Contents What to do if YOU Smell GAS INSTALLER/CONSUMER Safety InformationTable of Contents Please Review the Following Carefully Installation & Operating InstructionsCertified To Ansi Z21.50b-2005 / CSA 2.22b-2005 Vented Gas FireplaceStandard Framing Locating Your FireplaceMantels Clearance to CombustiblesGas Specifications HearthFraming and Finishing Final FinishingElectrical Junction Box Gas Line InstallationGas Inlet and Manifold Pressures High ElevationsControl System Control System InstallationChateau Direct Vent Gas Fireplace Special Feature for Cold ClimatesLCD Liquid Crystal Display Remote Control Transmitter Operating InstructionsKey Settings IntroductionThermostat Function Manual FunctionContinuous Pilot Feature CP Childproof FeatureSetting LOCK-OUT CP Operational Notes Thermostatic Updating FeatureLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2Canadian Installations USA InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Horizontal Termination Vertical TerminationSidewall Applications Step Sidewall InstallationZero clearance sleeve is only required for combustible walls Always install horizontal venting on a level planeHorizontal length requirement Sidewall Installation with Stationary Glass Facing OutsideInstalling the 38S2VDK Door Installation ProcedureTypical Applications Flue Restrictor Plate InstallationRestrictor Plate Installation Flue Restrictor Plate GuideFlue restrictor plate use in straight up installation + 2 + 3 + 4 = Vertical Through-the-Roof InstallationMin Component Description Model Number Chimney ComponentsClean the glass after the first two weeks of operation Glass Frame Assembly RemovalGlass Cleaning Ceramic Refractory InstallationDVT38Sw log identification Log, Lava Rock and Ember PlacementLog Pilot Plumbing F50 Overlay is very fragile Log Right Flame Characteristics Trim Installation Lighting & Operating Instructions Lighting InstructionsTurning Off the Gas to the Appliance Troubleshooting American Flame Gas Control SystemOperation Troubleshooting American Flame Gas Control System What to Check American Flame Gas Control System Error CodesConversion Precautions Conversion ProcedureFuel Conversion Instructions Remove pilot orifice Conversion to LP Pilot Flame AdjustmentDVT38S2 Injector Orifice Size Matrix Valve Minimum Rate ScrewMaintenance Cleaning the Control SystemBurner and Burner Compartment DVT38S2 Units GFYW5Q0 DVT38S2 DVT38S2Fuel Conversion Kits Back-up Battery Kit AccessoriesChateau Direct Vent Gas Fireplace Product Covered by this Warranty Limited Lifetime WarrantyModel EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings