Trane WC-IOM-7 manual Smoke Detector Customer Low Voltage Wiring, Smoke detector wiring

Page 28

Installation

Smoke Detector Customer Low Voltage Wiring

When interlocking System Sensor smoke detectors together, all of the detectors must be powered from the same power supply. If multiple smoke detectors are required, all detectors must be disconnected from the HVAC unit power supply and connected together from another single source supply.

Note: Do not interconnect smoke detectors together that have separate power supplies. Do not exceed ten smoke detectors on one power supply.

Note: Multiple System Sensor smoke detectors are connected together using terminals 1 and 12 on each detector.

If you have supply and return smoke detectors in all HVAC units, you can connect a maximum of 5 HVAC units (10 detectors) up to one power supply. See the following field wiring example.

If you have more than 5 HVAC units, you can connect all the supply detectors together on one power supply (up to 10 HVAC units), and all the return detectors together (up to 10 HVAC units) on another power supply. See the following field wiring example.

Figure 12. Smoke detector wiring

 

Up to 5 HVAC units

More than 5 HVAC units

28

Packaged Heat Pump • WC-IOM-7

Image 28
Contents Packaged Heat Pump DecemberModel Number Description Hazardous Voltage w/Capacitors Contains RefrigerantEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information Clogged Filter Switch Optional General InformationRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalCompressor Disable CPR1/2 Power Exhaust Control OptionalLow Pressure Control High Pressure Control OptionalLead/Lag Control Dual Circuit Only Zone Sensor Module ZSM BAYSENS007BZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BHigh Temperature Sensor BAYFRST001A Remote Zone Sensor BAYSENS013CRemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016AUnit Inspection Smoke Detector Sensor OptionalFirst Aid Measures Fiberglass WoolStorage Unit Clearances Unit Dimensions Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 TonUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Heavy Objects Improper Unit LiftRigging Installation If a Curb Accessory Kit is not usedHorizontal Units DuctworkInstallation Factory Installed EconomizerMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsFilter Installation Condensate Drain ConfigurationField Installed Power Wiring Main Unit Power Standard WiringOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyControl Power Transformer Field Installed Control WiringHazardous Voltage Controls using 24 VAC Rtrm Smoke Detector Customer Low Voltage Wiring Smoke detector wiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Live Electrical Components Electrical Phasing Three Phase MotorsCompressor Crankcase Heaters Optional ReliaTel Controls Pre-Start Test ModesPre-Start Verifying Proper Air Flow Units with Belt Drive Indoor FanReturn Air Smoke Detector Start Up Economizer Start-UpRotating Components Compressor Start-UpHeating Start-Up Start UpScroll Compressors Final System Setup Maintenance Fan Belt Adjustment Belt Drive UnitsMaintenance Monthly Maintenance Hazardous VoltageCooling Season Return Air Smoke Detector MaintenanceFilters Coil Cleaning Heating SeasonHazardous Pressures Final ProcessSample maintenance log Hazardous Service Procedures TroubleshootingReliaTel Control Troubleshooting System Status Checkout ProcedureSystem Failure MethodHeat Failure Resetting Cooling and Heating LockoutsCool Failure Clogged Filter Switch Zone Temperature Sensor ZTS Service IndicatorFan Failure Switch Test Cooling Set Point CSP and Heating Set Point HSP ZtempTesting serial communication voltage Test System Mode and Fan SelectionProgrammable & Digital Zone Sensor Test ReliaTel Refrigeration Module Rtrm Default Chart Unit Operation without a Zone SensorUnit Economizer Control ECA Troubleshooting ReliaTel Control Wiring Diagrams Drawing Number DescriptionWarranty Heat PumpWarranty Page WC-IOM-7