Trane WC-IOM-7 manual Remote Zone Sensor BAYSENS013C, Remote Zone Sensor BAYSENS014C

Page 11

General Information

Remote Zone Sensor (BAYSENS013C)

This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Integrated ComfortTM building management system.

Remote Zone Sensor (BAYSENS014C)

This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated ComfortTM building management system.

Remote Zone Sensor (BAYSENS016A)

This bullet type temperature sensor can be used for; outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered. Wiring procedures vary according to the particular application and equipment involved. Refer to the unit’s wiring diagrams for proper connections.

Remote Zone Sensor (BAYSENS017B)

This electronic sensor can be used with BAYSENS006B, 008B, 010B, 019B Remote Panels. When this sensor is wired to a BAYSENS019B Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.

High Temperature Sensor (BAYFRST001A)

This sensor connects to the RTRM Emergency Stop Input on the LTB and provides high limit “shutdown” of the unit. The sensor is used to detect high temperatures due to fire in the air conditioning or ventilation ducts. The sensor is designed to mount directly to the sheet metal duct. Each kit contains two sensors. The return air duct sensor (X1310004001) is set to open at 135°F. The supply air duct sensor (X1310004002) is set to open at 240°F. The control can be reset after the temperature has been lowered approximately 25°F below the cutout setpoint.

Evaporator Frost Control

This input incorporates the Frostat™ control (FOS) mounted in the indoor coil and can be activated by closing a field supplied contact installed in parallel with the FOS.

If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 5 continuous seconds during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the FOS close.

WC-IOM-7 • Packaged Heat Pump

11

Image 11
Contents December Packaged Heat PumpModel Number Description Equipment Damage From Ultraviolet UV Lights Contains RefrigerantHazardous Voltage w/Capacitors Contents Contents Model Number Description General Information Rtom ReliaTel Options Module Optional Clogged Filter Switch OptionalGeneral Information Rlci ReliaTel LonTalk Communication Interface OptionalHigh Pressure Control Optional Compressor Disable CPR1/2Power Exhaust Control Optional Low Pressure ControlZone Sensor BAYSENS011B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS007B Zone Sensor Module ZSM BAYSENS009BRemote Zone Sensor BAYSENS016A High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS013C Remote Zone Sensor BAYSENS014CSmoke Detector Sensor Optional Unit InspectionStorage Fiberglass WoolFirst Aid Measures Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging Ductwork InstallationIf a Curb Accessory Kit is not used Horizontal UnitsLow Voltage Wiring AC & DC Requirements InstallationFactory Installed Economizer Main Electrical Power RequirementsField Installed Power Wiring Condensate Drain ConfigurationFilter Installation Use Copper Conductors Only Main Unit PowerStandard Wiring Optional Tbue Wiring Through the Base Electrical OptionHazardous Voltage Field Installed Control WiringControl Power Transformer Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Compressor Crankcase Heaters Optional Electrical Phasing Three Phase MotorsLive Electrical Components ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Compressor Start-Up Start UpEconomizer Start-Up Rotating ComponentsScroll Compressors Start UpHeating Start-Up Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceFilters Return Air Smoke Detector MaintenanceCooling Season Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log ReliaTel Control TroubleshootingHazardous Service Procedures System Status Checkout Procedure TroubleshootingMethod System FailureCool Failure Resetting Cooling and Heating LockoutsHeat Failure Fan Failure Switch Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPProgrammable & Digital Zone Sensor Test Test System Mode and Fan SelectionTesting serial communication voltage Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7