Maintenance

￿WARNING

Hazardous Pressures!

Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil bursting, which could result in death or serious injury.

Do not heat the detergent-and-water solution above 150° F. Hot liquids sprayed on the exterior of the coil will raise the coil’s internal pressure and may cause it to burst. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage.

5.5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used:

a.do not allow sprayer pressure to exceed 600 psi.

b.the minimum nozzle spray angle is 15 degrees.

c.maintain a minimum clearance of 6" between the sprayer nozzle and the coil.

d.spray the solution perpendicular (at 90 degrees) to the coil face.

6.Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes.

7.Rinse both sides of the coil with cool, clean water.

8.Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7.

9.Reinstall all of the components and panels removed in Step 1 and any protective covers installed in step 2.

10.Restore the unit to it’s operational status and check system operation.

Final Process

For future reference, you may find it helpful to record the unit data requested below in the blanks provided.

(1)Complete Unit Model Number:

_______________________________________________________________________

(2)Unit Serial Number:

_______________________________________________________________________

(3)Wiring Diagram Numbers (from unit control panel):

schematic(s)

_______________________________________________________________________

_______________________________________________________________________

WC-IOM-7 • Packaged Heat Pump

45

Image 45
Contents December Packaged Heat PumpModel Number Description Contains Refrigerant Hazardous Voltage w/CapacitorsEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information General Information Clogged Filter Switch OptionalRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalPower Exhaust Control Optional Compressor Disable CPR1/2Low Pressure Control High Pressure Control OptionalZone Sensor Module ZSM BAYSENS007B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BRemote Zone Sensor BAYSENS013C High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016ASmoke Detector Sensor Optional Unit InspectionFiberglass Wool First Aid MeasuresStorage Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging If a Curb Accessory Kit is not used InstallationHorizontal Units DuctworkFactory Installed Economizer InstallationMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsCondensate Drain Configuration Filter InstallationField Installed Power Wiring Standard Wiring Main Unit PowerOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyField Installed Control Wiring Control Power TransformerHazardous Voltage Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Electrical Phasing Three Phase Motors Live Electrical ComponentsCompressor Crankcase Heaters Optional ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Economizer Start-Up Start UpRotating Components Compressor Start-UpStart Up Heating Start-UpScroll Compressors Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceReturn Air Smoke Detector Maintenance Cooling SeasonFilters Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log Troubleshooting Hazardous Service ProceduresReliaTel Control System Status Checkout Procedure TroubleshootingMethod System FailureResetting Cooling and Heating Lockouts Heat FailureCool Failure Zone Temperature Sensor ZTS Service Indicator Clogged Filter SwitchFan Failure Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPTest System Mode and Fan Selection Testing serial communication voltageProgrammable & Digital Zone Sensor Test Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7