Trane WC-IOM-7 manual Live Electrical Components, Compressor Crankcase Heaters Optional

Page 33

Installation

Electrical Phasing

(Three Phase Motors)

The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A, B, C.

Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model

45 Phase Sequence Indicator and following the steps below:

Turn the field supplied disconnect switch that provides power to the main power terminal block or to the “Line” side of the optional factory mounted disconnect switch to the “Off” position.

Connect the phase sequence indicator leads to the terminal block or to the “Line” side of the optional factory mounted disconnect switch as follows;

Black (phase A) to L1

Red (phase B) to L2

Yellow (phase C) toL3

Close the field supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit.

￿WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.

Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires.

Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator.

Compressor Crankcase Heaters (Optional)

Each compressor can be equipped with a crankcase heater. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor

WC-IOM-7 • Packaged Heat Pump

33

Image 33
Contents December Packaged Heat PumpModel Number Description Contains Refrigerant Hazardous Voltage w/CapacitorsEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information General Information Clogged Filter Switch OptionalRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalPower Exhaust Control Optional Compressor Disable CPR1/2Low Pressure Control High Pressure Control OptionalZone Sensor Module ZSM BAYSENS007B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BRemote Zone Sensor BAYSENS013C High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016ASmoke Detector Sensor Optional Unit InspectionFiberglass Wool First Aid MeasuresStorage Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging If a Curb Accessory Kit is not used InstallationHorizontal Units DuctworkFactory Installed Economizer InstallationMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsCondensate Drain Configuration Filter InstallationField Installed Power Wiring Standard Wiring Main Unit PowerOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyField Installed Control Wiring Control Power TransformerHazardous Voltage Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Electrical Phasing Three Phase Motors Live Electrical ComponentsCompressor Crankcase Heaters Optional ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Economizer Start-Up Start UpRotating Components Compressor Start-UpStart Up Heating Start-UpScroll Compressors Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceReturn Air Smoke Detector Maintenance Cooling SeasonFilters Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log Troubleshooting Hazardous Service ProceduresReliaTel Control System Status Checkout Procedure TroubleshootingMethod System FailureResetting Cooling and Heating Lockouts Heat FailureCool Failure Zone Temperature Sensor ZTS Service Indicator Clogged Filter SwitchFan Failure Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPTest System Mode and Fan Selection Testing serial communication voltageProgrammable & Digital Zone Sensor Test Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7