Trane WC-IOM-7 manual Pre-Start, Test Modes

Page 35

Pre-Start

Test Modes

There are three methods in which the “Test” mode can be cycled at LTB-Test 1 and LTB-Test 2.

1.Step Test Mode - This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds.

For the initial start-up of the unit, this method allows the technician to cycle a component “On” and have up to one hour to complete the check.

2.Resistance Test Mode - This method can be used for start-up providing a decade box for variable resistance outputs is available. This method initiates the different components of the unit, one at a time, when a specific resistance value is placed across the two test terminals. The unit will remain in the specific test mode for approximately one hour even though the resistance is left on the test terminals.

3.Auto Test Mode - This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System" control method.

For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 5.

Table 5.

Service test guide for component operation

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST

 

 

Econ

 

 

 

 

 

STEP

MODE

Fan

(Note 2)

Comp 1

Comp 2

Heat 1

Heat 2

Ohms

 

 

 

 

 

 

 

 

 

 

1

 

Fan

On

Minimum

Off

Off

Off

2.2K

 

 

 

 

 

Position Off

 

 

 

 

 

 

 

 

 

Setpoint 0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

On

Selectable

Off

Off

Off

Off

 

 

 

Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Economizer

On

Open

Off

Off

Off

Off

3.3K

 

 

Test Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Cool Stage 1

On

Minimum

(Note 1)

Off

Off

Off

4.7K

 

 

 

 

Position

On

 

 

 

 

 

 

 

 

 

 

 

 

 

4

(Note 3) Cool Stage 2

On

Minimum

(Note 1)

(Note 1)

Off

Off

6.8K

 

 

 

 

Position

On

On

 

 

 

 

 

 

 

 

 

 

 

 

5

(Note 3) Reheat

On

Minimum

On

On

Off

Off

33K

 

 

 

 

 

 

 

 

 

6

(Note 3) Heat Stage 1

On

Minimum

Off

Off

On

Off

10K

 

 

 

 

 

 

 

 

 

7

(Note 3) Heat Stage 2

On

Minimum

Off

Off

On

On

15K

Notes:

1 - The condenser fans will operate any time a compressor is "On" providing the outdoor air temperatures are within the operating values. 2 - The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.

3 - Steps for optional accessories and non-applicable modes in unit will be skipped.

WC-IOM-7 • Packaged Heat Pump

35

Image 35
Contents December Packaged Heat PumpModel Number Description Equipment Damage From Ultraviolet UV Lights Contains RefrigerantHazardous Voltage w/Capacitors Contents Contents Model Number Description General Information Rtom ReliaTel Options Module Optional Clogged Filter Switch OptionalGeneral Information Rlci ReliaTel LonTalk Communication Interface OptionalHigh Pressure Control Optional Compressor Disable CPR1/2Power Exhaust Control Optional Low Pressure ControlZone Sensor BAYSENS011B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS007B Zone Sensor Module ZSM BAYSENS009BRemote Zone Sensor BAYSENS016A High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS013C Remote Zone Sensor BAYSENS014CSmoke Detector Sensor Optional Unit InspectionStorage Fiberglass WoolFirst Aid Measures Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging Ductwork InstallationIf a Curb Accessory Kit is not used Horizontal UnitsLow Voltage Wiring AC & DC Requirements InstallationFactory Installed Economizer Main Electrical Power RequirementsField Installed Power Wiring Condensate Drain ConfigurationFilter Installation Use Copper Conductors Only Main Unit PowerStandard Wiring Optional Tbue Wiring Through the Base Electrical OptionHazardous Voltage Field Installed Control WiringControl Power Transformer Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Compressor Crankcase Heaters Optional Electrical Phasing Three Phase MotorsLive Electrical Components ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Compressor Start-Up Start UpEconomizer Start-Up Rotating ComponentsScroll Compressors Start UpHeating Start-Up Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceFilters Return Air Smoke Detector MaintenanceCooling Season Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log ReliaTel Control TroubleshootingHazardous Service Procedures System Status Checkout Procedure TroubleshootingMethod System FailureCool Failure Resetting Cooling and Heating LockoutsHeat Failure Fan Failure Switch Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPProgrammable & Digital Zone Sensor Test Test System Mode and Fan SelectionTesting serial communication voltage Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7