Trane WC-IOM-7 manual Start Up, Heating Start-Up, Scroll Compressors

Page 39

Start Up

Scroll Compressors

a.Once each compressor has started, verify that the rotation is correct. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed.

b.If the electrical phasing is correct, before condemning a compressor, interchange any two leads (at the compressor Terminal block) to check the internal phasing. Refer to the following illustration for the compressor terminal/phase identification. If the compressor runs backward for an extended period (15 to 30 minutes), the motor winding can overheat and cause the motor winding thermostat to open.

Figure 15.

c.Check the compressor oil levels. The oil level in each compressor sight glass should be 1/2 to 3/4 full when they are “Off”.

Note: The scroll compressor uses Trane OIL-42 without substitution. The appropriate oil charge for a 9 and 10 Ton scroll compressor is 8 pints. For a 14 and 15 Ton scroll compressor, use 14 pints.

2.After the compressor and condenser fan have started and operated for approximately 30 minutes, observe the operating pressures. Compare the operating pressures to the operating pressure curve in the Service Facts.

3.Check system superheat. Follow the instruction listed on the superheat charging curve in the Service Facts.

Superheat should be within ±5 F of the superheat chart value.

4.Repeat steps 1 through 4 for each refrigerant circuit.

5.To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable).

Heating Start-Up

1.Clamp an amp meter around one of 1st stage heater power wires at the heater contactor.

WC-IOM-7 • Packaged Heat Pump

39

Image 39
Contents December Packaged Heat PumpModel Number Description Contains Refrigerant Hazardous Voltage w/CapacitorsEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information Rtom ReliaTel Options Module Optional Clogged Filter Switch OptionalGeneral Information Rlci ReliaTel LonTalk Communication Interface OptionalHigh Pressure Control Optional Compressor Disable CPR1/2Power Exhaust Control Optional Low Pressure ControlZone Sensor BAYSENS011B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS007B Zone Sensor Module ZSM BAYSENS009BRemote Zone Sensor BAYSENS016A High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS013C Remote Zone Sensor BAYSENS014CSmoke Detector Sensor Optional Unit InspectionFiberglass Wool First Aid MeasuresStorage Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging Ductwork InstallationIf a Curb Accessory Kit is not used Horizontal UnitsLow Voltage Wiring AC & DC Requirements InstallationFactory Installed Economizer Main Electrical Power RequirementsCondensate Drain Configuration Filter InstallationField Installed Power Wiring Use Copper Conductors Only Main Unit PowerStandard Wiring Optional Tbue Wiring Through the Base Electrical OptionField Installed Control Wiring Control Power TransformerHazardous Voltage Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Electrical Phasing Three Phase Motors Live Electrical ComponentsCompressor Crankcase Heaters Optional ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Compressor Start-Up Start UpEconomizer Start-Up Rotating ComponentsStart Up Heating Start-UpScroll Compressors Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceReturn Air Smoke Detector Maintenance Cooling SeasonFilters Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log Troubleshooting Hazardous Service ProceduresReliaTel Control System Status Checkout Procedure TroubleshootingMethod System FailureResetting Cooling and Heating Lockouts Heat FailureCool Failure Zone Temperature Sensor ZTS Service Indicator Clogged Filter SwitchFan Failure Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPTest System Mode and Fan Selection Testing serial communication voltageProgrammable & Digital Zone Sensor Test Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7