Trane WC-IOM-7 manual System Failure, Method

Page 49

Troubleshooting

LED 4 (Service)

“On” indicates a clogged filter.

“Off” during normal operation.

“Flashing” indicates an evaporator fan failure

Below is the complete listing of failure indication causes.

System Failure

Check the voltage between terminals 6 and 9 on J6, it should read approximately 32 VDC. If no voltage is present, a System failure has occurred. Refer to Step 4 in the previous section for the recommended troubleshooting procedure.

Cooling Failure

1.Cooling and heating set point (slide pot) on the zone sensor has failed. Refer to the “Zone Sensor Test Procedure” section.

2.Zone temperature thermistor ZTEMP on ZTS failed. Refer to the “Zone Sensor Test Procedure” section.

3.CC1 or CC2 24 VAC control circuit has opened, check CC1 & CC2 coils, and any of the controls below that apply to the unit (HPC1, HPC2).

4.LPC1 has opened during the 3 minute minimum “on time” during 4 consecutive compressor starts, check LPC1 or LPC2 by testing voltage between the J1-8 & J3-2 terminals on the RTRM and ground. If 24 VAC is present, the LPC’s has not tripped. If no voltage is present, LPC’s has tripped.

Service Failure

5.If the supply fan proving switch has closed, the unit will not operate (when connected to RTOM), check the fan motor, belts, and proving switch.

6.Clogged filter switch has closed, check the filters.

Simultaneous Heat and Cool Failure

1.Emergency Stop is activated.

Method 2

The second method for determining system status is done by checking voltage readings at the RTRM (J6). The system indication descriptions and the approximate voltages are listed below.

System Failure

Measure the voltage between terminals J6-9 & J6-6.

Normal Operation = approximately 32 VDC

System Failure = less than 1 VDC, approximately 0.75 VDC

WC-IOM-7 • Packaged Heat Pump

49

Image 49
Contents December Packaged Heat PumpModel Number Description Hazardous Voltage w/Capacitors Contains RefrigerantEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information General Information Clogged Filter Switch OptionalRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalPower Exhaust Control Optional Compressor Disable CPR1/2Low Pressure Control High Pressure Control OptionalZone Sensor Module ZSM BAYSENS007B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BRemote Zone Sensor BAYSENS013C High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016ASmoke Detector Sensor Optional Unit InspectionFirst Aid Measures Fiberglass WoolStorage Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging If a Curb Accessory Kit is not used InstallationHorizontal Units DuctworkFactory Installed Economizer InstallationMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsFilter Installation Condensate Drain ConfigurationField Installed Power Wiring Standard Wiring Main Unit PowerOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyControl Power Transformer Field Installed Control WiringHazardous Voltage Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Live Electrical Components Electrical Phasing Three Phase MotorsCompressor Crankcase Heaters Optional ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Economizer Start-Up Start UpRotating Components Compressor Start-UpHeating Start-Up Start UpScroll Compressors Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceCooling Season Return Air Smoke Detector MaintenanceFilters Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log Hazardous Service Procedures TroubleshootingReliaTel Control System Status Checkout Procedure TroubleshootingMethod System FailureHeat Failure Resetting Cooling and Heating LockoutsCool Failure Clogged Filter Switch Zone Temperature Sensor ZTS Service IndicatorFan Failure Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPTesting serial communication voltage Test System Mode and Fan SelectionProgrammable & Digital Zone Sensor Test Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7