Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the maintenance section of this manual for instructions.

Verify that a condensate trap is installed and the piping is properly sized and pitched.

Verify that the correct size and number of filters are in place.

Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit.

Voltage Imbalance

Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit.

Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:

% Voltage Imbalance =

100AV VD⎞ ⎝ -----------------------⎠

AV

where Average Voltage (AV);

AV=

Volt1 + Volt2 + Volt3

-------------------------------

3---------------------------------

V1, V2, V3 = Line Voltage Readings

VD = Line Voltage reading that deviates the farthest from the average voltage.

Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:

221 + 230 + 227 2.2percent

----------------------------------------------= 3

VD (reading farthest from average) = 221

The percentage of Imbalance equals:

100226 2212.2percent ----------------------------⎠ =

226

The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment.

32

Packaged Heat Pump • WC-IOM-7

Image 32
Contents Packaged Heat Pump DecemberModel Number Description Equipment Damage From Ultraviolet UV Lights Contains RefrigerantHazardous Voltage w/Capacitors Contents Contents Model Number Description General Information Clogged Filter Switch Optional General InformationRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalCompressor Disable CPR1/2 Power Exhaust Control OptionalLow Pressure Control High Pressure Control OptionalLead/Lag Control Dual Circuit Only Zone Sensor Module ZSM BAYSENS007BZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BHigh Temperature Sensor BAYFRST001A Remote Zone Sensor BAYSENS013CRemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016AUnit Inspection Smoke Detector Sensor OptionalStorage Fiberglass WoolFirst Aid Measures Unit Clearances Unit Dimensions Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 TonUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Heavy Objects Improper Unit LiftRigging Installation If a Curb Accessory Kit is not usedHorizontal Units DuctworkInstallation Factory Installed EconomizerMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsField Installed Power Wiring Condensate Drain ConfigurationFilter Installation Main Unit Power Standard WiringOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyHazardous Voltage Field Installed Control WiringControl Power Transformer Controls using 24 VAC Rtrm Smoke Detector Customer Low Voltage Wiring Smoke detector wiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Compressor Crankcase Heaters Optional Electrical Phasing Three Phase MotorsLive Electrical Components ReliaTel Controls Pre-Start Test ModesPre-Start Verifying Proper Air Flow Units with Belt Drive Indoor FanReturn Air Smoke Detector Start Up Economizer Start-UpRotating Components Compressor Start-UpScroll Compressors Start UpHeating Start-Up Final System Setup Maintenance Fan Belt Adjustment Belt Drive UnitsMaintenance Monthly Maintenance Hazardous VoltageFilters Return Air Smoke Detector MaintenanceCooling Season Coil Cleaning Heating SeasonHazardous Pressures Final ProcessSample maintenance log ReliaTel Control TroubleshootingHazardous Service Procedures Troubleshooting System Status Checkout ProcedureSystem Failure MethodCool Failure Resetting Cooling and Heating LockoutsHeat Failure Fan Failure Switch Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Test Cooling Set Point CSP and Heating Set Point HSP ZtempProgrammable & Digital Zone Sensor Test Test System Mode and Fan SelectionTesting serial communication voltage ReliaTel Refrigeration Module Rtrm Default Chart Unit Operation without a Zone SensorUnit Economizer Control ECA Troubleshooting ReliaTel Control Wiring Diagrams Drawing Number DescriptionWarranty Heat PumpWarranty Page WC-IOM-7