Troubleshooting
Unit Economizer Control (ECA) Troubleshooting
ReliaTel Control
Table 10. Verify economizer status by economizer actuator (ECA) LED indicator:
OFF: | No Power or Failure | |
|
| |
ON: | Normal, OK to Economize | |
|
| |
Slow Flash: | Normal, Not OK to Economize | |
|
|
|
|
| 1/2 Second On / 2 Seconds Off: |
Fast Flash - |
| |
Error Code: | ||
|
|
|
|
| Communications Failure |
|
| |
Pulse Flash: | 2 Second On / 1/2 Second Off: | |
|
|
|
|
| Error Code: |
|
|
|
1 | Flash: | Actuator Fault |
|
|
|
2 | Flashes: | CO2 Sensor |
|
|
|
3 | Flashes: | RA Humidity Sensor |
|
|
|
4 | Flashes: | RA Temp Sensor |
|
|
|
5 | Flashes: | OA Quality Sensor |
|
|
|
6 | Flashes: | OA Humidity Sensor |
|
|
|
7 | Flashes: | OA Temp Sensor |
|
|
|
8 | Flashes: | MA Temp Sensor |
|
|
|
9 | Flashes: | RAM Fault |
|
| |
10 Flashes: | ROM Fault | |
|
| |
11 Flashes: | EEPROM Fault | |
|
|
|
55 |