Installation

starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase.

When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.

Before starting the unit in the “Cooling” mode, set the system switch to the “Off” position and turn the main power disconnect to the “On” position and allow the crankcase heater to operate a minimum of 8 hours.

Before closing the main power disconnect switch, insure that the “System” selection switch is in the “Off” position and the “Fan” selection switch is in the “Auto” position.

Close the main power disconnect switch and the unit mounted disconnect switch, if applicable.

￿WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.

ReliaTel Controls

Upon power initialization, the RTRM performs self-diagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The Liteport LED located on the RTRM module is turned “On” within one second of power-up if internal operation is okay.

Use one of the following “Test” procedure to bypass some time delays and to start the unit at the control panel. Each step of unit operation can be activated individually by temporarily shorting across the “Test” terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated. The unit can be left in any “Test” step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the “System” control.

34

Packaged Heat Pump • WC-IOM-7

Image 34
Contents Packaged Heat Pump DecemberModel Number Description Hazardous Voltage w/Capacitors Contains RefrigerantEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information Rlci ReliaTel LonTalk Communication Interface Optional Clogged Filter Switch OptionalGeneral Information Rtom ReliaTel Options Module OptionalLow Pressure Control Compressor Disable CPR1/2Power Exhaust Control Optional High Pressure Control OptionalZone Sensor Module ZSM BAYSENS009B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS007B Zone Sensor BAYSENS011BRemote Zone Sensor BAYSENS014C High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS013C Remote Zone Sensor BAYSENS016AUnit Inspection Smoke Detector Sensor OptionalFirst Aid Measures Fiberglass WoolStorage Unit Clearances Unit Dimensions Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 TonUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Heavy Objects Improper Unit LiftRigging Horizontal Units InstallationIf a Curb Accessory Kit is not used DuctworkMain Electrical Power Requirements InstallationFactory Installed Economizer Low Voltage Wiring AC & DC RequirementsFilter Installation Condensate Drain ConfigurationField Installed Power Wiring Optional Tbue Wiring Through the Base Electrical Option Main Unit PowerStandard Wiring Use Copper Conductors OnlyControl Power Transformer Field Installed Control WiringHazardous Voltage Controls using 24 VAC Rtrm Smoke Detector Customer Low Voltage Wiring Smoke detector wiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Live Electrical Components Electrical Phasing Three Phase MotorsCompressor Crankcase Heaters Optional ReliaTel Controls Pre-Start Test ModesPre-Start Verifying Proper Air Flow Units with Belt Drive Indoor FanReturn Air Smoke Detector Rotating Components Start UpEconomizer Start-Up Compressor Start-UpHeating Start-Up Start UpScroll Compressors Final System Setup Maintenance Fan Belt Adjustment Belt Drive UnitsMaintenance Monthly Maintenance Hazardous VoltageCooling Season Return Air Smoke Detector MaintenanceFilters Coil Cleaning Heating SeasonHazardous Pressures Final ProcessSample maintenance log Hazardous Service Procedures TroubleshootingReliaTel Control Troubleshooting System Status Checkout ProcedureSystem Failure MethodHeat Failure Resetting Cooling and Heating LockoutsCool Failure Clogged Filter Switch Zone Temperature Sensor ZTS Service IndicatorFan Failure Switch Test Cooling Set Point CSP and Heating Set Point HSP ZtempTesting serial communication voltage Test System Mode and Fan SelectionProgrammable & Digital Zone Sensor Test ReliaTel Refrigeration Module Rtrm Default Chart Unit Operation without a Zone SensorUnit Economizer Control ECA Troubleshooting ReliaTel Control Wiring Diagrams Drawing Number DescriptionWarranty Heat PumpWarranty Page WC-IOM-7