Trane WC-IOM-7 manual Final System Setup

Page 40

Start Up

2.ReliaTel Control

Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST start-up procedure for each compressor circuit.

Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started.

3.Verify that the heater stage is operating properly.

4.Clamp an amp meter around one of 2nd stage heater power wires at the heater contactor (if applicable).

5.ReliaTel Control

Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST start-up procedure for each compressor circuit. Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started.

6.Verify that the heater stage is operating properly

7.To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure.

Final System Setup

After completing all of the pre-start and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling & heating), perform these final checks before leaving the unit:

Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel.

Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone Temperature” settings for automatic operation are correct.

Inspect the unit for misplaced tools, hardware, and debris.

Verify that all exterior panels including the control panel doors and condenser grilles are secured in place.

Close the main disconnect switch or circuit protector switch that provides the supply power to the unit’s terminal block or the unit mounted disconnect switch.

40

Packaged Heat Pump • WC-IOM-7

Image 40
Contents Packaged Heat Pump DecemberModel Number Description Hazardous Voltage w/Capacitors Contains RefrigerantEquipment Damage From Ultraviolet UV Lights Contents Contents Model Number Description General Information Clogged Filter Switch Optional General InformationRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalCompressor Disable CPR1/2 Power Exhaust Control OptionalLow Pressure Control High Pressure Control OptionalLead/Lag Control Dual Circuit Only Zone Sensor Module ZSM BAYSENS007BZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BHigh Temperature Sensor BAYFRST001A Remote Zone Sensor BAYSENS013CRemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016AUnit Inspection Smoke Detector Sensor OptionalFirst Aid Measures Fiberglass WoolStorage Unit Clearances Unit Dimensions Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 TonUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Heavy Objects Improper Unit LiftRigging Installation If a Curb Accessory Kit is not usedHorizontal Units DuctworkInstallation Factory Installed EconomizerMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsFilter Installation Condensate Drain ConfigurationField Installed Power Wiring Main Unit Power Standard WiringOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyControl Power Transformer Field Installed Control WiringHazardous Voltage Controls using 24 VAC Rtrm Smoke Detector Customer Low Voltage Wiring Smoke detector wiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Live Electrical Components Electrical Phasing Three Phase MotorsCompressor Crankcase Heaters Optional ReliaTel Controls Pre-Start Test ModesPre-Start Verifying Proper Air Flow Units with Belt Drive Indoor FanReturn Air Smoke Detector Start Up Economizer Start-UpRotating Components Compressor Start-UpHeating Start-Up Start UpScroll Compressors Final System Setup Maintenance Fan Belt Adjustment Belt Drive UnitsMaintenance Monthly Maintenance Hazardous VoltageCooling Season Return Air Smoke Detector MaintenanceFilters Coil Cleaning Heating SeasonHazardous Pressures Final ProcessSample maintenance log Hazardous Service Procedures TroubleshootingReliaTel Control Troubleshooting System Status Checkout ProcedureSystem Failure MethodHeat Failure Resetting Cooling and Heating LockoutsCool Failure Clogged Filter Switch Zone Temperature Sensor ZTS Service IndicatorFan Failure Switch Test Cooling Set Point CSP and Heating Set Point HSP ZtempTesting serial communication voltage Test System Mode and Fan SelectionProgrammable & Digital Zone Sensor Test ReliaTel Refrigeration Module Rtrm Default Chart Unit Operation without a Zone SensorUnit Economizer Control ECA Troubleshooting ReliaTel Control Wiring Diagrams Drawing Number DescriptionWarranty Heat PumpWarranty Page WC-IOM-7