Troubleshooting

Test 3

System Mode and Fan Selection

The combined resistance of the Mode selection switch and the Fan selection switch can be measured between terminals 2 and 4 on the Zone Sensor. The possible switch combinations are listed on the following page with their corresponding resistance values.

Test 4

LED Indicator Test, (SYS ON, HEAT, COOL & SERVICE)

Method 1

Testing the LED using a meter with diode test function. Test both forward and reverse bias. Forward bias should measure a voltage drop of 1.5 to 2.5 volts, depending on your meter. Reverse bias will show an Over Load, or open circuit indication if LED is functional.

Method 2

Testing the LED with an analog Ohmmeter. Connect Ohmmeter across LED in one direction, then reverse the leads for the opposite direction. The LED should have at least 100 times more resistance in reverse direction, as compared with the forward direction. If high resistance in both directions, LED is open. If low in both directions, LED is shorted.

Method 3

To test LED’s with ZSM connected to unit, test voltages at LED terminals on ZSM. A measurement of 32 VDC, across an unlit LED, means the LED has failed.

Note: Measurements should be made from LED common (ZSM terminal 6 to respective LED terminal). Refer to the Zone Sensor Module (ZSM) Terminal Identification table at the beginning of this section.

Programmable & Digital Zone Sensor Test

Testing serial communication voltage

1.Verify 24 VAC is present between terminals J6-14 & J6-11.

2.Disconnect wires from J6-11 and J6-12. Measure the voltage between J6-11 and J6-12, should be about 32 VDC.

3.Reconnect wires to terminals J6-11 and J6-12. Measure voltage again between J6-11 and J6-12, voltage should flash high and low every 0.5 seconds. The voltage on the low end will measure about 19 VDC, while the voltage on the high end will measure from approximately 24 to 38 VDC.

WC-IOM-7 • Packaged Heat Pump

53

Image 53
Contents December Packaged Heat PumpModel Number Description Equipment Damage From Ultraviolet UV Lights Contains RefrigerantHazardous Voltage w/Capacitors Contents Contents Model Number Description General Information General Information Clogged Filter Switch OptionalRlci ReliaTel LonTalk Communication Interface Optional Rtom ReliaTel Options Module OptionalPower Exhaust Control Optional Compressor Disable CPR1/2Low Pressure Control High Pressure Control OptionalZone Sensor Module ZSM BAYSENS007B Lead/Lag Control Dual Circuit OnlyZone Sensor Module ZSM BAYSENS009B Zone Sensor BAYSENS011BRemote Zone Sensor BAYSENS013C High Temperature Sensor BAYFRST001ARemote Zone Sensor BAYSENS014C Remote Zone Sensor BAYSENS016ASmoke Detector Sensor Optional Unit InspectionStorage Fiberglass WoolFirst Aid Measures Unit Clearances Unit Dimensions Unit Dimensional Data 12 1/2 Ton, 15 Ton Unit DimensionsUnit Dimensional Data 20 Ton Horizontal Duct Dimensional Data 12 1/2 Ton, 15 Ton Improper Unit Lift Heavy ObjectsRigging If a Curb Accessory Kit is not used InstallationHorizontal Units DuctworkFactory Installed Economizer InstallationMain Electrical Power Requirements Low Voltage Wiring AC & DC RequirementsField Installed Power Wiring Condensate Drain ConfigurationFilter Installation Standard Wiring Main Unit PowerOptional Tbue Wiring Through the Base Electrical Option Use Copper Conductors OnlyHazardous Voltage Field Installed Control WiringControl Power Transformer Controls using 24 VAC Rtrm Smoke detector wiring Smoke Detector Customer Low Voltage WiringInstallation Space Temperature Averaging Temperature vs. Resistance Voltage Imbalance Compressor Crankcase Heaters Optional Electrical Phasing Three Phase MotorsLive Electrical Components ReliaTel Controls Test Modes Pre-StartVerifying Proper Air Flow Units with Belt Drive Indoor Fan Pre-StartReturn Air Smoke Detector Economizer Start-Up Start UpRotating Components Compressor Start-UpScroll Compressors Start UpHeating Start-Up Final System Setup Fan Belt Adjustment Belt Drive Units MaintenanceMonthly Maintenance Hazardous Voltage MaintenanceFilters Return Air Smoke Detector MaintenanceCooling Season Heating Season Coil CleaningFinal Process Hazardous PressuresSample maintenance log ReliaTel Control TroubleshootingHazardous Service Procedures System Status Checkout Procedure TroubleshootingMethod System FailureCool Failure Resetting Cooling and Heating LockoutsHeat Failure Fan Failure Switch Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Ztemp Test Cooling Set Point CSP and Heating Set Point HSPProgrammable & Digital Zone Sensor Test Test System Mode and Fan SelectionTesting serial communication voltage Unit Operation without a Zone Sensor ReliaTel Refrigeration Module Rtrm Default ChartUnit Economizer Control ECA Troubleshooting ReliaTel Control Drawing Number Description Wiring DiagramsHeat Pump WarrantyWarranty Page WC-IOM-7