12.3 Automatic Operation
•Automatic operation can be set using remote control.
•This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
•After judged the temperature, the operation mode is determined by referring to the below standard.
Intake Air | ↑ | |
23°C | ||
Temperature | ||
↓ | ||
|
Cooling Operation
Soft Dry Operation
•Then, the unit starts to operate at determined operation mode, until it is switched off using remote control, with the setting temperature as shown in table below.
| Setting Temperature (Standard) |
Cooling Operation | 25°C |
Soft Dry Operation | 22°C |
•The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as shown in table below by pressing the temperature up or temperature down button at remote control.
|
|
| Cooling | Soft Dry |
Higher | Æ | +2°C | 27°C | 24°C |
Standard | Æ | ±0°C | 25°C | 22°C |
Lower | Æ | 23°C | 20°C |
•The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the circuit of JX03 at indoor unit’s printed circuit board.
Intake Air | ↑ | |
25°C | ||
Temperature | ||
↓ | ||
|
Cooling Operation
Soft Dry Operation
| Setting Temperature (Standard) |
|
|
Cooling Operation | 27°C |
|
|
Soft Dry Operation | 24°C |
|
|
31