12.5 Outdoor Fan Speed Control
•There is only one speed for outdoor fan motor. (Applicable for
•There is 2 speeds for outdoor fan motor. Outdoor fan speed can be changed to Hi or Lo according to outdoor temperature. (Applicable for
•For Cooling and Soft Dry operation, when outdoor temperature reaches to 31°C
•When air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
•Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
12.6 Vertical Airflow Direction Control
12.6.1Auto Control
•When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the diagram.
•When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
•During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the louver will stop swinging.
Closing position / 148°
Horizontal
Upper limit/0°
Upper limit for cooling mode
28° and soft dry mode/17°
Swing up and down
Lower limit for cooling mode and soft dry mode/45°
12.6.2Manual Control
•When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow direction louver move up and down in the range shown in the diagram.
•The louver can be adjusted by pressing the button to the desired louver position.
•When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
|
| Horizontal |
| |
|
|
| ||
|
| Upper limit / 0° | ||
|
| |||
Closing | 17° Upper limit for | |||
position | 22° | cooling mode and | ||
/ 148° | soft dry mode | |||
| ||||
|
| 28° |
| |
|
| 33° |
|
39° Lower limit for cooling mode and soft dry mode
34