Installation of Diffuser and Remote Panel (TSCP)
NOTE
The location of the discharge diffuser and the TSCP Space Heat Remote Panel are critical for optimum performance of the Greenheat™ System.
1. Install Diffuser
Using
Airflow |
| Diffuser Height (feet) | ||
(cfm) | Minimum |
| Recommended | Maximum |
|
|
|
|
|
4000 | 15 |
| 20 | 25 |
|
|
|
|
|
6000 | 15 |
| 20 | 25 |
|
|
|
|
|
8000 | 20 |
| 30 | |
|
|
|
|
|
10000 | 20 |
| 35 | |
|
|
|
|
|
13000 - | 25 |
| 40 | |
| ||||
20000 |
| |||
|
|
|
| |
|
|
|
|
|
2. Install TSCP
When installing the TSCP Space Heat Remote Panel, the location is critical to performance of the Greenheat™ System. The TSCP should be installed five to six feet above the floor. It is recommended that the TSCP be installed on an outside wall, in the space, and close to any source of infiltration such as dock doors. DO NOT install the TSCP in the blast area of the heater or near any other source of heat.
Important
DO NOT install the TSCP in the blast area of the space heater or near any other source of heat.
Recommended
TSCP Location
Blast Area
Indoor Mounted
Unit
TSCP Location
h
Rooftop
Unit
h
Rooftop Diffuser Height
6 DGX Industrial Space Heating
®