COMPRESSOR CHECKS

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

Locked Rotor Voltage (L.R.V.) Test

Locked rotor voltage (L.R.V.) is the actual voltage available at the compressor under a stalled condition.

Single Phase Connections

Disconnect power from unit. Using a voltmeter, attach one lead of the meter to the run “R” terminal on the compressor and the other lead to the common “C” terminal of the com- pressor. Restore power to unit.

Determine L.R.V.

Start the compressor with the volt meter attached; then stop the unit. Attempt to restart the compressor within a couple of seconds and immediately read the voltage on the meter. The compressor under these conditions will not start and will usually kick out on overload within a few seconds since the pressures in the system will not have had time to equalize. Voltage should be at or above minimum voltage of 197 VAC, as specified on the rating plate. If less than minimum, check for cause of inadequate power supply; i.e., incorrect wire size, loose electrical connections, etc.

Amperage (L.R.A.) Test

The running amperage of the compressor is the most important of these readings. A running amperage higher than that indicated in the performance data indicates that a problem exists mechanically or electrically.

Single Phase Running and L.R.A. Test

NOTE: Consult the specification and performance section for running amperage. The L.R.A. can also be found on the rating plate.

Select the proper amperage scale and clamp the meter probe around the wire to the “C” terminal of the compressor.

Turn on the unit and read the running amperage on the meter. If the compressor does not start, the reading will indicate the locked rotor amperage (L.R.A.).

Overloads

The compressor is equipped with either an external or internal overload which senses both motor amperage and winding temperature. High motor temperature or amperage heats the overload causing it to open, breaking the common circuit within the compressor.

Heat generated within the compressor shell, usually due to recycling of the motor, is slow to dissipate. It may take anywhere from a few minutes to several hours for the overload to reset.

Checking the Overloads

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

WARNING

BURN HAZARD

Certain unit components operate at temperatures hot enough to cause burns.

Proper safety procedures must be followed, and proper protective clothing must be worn.

Failure to follow this warning could result in moderate to serious injury.

External Overloads

With power off, remove the leads from compressor terminals. If the compressor is hot, allow the overload to cool before starting check. Using an ohmmeter, test continuity across the terminals of the external overload. If you do not have continuity; this indicates that the overload is open and must be replaced.

Interrnal Overloads

Some model compressors are equipped with an internal overload. The overload is embedded in the motor windings to sense the winding temperature and/or current draw. The overload is connected in series with the common motor terminal.

Should the internal temperature and/or current draw become excessive, the contacts in the overload will open, turning off the compressor. The overload will automatically reset, but may require several hours before the heat is dissipated.

Checking the Internal Overload

1.With no power to unit, remove the leads from the compressor terminals.

2.Using an ohmmeter, test continuity between terminals C-S and C-R. If no continuity, the compressor overload is open and the compressor must be replaced.

46

Image 47
Contents Heat Pump Volt YS10M10 Cool OnlyCool with Electric Heat Heat Pump with Electric HeatTable Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Repair Hazards Property Damage Hazards Model and Serial Number Location IntroductionUnit Identification Performance Data SpecificationsInstallation Information / Sleeve Dimensions Fire Hazard Electrical DataElectric Shock Hazard Make sure the wiring is adequate for your unit Control Panel Operation Special Functions System Exit Back FAN Mode Speed Display Schedule Enter Key Sequence Action Digital Control Panels Access Codes SummaryRemote Control Operation Remote Control Operation Introduction Electronic Control System MaintenanceElectronic Control System Maintenance Operation Following functions Can be Tested Test mode BypassesFactory USE only To Clear Error Codes’ HistoryFront Panel Unit OperationSystem Set Point Mapping Figure COOL-HEAT SET PointsCompressor Operation Electronic Control Sequence of OperationHeat Control Heat Pump Only Heating Mode Control OperationCondition Heat Pump With Electric Heat OperationElectric Heat Operation in Cool with Electric Heat Units Compressor Lock Out Time Fan Mapping Unit Operation with a WALL-STAT During Heat ModeRemoving the Front Cover Swing Out Replacing the Indoor Coil ThermistorConnecting a Remote Wall Thermostat Remote Wall Thermostat Location Capacitor Connections Components TestingCapacitors Capacitor Check with Capacitor AnalyzerDrain PAN Valve Testing the Heating Element Electric Shock HazardHeating Element Heating Element Heat Pump ModelsRefrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRisk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckMetering Device Check ValveReversing Valve DESCRIPTION/OPERATION Checking the Reversing Valve Testing the Reversing Valve Solenoid CoilReversing Valve in Heating Mode Explosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Checking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Compressor ReplacementRecommended procedure for compressor replacement High Pressure Hazard Routine Maintenance Clearances Sleeve / DrainDecorative Front Cover Standard Filter Cleaning Installation Instructions Battery type Lithium, 3 Volts, #CR2450 Control Panel Battery Change ProcedureService and Assistance Room AIR Conditioner Unit Performance Test Data Sheet Icon Error Codes and Alarm StatusProblem Possible Cause Possible Solution Troubleshooting TipsTroubleshooting Tips Problem Possible Cause Possible Solution Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check Possible Cause Possible Solution Problem Possible Cause Possible Solution Bad outdoor coil thermistor Replace thermistor Heat / Cool only Room AIR Conditioners Troubleshooting TipsProblem Possible Cause Action Heat Pump Room AIR Conditioners Trouble Shooting TipsTroubleshooting Chart Heat Pump YES Electrical Troubleshooting Chart Heat PumpSystem Cools When Heating is Desired Heat PumpMalfunction of Valve Normal Function of ValveDischarge Electronic Control Board Components IdentificationCool W/O Electric Heat Remote Wall Thermostat Wiring DiagramsKuhl Electronic Control Cool only Models SchematicSL28M30A, SL36M30A ES12M33A, ES15M33A EM18M34A, EM24M34A KUHL+ Electronic Control Cool with Electric Heat ModelsEL36M35A KUHL+ Electronic Control Cool with Electric Heat ModelYS10M10A KUHL+ Electronic Control Heat Pump only ModelHeat YL24M35A KUHL+ Electronic Control Heat Pump with Electric Heat ModelThis Table Applies to All Thermistors THERMISTORS’ Resistance ValuesReplacement Remote Control Configuration Instructions Checking the Remote Control’s OPT # Code Replacement Instructions Aham PUB. NO. RAC-1 DAY Cooling Load Estimate FormHeat Gain from Quantity Factors Heat Load Form Following is an example using the heat load formInfiltration Windows & Doors AVG Heating Load Form Friedrich Room Unit Heat PumpsWindows & Doors Area, sq. ft Room AIR Conditioners Limited Warranty Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 32 pages 34.87 Kb Manual 47 pages 33.75 Kb Manual 16 pages 9.01 Kb Manual 32 pages 56.71 Kb

R-410A specifications

Friedrich R-410A is an advanced refrigerant widely used in HVAC (Heating, Ventilation, and Air Conditioning) systems, known for its high efficiency and environmental friendliness. As a hydrofluorocarbon (HFC) blend, R-410A has become the preferred alternative to R-22, which is being phased out due to its ozone-depleting potential. One of the main features of R-410A is its high latent heat of vaporization, which allows for efficient heat transfer and improved cooling performance in air conditioning units.

Technologically, R-410A operates at higher pressures than older refrigerants, meaning systems designed for R-410A need to be built with more robust components to safely handle these pressures. This results in a more compact system design that offers enhanced performance and reliability. The dual-component nature of R-410A—composed of difluoromethane (R-32) and pentafluoroethane (R-125)—provides an optimal balance of thermodynamic properties, leading to superior energy efficiency, especially in variable speed applications.

In terms of characteristics, R-410A has a higher cooling capacity, which enables HVAC systems to effectively cool larger spaces or run more efficiently when cooling smaller areas. The refrigerant is non-toxic and non-flammable, which enhances safety during its use. In addition, R-410A has a lower global warming potential relative to other refrigerants, making it a more environmentally responsible choice for modern cooling systems.

Moreover, R-410A systems typically require less refrigerant charge due to their efficiency, contributing to reduced greenhouse gas emissions. The adoption of R-410A aligns with regulatory trends aimed at minimizing the environmental impact of refrigerants in cooling applications.

Overall, the Friedrich R-410A refrigerant embodies a combination of technology and environmental stewardship, making it a cornerstone of contemporary HVAC design. Its ability to provide effective and energy-efficient cooling solutions while being compliant with modern environmental regulations positions R-410A as the refrigerant of choice for engineers and installers focused on sustainability and performance in air conditioning systems.