INSTALLATION
TABLE A.1 - CABLE SIZES FOR COMBINED LENGTHS OF COPPER ELECTRODE
AND WORK CABLES
| Up to 50 ft | 50 - 100 ft | 100 - 150 ft | 150 - 200 ft | 200 - 250 ft |
Machine Size | (15 m) | (15 - 30 m) | (30 - 46 m) | (46 - 61 m) | (67 - 76 m) |
400 Amp | 3/0 | 3/0 | 3/0 | 3/0 | 4/0 |
(100% Duty | 85 mm2 | 85 mm2 | 85 mm2 | 85 mm2 | 107 mm2 |
Cycle) |
|
|
|
|
|
500 Amp | 2/0 | 2/0 | 3/0 | 3/0 | 4/0 |
(50% Duty | 67 mm2 | 67 mm2 | 85 mm2 | 85 mm2 | 107 mm2 |
Cycle) |
|
|
|
|
|
|
|
|
|
|
|
Return to Section TOC
Return to Section TOC
Return to Master TOC
Return to Master TOC
WIRE FEEDER CONNECTIONS
See the Accessories section of this manual for spe- cific instructions on connecting the following semi- automatic and automatic wire feeders to the Idealarc
Automatic Wire Feeders:
•
•
•
•
•
•
•
CONNECTIONS FOR STICK, TIG, OR AIR/CARBON ARC CUTTING OPERA- TIONS
The work and electrode cables for stick, TIG, or air/carbon arc cutting are connected as described ear- lier, under the heading Output Connections. A TIG torch is connected to the electrode (+) terminal of the welder. Select cable size according to Table A.1.
WARNING
Do not connect a TIG torch and stick electrode cable at the same time. They will both be electrically HOT.
If the Idealarc
However, the Idealarc
Return to Section TOC
Return to Master TOC
WARNING
The output terminals are energized at all times when the Idealarc