INSTALLATION | ||
|
|
|
AUXILIARY POWER WhILE WELDING
Simultaneous welding and power loads are permitted by following Table I. The permissible currents shown assume that current is being drawn from either the 120V or 240V supply (not both at the same time). Also, the “Output Control” is set at “10” for maximum auxiliary power.
TAbLE I
SIMULTANEOUS WELDING AND POWER
Output Selector | Permissible Power | Permissible Auxiliary |
| ||
| Setting | Watts (Unity Power | Current in Amperes | ||
|
| Factor) | @ 120V | ||
|
|
|
|
| |
Max. Stick or Wire |
|
|
|
| |
Feed Setting | None | 0 | 0 |
| |
|
|
|
|
|
|
145 | Stick Setting | 4500 | 38** | 23 |
|
|
|
|
|
|
|
90 | Stick Setting | 6500 | 54** | 27 |
|
|
|
|
|
| |
No Welding | 9500 | 80** | 40 |
| |
|
|
|
|
|
|
*Each duplex receptacle is limited to 20 amps.
**Not to exceed 40A per 120VAC branch circuit when splitting the 240 VAC output.
***Use of 3 Phase AC Power is not recommended while welding
STANDbY POWER CONNECTIONS
The RANGER® 3 PHASE is suitable for temporary, standby, or emergency power using the engine manu- facturer’s recommended maintenance schedule.
The RANGER® 3 PHASE can be permanently installed as a standby power unit for
WARNING
(Connections must be made by a licensed electri- cian who can determine how the 120/240V power can be adapted to the particular installation and comply with all applicable electrical codes.) The following information can be used as a guide by the electrician for most applications (refer also to the connection diagram shown in Figure A.1.)
1.Install a double pole, double throw switch between the power company meter and the premises dis- connect.
Switch rating must be the same or greater than the customer’s premises disconnect and service over- current protection.
2.Take necessary steps to assure load is limited to the capacity of the RANGER® 3 PHASE by installing a 40 amp 240V double pole circuit break- er. Maximum rated load for the 240V auxiliary is 40 amperes. Loading above 40 amperes will reduce output voltage below the allowable
3.Install a 50 amp 120/240V plug (NEMA type
4.Plug this cable into the 50 amp 120/240V recepta- cle on the RANGER® 3 PHASE case front.
RANGER® 3 PhASE