Troubleshooting
Table 9 provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact your dealer or Customer Service.
Table 9 Fault Messages
Fault |
|
|
|
|
Number | Message | Fault Type | Cause | Solution |
|
|
|
|
|
F0 | Unit is too hot and has shut | Automatic | FET1 Over Temperature | Clear the fault and attempt restart. Ensure |
| down. See guide. |
| Shutdown | adequate ventilation around the Freedom |
|
|
|
| SW 3000. Reduce AC loads. |
|
|
|
|
|
F2 | Unit is too hot and has shut | Automatic | FET2 Over Temperature | Clear the fault and attempt restart. Ensure |
| down. See guide. |
| Shutdown | adequate ventilation around the Freedom |
|
|
|
| SW 3000. Reduce AC loads. |
|
|
|
|
|
F3 | Unit is too hot and has shut | Automatic | Transformer Over | Clear the fault and attempt restart. Ensure |
| down. See guide. |
| Temperature Shutdown | adequate ventilation around the Freedom |
|
|
|
| SW 3000. Reduce AC loads. |
|
|
|
|
|
F4 | Battery | Automatic | Battery Over Temperature | Clear the fault and attempt restart. Stop |
| has shut down. See guide. |
| Shutdown | charging, check battery voltage and |
|
|
|
| temperature. Check for excessive ambient |
|
|
|
| temperature and adequate ventilation in |
|
|
|
| the battery compartment. |
|
|
|
|
|
F5 | is too hot and has shut | Automatic | Ambient Over Temperature | Clear the fault and attempt restart. Ensure |
| down. See guide. |
| Shutdown | adequate ventilation around Freedom SW |
|
|
|
| 3000. Reduce AC loads. |
|
|
|
|
|