Battery Charging Reference
Battery Charger Interruption
If battery charging is interrupted in bulk charge (for example, AC is disconnected, or a fault occurs), the unit will return to bulk charge when battery charging resumes.
If battery charging is interrupted in any stage other than bulk, the unit will go to float charge when battery charging resumes.
However, a new bulk charge cycle is initiated when battery charging begins, if:
•the battery drops below 12.5 Vdc for 15 minutes (VF2) i.e., the
•7 days have passed from the time the charger completed Absorption (ΔTF).
60 | Freedom SW 3000 Owner’s Guide |