Second System Setup Screen

Once the settings have been entered into the initial System Setup Screen, press F3 to access the next set of configurable system settings. The second system setup screen (Figure 14) will be shown.

Figure 14: Second System Setup Screen

This screen will allow you to set the following feature:

Station Demand Debounce- This is the minimum amount of time in seconds before the demand signal is recognized by the system. Values can be set between 0.5 and 2.0.

Once the values have been entered for the settings listed above, the operator can choose to do the following:

Press the F5 key once while in this screen to view and set the Debounce settings for Stations 4-6. If the F5 key is pressed again while in the Debounce settings for Stations 4-6, the screen will display and allow the operator to set the Debounce settings for Stations 7-9.

Return to the Main Menu (Press F6).

Third System Setup Screen

Once the Debounce settings have been entered into the second System Setup Screen, press F3 to access the next system setting. The third (really the fifth) system setup screen (Figure 15) will be shown.

Figure 15: Third System Setup Screen

This screen will allow you to set the Alarm Silence Duration. This feature is the length of time (in minutes) before an alarm horn will reactivate while in an alarm condition. The value can be set between 1 and 50.

Once the value has been entered for the setting listed above, the operator can choose to do the following:

Return to the Initial System Setup Screen (Press F5).

Return to the Main Menu (Press F6).

1 –Pump 9-Station Controller

Chapter 3: Installation

27 of 38

Image 28
Contents SCC 1-Pump 9-Station Controller Parts and Service Department Shipping Information Unpacking and InspectionEvent of Shipping Damage If the Shipment is Not CompleteReturns Warranty ReturnsCredit Returns Table of Contents Configurable Settings How to Use This Manual SafetySafety Symbols Used in this Manual Controller Safety Tags Description Wear Safety Glasses and Work Gloves Responsibility General ResponsibilityReporting a Safety Defect Maintenance ResponsibilityOperator Responsibility Models Covered in This Manual Functional DescriptionGeneral Description Standard Features Mechanical FeaturesElectrical Features Controller FeaturesOptional Features Safety Devices and InterlocksSafety Circuit Standards Fail Safe OperationSafety Device Lock-Outs Installation Making Control Panel Power Drop Wiring ConnectionsUncrating Mounting the Control PanelConnecting the Control Panel to Vacuum Hoppers Connecting the Control Panel to the Pump PackageBasic Menus and Setup of Controller SetupActivating and Deactivating the System Viewing System Status Name DescriptionStation Setup Initial Station Setup ScreenEntering Values Into Controller Fields Controller KeypadSecond Station Setup Screen Third Station Setup Screen Pump Setup Initial Pump Setup ScreenSecond Pump Setup Screen Third Pump Setup Screen System Setup Initial System Setup ScreenSecond System Setup Screen Third System Setup ScreenAlarms OperationOverview Starting and Stopping the SystemPump Fault General FaultAll Faults Filter CanMaintenance Configurable Settings Options for Station SetupOptions for Pump Setup Troubleshooting General TroubleshootingStation Alarms Pump AlarmsWarranty Warranty SpecificationsWarranty Restrictions AppendixOptional Components Warranty LiabilitiesCustomer Responsibilities Drawings and Diagrams Spare Parts ListController Identification Serial Number Tag Technical Assistance Contact Information