Sterling Plumbing 822.00247.00 specifications Pump Fault, Filter Can, General Fault, All Faults

Page 30

Pump Fault

If the pump verify signal is not present after the pump is started, the alarm horn/light will activate. The pump will be stopped and set to an offline condition. The Status screen will display “PMP FLT.” Pressing F2 while the status screen is displayed will silence the alarm.

Filter Can

If the filter can limit switch signal is not present after the pump is started, the alarm horn/light will activate. The Status screen will display “FLTR CAN”. Pressing F2 while the status screen is displayed will silence the alarm.

General Fault

If the general fault signal is present after the pump is started, the alarm horn/light will activate. The pump will be stopped and set to an offline condition. The Status screen will display “GEN FLT.” Pressing F2 while the status screen is displayed will silence the alarm.

All Faults

If after silencing an alarm, the condition remains beyond the time specified for ALARM SILENCE DURATION, the alarm horn/light will reactivate. Pressing F2 from the status screen will silence the alarm.

1 –Pump 9-Station Controller

Chapter 4: Operation

29 of 38

Image 30
Contents SCC 1-Pump 9-Station Controller Parts and Service Department Event of Shipping Damage Shipping InformationUnpacking and Inspection If the Shipment is Not CompleteWarranty Returns ReturnsCredit Returns Table of Contents Configurable Settings Safety How to Use This ManualSafety Symbols Used in this Manual Controller Safety Tags Description Wear Safety Glasses and Work Gloves Responsibility General ResponsibilityMaintenance Responsibility Reporting a Safety DefectOperator Responsibility Functional Description Models Covered in This ManualGeneral Description Electrical Features Standard FeaturesMechanical Features Controller FeaturesSafety Circuit Standards Optional FeaturesSafety Devices and Interlocks Fail Safe OperationSafety Device Lock-Outs Uncrating InstallationMaking Control Panel Power Drop Wiring Connections Mounting the Control PanelConnecting the Control Panel to Vacuum Hoppers Connecting the Control Panel to the Pump PackageSetup Basic Menus and Setup of ControllerActivating and Deactivating the System Viewing System Status Name DescriptionStation Setup Initial Station Setup ScreenEntering Values Into Controller Fields Controller KeypadSecond Station Setup Screen Third Station Setup Screen Pump Setup Initial Pump Setup ScreenSecond Pump Setup Screen Third Pump Setup Screen System Setup Initial System Setup ScreenSecond System Setup Screen Third System Setup ScreenOverview AlarmsOperation Starting and Stopping the SystemAll Faults Pump FaultGeneral Fault Filter CanMaintenance Configurable Settings Options for Station SetupOptions for Pump Setup Troubleshooting General TroubleshootingStation Alarms Pump AlarmsWarranty Restrictions WarrantyWarranty Specifications AppendixWarranty Liabilities Optional ComponentsCustomer Responsibilities Drawings and Diagrams Spare Parts ListController Identification Serial Number Tag Technical Assistance Contact Information