Description of Operation

Figure 13: Econ state operation (occupied mode and auto fan)

Econ Mech State (State 1)

The Econ Mech state is a “normal” state during Cool mode. The Econ Mech state typically is active in the Cool mode when primary cooling (economizer) alone is not adequate to meet the cooling requirements and both primary cooling and secondary cooling (compressor) are available.

When the Econ Mech state becomes active, the OA damper is set to 100% open, and the UVC uses the units mechanical cooling capabilities as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on page 26).

The UVC monitors the DAT to ensure it does not fall below MCLL.

Figure 14: Econ mech state operation (occupied mode and auto fan)

Mech State (State 2)

The Mech state is a “normal” state during Cool mode. The Mech state typically is active in the Cool mode when primary cooling (economizer) is not available and secondary cooling (compressor) is available.

When the Mech state becomes active, the UVC uses the unit’s mechanical cooling capabilities as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on page 26). If cooling is not required while in the Mech state, the UVC can “idle” in the Mech state until cooling is required or until there is a call to switch to another mode or state.The UVC monitors the DAT to ensure it does not fall below MCLL.

20

McQuay OM 751

Image 20
Contents Date November DX Cooling Only Software Model UV05Group Applied Systems UVC Configuration Parameters IntroductionGetting Started Description of OperationDescription Manual # Model-specific unit ventilator installation literatureAccessory-specific installation literature Extreme temperature can damage system components Software program literatureDescription Acronym Abr Acronyms/AbbreviationsAcronyms and abbreviations OCS Using the Keypad/Display Display FormatKeypad Functions Security LevelsMode Key ON/STOP Key and LEDFAN Key Arrow KeysUsing the Keypad/Display Viewing Actual Indoor Air Temperature IATMenu Reference Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesOFF Mode State UVC state names and numbersNormal UVC modes State names DecimalNight Purge Mode State Fan Only Mode State aCant Heat State State D Emergency Heat Mode Super StateFull Heat State State Heat State State Auto ModeHeat Mode Super State Cant Heat State State B Cool Mode Super StateLow Limit State State E Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateSpecial Purpose Unit Modes Discharge Air DA Heat State StateLow Limit State State F Cant Cool State State CPressurize Mode Depressurize ModePurge Mode Shutdown ModeUnit Mode Priority Special purpose UVC unit mode priorityNormal UVC mode priority Priority resultOccupied Mode Unoccupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Space Temperature Set Points Networked Space Temperature Sensor CapabilityNetworked Set Point Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsEffective set point calculations Set point calculation examplesExample a Example B Given Discharge Air Temperature Control Proportional Integral PI Control LoopsPI loop list PI loopsPI Control Parameters Proportional BandOccupied, Standby, and Bypass Operation Indoor Air Fan OperationIntegral Time Outdoor Air Damper Operation OA temp sensor Space humidity Economizer enableEconomizer Networked Space Humidity Sensor Capability Networked Outdoor Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityCompressor Operation Ashrae CycleCompressor Envelope Compressor Cooling LockoutCompressor Minimum On and Off Timers Compressor Start DelayFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationUnoccupied Input Signal Remote Shutdown Input SignalVentilation Lockout Input Signal External Binary InputsExhaust Interlock Input Signal Lights On/Off SignalFault Signal External Binary OutputsExhaust Fan ON/OFF Signal Auxiliary Heat SignalAuxiliary heat start/stop calculation Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardPriority Fault description Reset Keypad Alarm and Fault MonitoringAlarm and fault code summary DX Pressure Fault F1 Compressor Envelope Fault F2Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Condensate Overflow Indication optional F4 Space Coil DX Temp Sensor Failure F5Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceTroubleshooting Carbon Dioxide CO2 Sensors Humidity versus voltageCO2 versus voltage table RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty