Page 10

Getting Started

Figure 5: Changing a keypad/display menu item

Table 7: Keypad/display menu item list

Display

Keypad menu item list

Abr.

Description

RO

05

Default

RW1

 

 

 

 

 

 

 

rA

Reset Alarm Input

 

Enter 1 to clear alarms (clears all inactive alarms, except filter alarm). To enable

RW

x

//2

 

 

 

the alarm again, enter 0.

 

 

 

HC

UVC (Heat/Cool) Mode

UVCM

Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg.

RO

x

 

Output

Heat, 9 = Fan Only

 

 

UVC State Output

 

Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 =

 

 

 

St

 

UVCS

Heat, 6 = ActiveDehum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11

RO

x

 

 

 

 

= Heat Mode Cant Heat, 12 = CantCool, 13 = Emerg Heat Mode Cant Heat, 14 =

 

 

 

 

 

 

Heat Mode Low Limit, 15 = Cool Mode Low Limit

 

 

 

d0

Discharge Air Temp Set

DATS

Display current DA temperature set point.

RO

x

 

point Output

 

d1

OutputDischarge Air Temp

DAT

Display current DA temperature.

RO

x

 

d2

Ventilation Cooling Low

VCLL

Adjust economizer cooling DA temperature low limit.

RW

x

54°F

Limit set point

(12°C)

d3

Mechanical Cooling Low

MCLL

Adjust mechanical cooling DA temperature low limit.

RW

x

45°F

Limit set point

(7°C)

SL

Slave Type Configuration

 

Set slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave

 

 

 

 

 

follows master). This feature requires a network over which the master and slave

RW

x

0

 

 

 

UVCs can communicate.

 

 

 

Eo

OutputEffective Occupancy

 

Display current occupancy.

RO

x

 

o(

Occupancy Override

 

Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting

 

 

//2

Input

 

this variable is intended only for troubleshooting. Once you are done, cycle unit

RW

x

 

 

 

power to clear this variable and return the UVC to normal operation.

 

 

 

(o

Occupied Cooling set

OCS

Adjust occupied cooling set point.

RW

x

73.4°F

point

(23°C)

(S

Standby Cooling Set

SCS

Adjust standby cooling set point.

RW

x

77°F

point

(25°C)

(U

Unoccupied Cooling Set

UCS

Adjust unoccupied cooling set point.

RW

x

82.4°F

point

(28°C)

ko

Occupied Heating Set

OHS

Adjust occupied heating set point.

RW

x

69.8°F

point

(21°C)

kS

Standby Heating Set

SHS

Adjust standby heating set point.

RW

x

66.2°F

point

(19°C)

kU

Unoccupied Heating Set

UHS

Adjust unoccupied heating set point.

RW

x

60.8°F

point

(16°C)

rS

Wall Sensor Type

 

Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F.

RW

x

0

o1

Outside Air Damper

OADP

Display OA damper position.

RO

x

 

Position Output

 

o2

OAD Min Position High-

OADH

Adjust OA damper minimum position with IAF at high speed. (This variable is

RW

x

20%

Speed Set point

factory set to 5% open when the unit is ordered with optional CO DCV.)

 

 

 

2

 

 

 

o3

OAD Min Position Med-

 

Adjust OA damper minimum position with IAF at medium speed. (This variable is

 

 

 

Speed Set point

OADM

not used when the optional CO2 DCV is enabled. Only OADH is active as the OA

RW

x

25%

 

 

 

damper minimum regardless of fan speed.)

 

 

 

o4

OAD Min Position Low-

 

Adjust OA damper minimum position with IAF at low speed. (This variable is not

 

 

 

Speed Set point

OADL

used when the optional CO2 DCV is enabled. Only OADH is active as the OA

RW

x

30%

 

 

 

damper minimum regardless of fan speed.)

 

 

 

10

McQuay OM 751

Image 10
Contents Group Applied Systems DX Cooling Only Software Model UV05Date November Getting Started UVC Configuration ParametersIntroduction Description of OperationAccessory-specific installation literature Model-specific unit ventilator installation literatureDescription Manual # Extreme temperature can damage system components Software program literatureAcronyms and abbreviations Acronyms/AbbreviationsDescription Acronym Abr OCS Keypad Functions Using the Keypad/DisplayDisplay Format Security LevelsFAN Key Mode KeyON/STOP Key and LED Arrow KeysMenu Reference Using the Keypad/DisplayViewing Actual Indoor Air Temperature IAT Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesNormal UVC modes State names OFF Mode StateUVC state names and numbers DecimalNight Purge Mode State Fan Only Mode State aFull Heat State State Emergency Heat Mode Super StateCant Heat State State D Heat Mode Super State Auto ModeHeat State State Low Limit State State E Cool Mode Super StateCant Heat State State B Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateLow Limit State State F Special Purpose Unit ModesDischarge Air DA Heat State State Cant Cool State State CPurge Mode Pressurize ModeDepressurize Mode Shutdown ModeNormal UVC mode priority Unit Mode PrioritySpecial purpose UVC unit mode priority Priority resultStandby Mode Occupied ModeUnoccupied Mode Occupancy mode priorityAdditional Occupancy Features Networked Set Point Capability Space Temperature Set PointsNetworked Space Temperature Sensor Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsExample a Example B Given Set point calculation examplesEffective set point calculations PI loop list Discharge Air Temperature ControlProportional Integral PI Control Loops PI loopsPI Control Parameters Proportional BandIntegral Time Indoor Air Fan OperationOccupied, Standby, and Bypass Operation Outdoor Air Damper Operation Economizer Economizer enableOA temp sensor Space humidity CO2 Demand Controlled Ventilation optional Networked Space Humidity Sensor CapabilityNetworked Outdoor Humidity Sensor Capability Networked Space CO2 Sensor CapabilityCompressor Envelope Compressor OperationAshrae Cycle Compressor Cooling LockoutFloating-Point Actuator Auto-Zero, Overdrive and Sync Compressor Minimum On and Off TimersCompressor Start Delay Outdoor Air Fan OperationVentilation Lockout Input Signal Unoccupied Input SignalRemote Shutdown Input Signal External Binary InputsFault Signal Exhaust Interlock Input SignalLights On/Off Signal External Binary OutputsAuxiliary heat start/stop calculation Exhaust Fan ON/OFF SignalAuxiliary Heat Signal Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardAlarm and fault code summary Alarm and Fault MonitoringPriority Fault description Reset Keypad Space Temp Sensor Failure F0 DX Pressure Fault F1Compressor Envelope Fault F2 Discharge Air DX Cooling Low Limit Indication F3Outdoor Temp Sensor Failure F6 Condensate Overflow Indication optional F4Space Coil DX Temp Sensor Failure F5 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceCO2 versus voltage table Troubleshooting Carbon Dioxide CO2 SensorsHumidity versus voltage RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty