UVC Configuration Parameters

Configuration Parameter Name

Abr.

Notes

Default

LUI Menu

Item1

 

 

 

 

Primary Cool Proportional Band

 

 

18°F (10°C)

 

 

 

 

 

 

Primary Cool Integral Time

 

 

180 sec

 

 

 

 

 

 

Secondary Cool Proportional Band

 

 

18°F (10°C)

 

 

 

 

 

 

Secondary Cool Integral Time

 

 

600 sec

 

 

 

 

 

 

Discharge Air Temp Proportional Band

 

 

4°F (2.22°C)

 

 

 

 

 

 

Discharge Air Temp Integral Time

 

 

300 sec

 

 

 

 

 

 

CO2 Proportional Band2

 

 

100 PPM

 

CO Integral Time2

 

 

600 sec

 

2

 

 

 

 

 

 

 

 

Ventilation Cooling Low Limit Setpoint

VCLL

discharge air low limit during ventilation or economizer cooling

54°F (12°C)

d2

 

 

 

 

 

Mechanical Cooling Low Limit Setpoint

MCLL

discharge air low limit during mechanical (compressor) cooling

45°F (7°C)

d3

 

 

 

 

 

Discharge Air High Limit

DAHL

 

140°F (60°C)

 

 

 

 

 

 

Space Fan Off Delay

 

 

30 sec

 

 

 

 

 

 

Fan Cycling Configuration

 

space fan operation during occupied, standby and bypass

2

CF

 

 

occupancy modes: 2 = continuous, 3 = cycle

 

 

 

 

Space Fan Speed Changes Per Hour

 

example: 6/60min = 10min (maximum of 1 fan speed change every

6

 

 

 

10min when fan in auto)

 

 

 

 

 

Space Fan Run Time Reset

 

reset total run time: 1 = reset (you must return the variable back to

0

 

 

 

0 after reset)

 

 

 

 

 

Compressor Run Time Reset

 

reset total run time: 1 = reset (you must return the variable back to

0

 

 

 

0 after reset)

 

 

 

 

 

Compressor Enable

 

0 = disable, 1 = enable

1

C!

 

 

 

 

 

Compressor Minimum On Time

 

 

180 sec

 

 

 

 

 

 

Compressor Minimum Off Time

 

 

300 sec

 

 

 

 

 

 

Compressor Cooling Lockout Setpoint

CCLO

OA temperature below which compressor cooling is not allowed

63.5°F (17.5°C)

 

 

 

 

 

 

Compressor Envelope Cool Max In

 

 

120°F (48.89°C)

 

 

 

 

 

 

Compressor Envelope Cool Min In

 

 

28°F (-2.22°C)

 

 

 

 

 

 

Compressor Envelope Cool Max Out

 

 

160°F (71.11°C)

 

 

 

 

 

 

Compressor Envelope Cool Min Out

 

 

40°F (4.44°C)

 

 

 

 

 

 

Compressor Envelope Cool Max Ratio

 

 

0.00

 

 

 

 

 

 

Compressor Envelope Cool Max Offset

 

 

88°F (48.89°C)

 

 

 

 

 

 

Compressor Envelope Cool Min Ratio

 

 

0.0

 

 

 

 

 

 

Compressor Envelope Cool Min Offset

 

 

-4°F (-2.22°C)

 

 

 

 

 

 

Auxiliary Heat Start Differential

AHSD

degrees above auxiliary heat start point where auxiliary heat ends

2°F (1°C)

A1

 

 

 

 

 

Auxiliary Heat End Differential

AHED

degrees above auxiliary heat start point where auxiliary heat ends

2°F (1°C)

A2

 

 

 

 

 

Auxiliary Heat Configuration

 

0 = normally open heat device (hot water valve, etc.),

0

A3

 

 

1 = normally closed heat device (electric heat, etc.)

 

 

 

 

Space Humidity Sensor Enable2

 

0 = disable, 1 = enable (this variable will be factory set to 1 when

0

 

 

 

the unit is ordered with optional humidity sensor)

 

 

 

 

 

Outdoor Humidity Sensor Enable2

 

0 = disable, 1 = enable (this variable will be factory set to 1 when

0

 

 

 

the unit is ordered with optional humidity sensor)

 

 

 

 

 

48

McQuay OM 751

Image 48
Contents DX Cooling Only Software Model UV05 Group Applied SystemsDate November UVC Configuration Parameters IntroductionGetting Started Description of OperationModel-specific unit ventilator installation literature Accessory-specific installation literatureDescription Manual # Extreme temperature can damage system components Software program literatureAcronyms/Abbreviations Acronyms and abbreviationsDescription Acronym Abr OCS Using the Keypad/Display Display FormatKeypad Functions Security LevelsMode Key ON/STOP Key and LEDFAN Key Arrow KeysUsing the Keypad/Display Viewing Actual Indoor Air Temperature IATMenu Reference Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesOFF Mode State UVC state names and numbersNormal UVC modes State names DecimalNight Purge Mode State Fan Only Mode State aEmergency Heat Mode Super State Full Heat State StateCant Heat State State D Auto Mode Heat Mode Super StateHeat State State Cool Mode Super State Low Limit State State ECant Heat State State B Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateSpecial Purpose Unit Modes Discharge Air DA Heat State StateLow Limit State State F Cant Cool State State CPressurize Mode Depressurize ModePurge Mode Shutdown ModeUnit Mode Priority Special purpose UVC unit mode priorityNormal UVC mode priority Priority resultOccupied Mode Unoccupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Space Temperature Set Points Networked Space Temperature Sensor CapabilityNetworked Set Point Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsSet point calculation examples Example a Example B GivenEffective set point calculations Discharge Air Temperature Control Proportional Integral PI Control LoopsPI loop list PI loopsPI Control Parameters Proportional BandIndoor Air Fan Operation Integral TimeOccupied, Standby, and Bypass Operation Outdoor Air Damper Operation Economizer enable EconomizerOA temp sensor Space humidity Networked Space Humidity Sensor Capability Networked Outdoor Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityCompressor Operation Ashrae CycleCompressor Envelope Compressor Cooling LockoutCompressor Minimum On and Off Timers Compressor Start DelayFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationUnoccupied Input Signal Remote Shutdown Input SignalVentilation Lockout Input Signal External Binary InputsExhaust Interlock Input Signal Lights On/Off SignalFault Signal External Binary OutputsExhaust Fan ON/OFF Signal Auxiliary Heat SignalAuxiliary heat start/stop calculation Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardAlarm and Fault Monitoring Alarm and fault code summaryPriority Fault description Reset Keypad DX Pressure Fault F1 Compressor Envelope Fault F2Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Condensate Overflow Indication optional F4 Space Coil DX Temp Sensor Failure F5Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceTroubleshooting Carbon Dioxide CO2 Sensors Humidity versus voltageCO2 versus voltage table RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty