UVC Configuration Parameters
Configuration Parameter Name | Abr. | Notes | Default | LUI Menu | |
Item1 | |||||
|
|
|
| ||
Primary Cool Proportional Band |
|
| 18°F (10°C) |
| |
|
|
|
|
| |
Primary Cool Integral Time |
|
| 180 sec |
| |
|
|
|
|
| |
Secondary Cool Proportional Band |
|
| 18°F (10°C) |
| |
|
|
|
|
| |
Secondary Cool Integral Time |
|
| 600 sec |
| |
|
|
|
|
| |
Discharge Air Temp Proportional Band |
|
| 4°F (2.22°C) |
| |
|
|
|
|
| |
Discharge Air Temp Integral Time |
|
| 300 sec |
| |
|
|
|
|
| |
CO2 Proportional Band2 |
|
| 100 PPM |
| |
CO Integral Time2 |
|
| 600 sec |
| |
2 |
|
|
| ||
|
|
|
|
| |
Ventilation Cooling Low Limit Setpoint | VCLL | discharge air low limit during ventilation or economizer cooling | 54°F (12°C) | d2 | |
|
|
|
|
| |
Mechanical Cooling Low Limit Setpoint | MCLL | discharge air low limit during mechanical (compressor) cooling | 45°F (7°C) | d3 | |
|
|
|
|
| |
Discharge Air High Limit | DAHL |
| 140°F (60°C) |
| |
|
|
|
|
| |
Space Fan Off Delay |
|
| 30 sec |
| |
|
|
|
|
| |
Fan Cycling Configuration |
| space fan operation during occupied, standby and bypass | 2 | CF | |
|
| occupancy modes: 2 = continuous, 3 = cycle | |||
|
|
|
| ||
Space Fan Speed Changes Per Hour |
| example: 6/60min = 10min (maximum of 1 fan speed change every | 6 |
| |
|
| 10min when fan in auto) |
| ||
|
|
|
| ||
Space Fan Run Time Reset |
| reset total run time: 1 = reset (you must return the variable back to | 0 |
| |
|
| 0 after reset) |
| ||
|
|
|
| ||
Compressor Run Time Reset |
| reset total run time: 1 = reset (you must return the variable back to | 0 |
| |
|
| 0 after reset) |
| ||
|
|
|
| ||
Compressor Enable |
| 0 = disable, 1 = enable | 1 | C! | |
|
|
|
|
| |
Compressor Minimum On Time |
|
| 180 sec |
| |
|
|
|
|
| |
Compressor Minimum Off Time |
|
| 300 sec |
| |
|
|
|
|
| |
Compressor Cooling Lockout Setpoint | CCLO | OA temperature below which compressor cooling is not allowed | 63.5°F (17.5°C) |
| |
|
|
|
|
| |
Compressor Envelope Cool Max In |
|
| 120°F (48.89°C) |
| |
|
|
|
|
| |
Compressor Envelope Cool Min In |
|
| 28°F |
| |
|
|
|
|
| |
Compressor Envelope Cool Max Out |
|
| 160°F (71.11°C) |
| |
|
|
|
|
| |
Compressor Envelope Cool Min Out |
|
| 40°F (4.44°C) |
| |
|
|
|
|
| |
Compressor Envelope Cool Max Ratio |
|
| 0.00 |
| |
|
|
|
|
| |
Compressor Envelope Cool Max Offset |
|
| 88°F (48.89°C) |
| |
|
|
|
|
| |
Compressor Envelope Cool Min Ratio |
|
| 0.0 |
| |
|
|
|
|
| |
Compressor Envelope Cool Min Offset |
|
|
| ||
|
|
|
|
| |
Auxiliary Heat Start Differential | AHSD | degrees above auxiliary heat start point where auxiliary heat ends | 2°F (1°C) | A1 | |
|
|
|
|
| |
Auxiliary Heat End Differential | AHED | degrees above auxiliary heat start point where auxiliary heat ends | 2°F (1°C) | A2 | |
|
|
|
|
| |
Auxiliary Heat Configuration |
| 0 = normally open heat device (hot water valve, etc.), | 0 | A3 | |
|
| 1 = normally closed heat device (electric heat, etc.) | |||
|
|
|
| ||
Space Humidity Sensor Enable2 |
| 0 = disable, 1 = enable (this variable will be factory set to 1 when | 0 |
| |
|
| the unit is ordered with optional humidity sensor) |
| ||
|
|
|
| ||
Outdoor Humidity Sensor Enable2 |
| 0 = disable, 1 = enable (this variable will be factory set to 1 when | 0 |
| |
|
| the unit is ordered with optional humidity sensor) |
| ||
|
|
|
|