American Standard UV05 manual Pressurize Mode, Depressurize Mode, Purge Mode, Shutdown Mode

Page 22

Description of Operation

In each of these special purpose UVC modes, if the space temperature drops below EHS and the Emergency Heat function is enabled, the UVC is forced into the Emergency Heat mode (see “Emergency Heat Mode (Super State)” on page 16) and then return once the Emergency Heat function is satisfied.

Table 9: Actions during special purpose unit modes

Action

Indoor air fan

Outdoor air

Exhaust fan

(IAF)

damper (OAD)

output

 

Pressurize

High

100% Open

Off

Depressurize

Off

Closed

On

Purge

High

100% Open

On

Shutdown

Off

Closed

Off

Energy hold off

Off

Closed

Off

Pressurize Mode

When in Pressurize mode, the UVC uses the IAF, OAD, and exhaust output as needed to pressurize the space. The UVC stops all normal heating and cooling but does allow emergency heat if required. The pressurize mode can only be accessed via a network connection.

Depressurize Mode

When in Depressurize mode the UVC will use the IAF, OAD, and exhaust output as needed to depressurize the space. The UVC stops all normal heating and cooling but does allow emergency heat if required. The de-pressurize mode can only be accessed via a network connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).

Purge Mode

When in Purge mode, the UVC uses the IAF, OAD, and exhaust output as needed to purge the space. The UVC stops all normal heating and cooling but does allow emergency heat if required. The purge mode can only be accessed via a network connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).

Shutdown Mode

Shutdown mode is the equivalent of the Off mode, but is an Off mode forced by a network connection. When in Shutdown mode, the UVC stops all normal heating, cooling, ventilation (OA damper is closed), and fan operation. By default emergency heat is not be used during the shutdown mode, however, the UVC can be configured (Emergency Heat Shutdown Configuration) to allow emergency heat operation during shutdown mode. The shutdown mode can be accessed via a network connection, a binary input to the UVC, or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).

WARNING

Shutdown mode and energy hold off mode are a “stop” state for the unit ventilator. It is not a “power off” state.

Energy Hold Off Mode

The UVC supports an energy hold off state, which when active forces the UVC to stop all normal heating, cooling and ventilation. Typically used by a network connection to force the UVC to cease heating, cooling and ventilation when conditions exist where heating, cooling and ventilation are not required or desired. Energy hold off mode is very similar to shutdown mode except that energy hold off always allows emergency heat if required. The energy hold off mode can only be accessed via a network connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).

22

McQuay OM 751

Image 22
Contents Group Applied Systems DX Cooling Only Software Model UV05Date November Getting Started UVC Configuration ParametersIntroduction Description of OperationAccessory-specific installation literature Model-specific unit ventilator installation literatureDescription Manual # Extreme temperature can damage system components Software program literatureAcronyms and abbreviations Acronyms/AbbreviationsDescription Acronym Abr OCS Keypad Functions Using the Keypad/DisplayDisplay Format Security LevelsFAN Key Mode KeyON/STOP Key and LED Arrow KeysMenu Reference Using the Keypad/DisplayViewing Actual Indoor Air Temperature IAT Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesNormal UVC modes State names OFF Mode StateUVC state names and numbers DecimalNight Purge Mode State Fan Only Mode State aFull Heat State State Emergency Heat Mode Super StateCant Heat State State D Heat Mode Super State Auto ModeHeat State State Low Limit State State E Cool Mode Super StateCant Heat State State B Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateLow Limit State State F Special Purpose Unit ModesDischarge Air DA Heat State State Cant Cool State State CPurge Mode Pressurize ModeDepressurize Mode Shutdown ModeNormal UVC mode priority Unit Mode PrioritySpecial purpose UVC unit mode priority Priority resultStandby Mode Occupied ModeUnoccupied Mode Occupancy mode priorityAdditional Occupancy Features Networked Set Point Capability Space Temperature Set PointsNetworked Space Temperature Sensor Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsExample a Example B Given Set point calculation examplesEffective set point calculations PI loop list Discharge Air Temperature ControlProportional Integral PI Control Loops PI loopsPI Control Parameters Proportional BandIntegral Time Indoor Air Fan OperationOccupied, Standby, and Bypass Operation Outdoor Air Damper Operation Economizer Economizer enableOA temp sensor Space humidity CO2 Demand Controlled Ventilation optional Networked Space Humidity Sensor CapabilityNetworked Outdoor Humidity Sensor Capability Networked Space CO2 Sensor CapabilityCompressor Envelope Compressor OperationAshrae Cycle Compressor Cooling LockoutFloating-Point Actuator Auto-Zero, Overdrive and Sync Compressor Minimum On and Off TimersCompressor Start Delay Outdoor Air Fan OperationVentilation Lockout Input Signal Unoccupied Input SignalRemote Shutdown Input Signal External Binary InputsFault Signal Exhaust Interlock Input SignalLights On/Off Signal External Binary OutputsAuxiliary heat start/stop calculation Exhaust Fan ON/OFF SignalAuxiliary Heat Signal Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardAlarm and fault code summary Alarm and Fault MonitoringPriority Fault description Reset Keypad Space Temp Sensor Failure F0 DX Pressure Fault F1Compressor Envelope Fault F2 Discharge Air DX Cooling Low Limit Indication F3Outdoor Temp Sensor Failure F6 Condensate Overflow Indication optional F4Space Coil DX Temp Sensor Failure F5 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceCO2 versus voltage table Troubleshooting Carbon Dioxide CO2 SensorsHumidity versus voltage RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty