American Standard UV05 manual Remote Wall-Mounted Sensor with +/-3F Adjustment optional

Page 27

Description of Operation

Remote Wall-Mounted Sensor with +/–3°F

Adjustment (optional)

When the optional remote wall-mounted sensor with +/–3°F adjustment dial is used, the UVC effectively writes the value of the set point adjustment dial to the Set Point Offset Input variable.

Note – If a network connection is used to adjust the Set Point Offset Input variable, you must not use the optional remote wall-mounted sensor with +/–3°F adjustment.

If the keypad/display is used by room occupants to adjust the Set Point Offset, do not use the optional remote wall-mounted sensor with +/–3°F adjustment.

If you have the optional remote wall-mounted sensor with +/–3°F adjustment and an occupant uses the keypad to make Set Point Offset adjustments, this overrides any +/–3°F adjustment on the optional remote wall-mounted sensor since the keypad/display has higher priority. If you find that changes to the +/–3°F adjustment on the remote wall- mounted sensor have no effect, it is likely that an occupant used the keypad/display to make a Set Point Offset change. Cycle unit power to clear this situation and restore the ability to change the Set Point Offset from the +/–3°F adjustment on the remote wall-mounted sensor.

Remote Wall-Mounted Sensor with 55°F to 85°F

Adjustment (optional)

When the optional remote wall-mounted sensor with 55°F to 85°F adjustment dial is used, the UVC will effectively write the value of the set point dial to the Space Temp Set Point Input variable.

Note – If a network connection is using the Space Temp Set Point Input variable, do not use the optional remote wall-mounted sensor with 55°F to 85°F adjustment.

If it is intended that the LUI will be used by room occupants to adjust the Setpoint Offset, then you must not use the optional remote wall-mounted sensor with 55°F to 85°F adjustment. When using the optional remote wall-mounted sensor with 55°F to 85°F adjustment, the UVC will ignore any Setpoint Offset changes made at the LUI.

Effective Set Point Calculations

The UVC calculates the effective set point (Effective Set Point Output) based on several factors. These factors include the six occupancy set points for heating and cooling (Occupancy Temperature Set Point), occupancy mode, the value of the network variables Space Temp Set Point Input, Set Point Offset Input, and the Set Point Shift Input as well as the optional wall- mounted sensor’s set point adjustment knob. As always, network inputs have priority over hardwired connections.

The UVC determines if heating or cooling is required based on the current unit mode (Heat/ Cool Mode Output) and then calculates the required set point for heating or cooling. After calculating, the Effective Set Point Output network variable is set equal to the calculated set point. The Effective Set Point Output is the temperature set point that the UVC maintains, which normally appears on the keypad/display.

McQuay OM 751

27

Image 27
Contents DX Cooling Only Software Model UV05 Group Applied SystemsDate November Description of Operation UVC Configuration ParametersIntroduction Getting StartedModel-specific unit ventilator installation literature Accessory-specific installation literatureDescription Manual # Software program literature Extreme temperature can damage system componentsAcronyms/Abbreviations Acronyms and abbreviationsDescription Acronym Abr OCS Security Levels Using the Keypad/DisplayDisplay Format Keypad FunctionsArrow Keys Mode KeyON/STOP Key and LED FAN KeyChanging Set Points Using the Keypad/DisplayViewing Actual Indoor Air Temperature IAT Menu ReferenceRW1 Abr Description DefaultChlo State Programming Description of OperationUVC Unit Modes Complete UVC-state diagramDecimal OFF Mode StateUVC state names and numbers Normal UVC modes State namesFan Only Mode State a Night Purge Mode StateEmergency Heat Mode Super State Full Heat State StateCant Heat State State D Auto Mode Heat Mode Super StateHeat State State Cool Mode Super State Low Limit State State ECant Heat State State B Econ State State Cool mode super state diagramMech State State Econ Mech State StateCant Cool State State C Special Purpose Unit ModesDischarge Air DA Heat State State Low Limit State State FShutdown Mode Pressurize ModeDepressurize Mode Purge ModePriority result Unit Mode PrioritySpecial purpose UVC unit mode priority Normal UVC mode priorityOccupancy mode priority Occupied ModeUnoccupied Mode Standby ModeAdditional Occupancy Features Networked Set Point Offset Capability Space Temperature Set PointsNetworked Space Temperature Sensor Capability Networked Set Point CapabilityEffective Set Point Calculations Remote Wall-Mounted Sensor with +/-3F Adjustment optionalSet point calculation examples Example a Example B GivenEffective set point calculations PI loops Discharge Air Temperature ControlProportional Integral PI Control Loops PI loop listProportional Band PI Control ParametersIndoor Air Fan Operation Integral TimeOccupied, Standby, and Bypass Operation Outdoor Air Damper Operation Economizer enable EconomizerOA temp sensor Space humidity Networked Space CO2 Sensor Capability Networked Space Humidity Sensor CapabilityNetworked Outdoor Humidity Sensor Capability CO2 Demand Controlled Ventilation optionalCompressor Cooling Lockout Compressor OperationAshrae Cycle Compressor EnvelopeOutdoor Air Fan Operation Compressor Minimum On and Off TimersCompressor Start Delay Floating-Point Actuator Auto-Zero, Overdrive and SyncExternal Binary Inputs Unoccupied Input SignalRemote Shutdown Input Signal Ventilation Lockout Input SignalExternal Binary Outputs Exhaust Interlock Input SignalLights On/Off Signal Fault SignalStart/Stop Calculation Exhaust Fan ON/OFF SignalAuxiliary Heat Signal Auxiliary heat start/stop calculationExpansion board Inputs and outputs, software model 05-DX cooling onlyAlarm and Fault Monitoring Alarm and fault code summaryPriority Fault description Reset Keypad Discharge Air DX Cooling Low Limit Indication F3 DX Pressure Fault F1Compressor Envelope Fault F2 Space Temp Sensor Failure F0Discharge Air Temp Sensor Failure F7 Condensate Overflow Indication optional F4Space Coil DX Temp Sensor Failure F5 Outdoor Temp Sensor Failure F6Troubleshooting Temperature Sensors Temperature versus resistance Troubleshooting Humidity SensorsRH % VDC mV Troubleshooting Carbon Dioxide CO2 SensorsHumidity versus voltage CO2 versus voltage tableConfiguration Parameter Name Abr Default LUI Menu UVC configuration parameters OMAbr Default LUI Menu OAD Stroke Time Warranty