American Standard UV05 Inputs and outputs, software model 05-DX cooling only, Expansion board

Page 40

UVC Input and Output Table

UVC Input and Output Table

All UVC input and output connections and their corresponding unit ventilator usage are shown in the following table.

Table 21: Inputs and outputs, software model 05—DX cooling only

I/O

Description

BO-1

Inside Fan High

BO-2

Inside Fan Medium

BO-3

Electric Heat 1

BO-4

Electric Heat 2

BO-5

Electric Heat 3

BO-6

External Output Option 2: Fault Indication1

BO-7

 

BO-8

 

BO-9

Compressor2

BI-1

Condensate Overflow

BI-2

 

BI-3

 

BI-4

External Input Option 3:Ventilation Lockout (default) or Exhaust

Interlock3

 

BI-5

External Input Option 2: Remote Shutdown3

BI-6

External Input Option 1: Unoccupied (default)

BI-7

 

BI-8

 

BI-9

 

BI-10

 

BI-11

 

BI-12

DX Press Switch (NC)4

AI-1

IA Temp. Sensor + T.O.

AI-2

Remote Setpt. Adjust. Pot.

AI-3

OA Coil DX Temp Sensor5

AI-4

OA Temp Sensor

AI-5

IA Coil DX Temp Sensor

AI-6

DA Temp Sensor

 

Expansion board

xBO-1

External Output Option 1: Lights On/Off 1

xBO-2

External Output Option 3: Exhaust Fan On/Off (default) or

Auxiliary Heat 1

xBO-3

OA Damper Open

xBO-4

OA Damper Close

xBO-5

 

xBO-6

 

xBO-7

Outdoor Fan5

xBO-8

Inside Fan Low

xAI-1

IA Humidity Sensor6

xAI-2

OA Humidity Sensor6

xAI-3

Indoor CO Sensor6

 

2

xAI-4

 

1.Field selectable external output options (all possible options are shown).

2.This is the condensing unit on/off signal on split-systems.

3.Field selectable external input options (all possible options are shown).

4.DX pressures switch not installed on split-systems; this input is then wired for constant no-fault condition.

5.Not installed or wired on split-systems.

6.Optional.

40

McQuay OM 751

Image 40
Contents Group Applied Systems DX Cooling Only Software Model UV05Date November UVC Configuration Parameters IntroductionGetting Started Description of OperationAccessory-specific installation literature Model-specific unit ventilator installation literatureDescription Manual # Extreme temperature can damage system components Software program literatureAcronyms and abbreviations Acronyms/AbbreviationsDescription Acronym Abr OCS Using the Keypad/Display Display FormatKeypad Functions Security LevelsMode Key ON/STOP Key and LEDFAN Key Arrow KeysUsing the Keypad/Display Viewing Actual Indoor Air Temperature IATMenu Reference Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesOFF Mode State UVC state names and numbersNormal UVC modes State names DecimalNight Purge Mode State Fan Only Mode State aFull Heat State State Emergency Heat Mode Super StateCant Heat State State D Heat Mode Super State Auto ModeHeat State State Low Limit State State E Cool Mode Super StateCant Heat State State B Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateSpecial Purpose Unit Modes Discharge Air DA Heat State StateLow Limit State State F Cant Cool State State CPressurize Mode Depressurize ModePurge Mode Shutdown ModeUnit Mode Priority Special purpose UVC unit mode priorityNormal UVC mode priority Priority resultOccupied Mode Unoccupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Space Temperature Set Points Networked Space Temperature Sensor CapabilityNetworked Set Point Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsExample a Example B Given Set point calculation examplesEffective set point calculations Discharge Air Temperature Control Proportional Integral PI Control LoopsPI loop list PI loopsPI Control Parameters Proportional BandIntegral Time Indoor Air Fan OperationOccupied, Standby, and Bypass Operation Outdoor Air Damper Operation Economizer Economizer enableOA temp sensor Space humidity Networked Space Humidity Sensor Capability Networked Outdoor Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityCompressor Operation Ashrae CycleCompressor Envelope Compressor Cooling LockoutCompressor Minimum On and Off Timers Compressor Start DelayFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationUnoccupied Input Signal Remote Shutdown Input SignalVentilation Lockout Input Signal External Binary InputsExhaust Interlock Input Signal Lights On/Off SignalFault Signal External Binary OutputsExhaust Fan ON/OFF Signal Auxiliary Heat SignalAuxiliary heat start/stop calculation Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardAlarm and fault code summary Alarm and Fault MonitoringPriority Fault description Reset Keypad DX Pressure Fault F1 Compressor Envelope Fault F2Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Condensate Overflow Indication optional F4 Space Coil DX Temp Sensor Failure F5Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceTroubleshooting Carbon Dioxide CO2 Sensors Humidity versus voltageCO2 versus voltage table RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty