American Standard UV05 manual Floating-Point Actuator Auto-Zero, Overdrive and Sync

Page 36

Description of Operation

Compressor Minimum On and Off Timers

The UVC is provided with minimum On (3-minute default) and minimum Off (5-minute default) timers to prevent adverse compressor cycling.

Compressor Start Delay

The UVC is provided with a Compressor Start Delay configuration variable, which is intended to be adjusted as part of the start-up procedure for each unit. This variable is used to delay compressor operation each time the compressor is required.

Note – To prevent strain on a building’s electrical supply system from multiple unit compressors all starting at the same time after a power failure or after an unoccupied-to-occupied changeover, McQuay strongly recommends configuring each unit or groups of units at start-up with different start delays.

Outdoor Air Fan Operation

The UVC is configured with a fan on delay that delays OA fan operation for a time period (10 seconds, default) after the compressor starts. The OA fan stops with the compressor.

Floating-Point Actuator Auto-Zero, Overdrive and Sync

The UVC at power-up auto-zeros all floating-point actuators (OA damper) before going into normal operation to ensure proper positioning. During auto-zero, the unit remains off. The actuators all open approximately 30% and then are driven full closed. The overdrive feature then is used to continue forcing the actuators closed for one full stroke period. Once the zeroing process is complete, normal unit operation begins.

The UVC is configured such that whenever a floating-point actuator is commanded to go to 0% or 100%, the UVC overdrives the actuator one full stroke period past the 0% or 100% position to ensure proper positioning.

Additionally, the UVC is configured to sync all floating-point actuators once every six hours of operation. To do this, the UVC forces the actuator to the closest rail position (0% or 100%), uses the overdrive feature, and then returns to the required position. For example, if the actuator is at 20% when the six-hour limit is reached, the UVC then forces the actuator to 0%, overdrive for one full stroke and then returns to the 20% position.

36

McQuay OM 751

Image 36
Contents DX Cooling Only Software Model UV05 Group Applied SystemsDate November UVC Configuration Parameters IntroductionGetting Started Description of OperationModel-specific unit ventilator installation literature Accessory-specific installation literatureDescription Manual # Extreme temperature can damage system components Software program literatureAcronyms/Abbreviations Acronyms and abbreviationsDescription Acronym Abr OCS Using the Keypad/Display Display FormatKeypad Functions Security LevelsMode Key ON/STOP Key and LEDFAN Key Arrow KeysUsing the Keypad/Display Viewing Actual Indoor Air Temperature IATMenu Reference Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesOFF Mode State UVC state names and numbersNormal UVC modes State names DecimalNight Purge Mode State Fan Only Mode State aEmergency Heat Mode Super State Full Heat State StateCant Heat State State D Auto Mode Heat Mode Super StateHeat State State Cool Mode Super State Low Limit State State ECant Heat State State B Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateSpecial Purpose Unit Modes Discharge Air DA Heat State StateLow Limit State State F Cant Cool State State CPressurize Mode Depressurize ModePurge Mode Shutdown ModeUnit Mode Priority Special purpose UVC unit mode priorityNormal UVC mode priority Priority resultOccupied Mode Unoccupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Space Temperature Set Points Networked Space Temperature Sensor CapabilityNetworked Set Point Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsSet point calculation examples Example a Example B GivenEffective set point calculations Discharge Air Temperature Control Proportional Integral PI Control LoopsPI loop list PI loopsPI Control Parameters Proportional BandIndoor Air Fan Operation Integral TimeOccupied, Standby, and Bypass Operation Outdoor Air Damper Operation Economizer enable EconomizerOA temp sensor Space humidity Networked Space Humidity Sensor Capability Networked Outdoor Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityCompressor Operation Ashrae CycleCompressor Envelope Compressor Cooling LockoutCompressor Minimum On and Off Timers Compressor Start DelayFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationUnoccupied Input Signal Remote Shutdown Input SignalVentilation Lockout Input Signal External Binary InputsExhaust Interlock Input Signal Lights On/Off SignalFault Signal External Binary OutputsExhaust Fan ON/OFF Signal Auxiliary Heat SignalAuxiliary heat start/stop calculation Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardAlarm and Fault Monitoring Alarm and fault code summaryPriority Fault description Reset Keypad DX Pressure Fault F1 Compressor Envelope Fault F2Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Condensate Overflow Indication optional F4 Space Coil DX Temp Sensor Failure F5Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceTroubleshooting Carbon Dioxide CO2 Sensors Humidity versus voltageCO2 versus voltage table RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty