American Standard UV05 manual Unit Mode Priority, Special purpose UVC unit mode priority

Page 23

Description of Operation

Unit Mode Priority

The UVC uses the network variables and binary inputs listed in Table 10 and Table 11 to determine the current unit mode. Special purpose UVC unit modes have higher priority than the normal UVC unit modes as shown in the tables.

Each table lists the highest priority items on the left to the lower priority items to the right. The right-most columns indicate unit operation as a result of the left-most columns. The term “Don’t care” in these tables implies that another network variable or binary input to the left has a higher priority.

Table 10: Special purpose UVC unit mode priority

 

 

 

 

Priority result

 

 

Emergency override

Remote shutdown

Energy hold

Energy hold

Unit mode

Actual UVC action

 

input1

binary input

off input1

off output2

output2

 

 

 

 

De-energized4

Normal

Normal

See

the normal

 

Normal3

UVC mode priority (Table 11)

 

 

 

 

 

Energy hold off

Energy hold off

Off

Off

 

 

 

 

 

Energized5

Don’t care

Energy hold off

Off

Off

 

Pressurize

Don’t care

Don’t care

Don’t care

Off

Pressurize

 

De-pressurize

Don’t care

Don’t care

Don’t care

Off

De-pressurize

 

Purge

Don’t care

Don’t care

Don’t care

Off

Purge

 

Shutdown

Don’t care

Don’t care

Don’t care

Off

Off

 

1.Network input.

2.Network output.

3.Normal indicates the UVC power-up condition.

4.De-energized indicates that the contacts connected to this binary input are open.

5.Energized indicates that the contacts connected to this binary input are closed.

Table 11: Normal UVC mode priority

 

 

 

Priority result

 

Application override

Unit mode override

 

Unit mode output 2

 

input 1

input1

 

 

 

 

Normal (Auto)3

 

Heat

 

 

 

Cool

 

 

 

 

Emergency heat

 

Normal (Auto)3

Heat

Heat

 

Cool

Cool

 

 

Night purge

Night purge

 

 

Off

Off

 

 

Emergency heat

Emergency heat

 

 

Fan only

Fan only

 

Heat

Don’t care

Heat

 

Cool

Don’t care

Cool

 

Night purge

Don’t care

Night purge

 

Off

Don’t care

Off

 

Emergency heat

Don’t care

Emergency heat

 

Fan only

Don’t care

Fan only

 

1.Network input.

2.Network output.

3.Normal (Auto) is the normal UVC power-up state.

McQuay OM 751

23

Image 23
Contents Date November DX Cooling Only Software Model UV05Group Applied Systems Description of Operation UVC Configuration ParametersIntroduction Getting StartedDescription Manual # Model-specific unit ventilator installation literatureAccessory-specific installation literature Software program literature Extreme temperature can damage system componentsDescription Acronym Abr Acronyms/AbbreviationsAcronyms and abbreviations OCS Security Levels Using the Keypad/DisplayDisplay Format Keypad FunctionsArrow Keys Mode KeyON/STOP Key and LED FAN KeyChanging Set Points Using the Keypad/DisplayViewing Actual Indoor Air Temperature IAT Menu ReferenceRW1 Abr Description DefaultChlo State Programming Description of OperationUVC Unit Modes Complete UVC-state diagramDecimal OFF Mode StateUVC state names and numbers Normal UVC modes State namesFan Only Mode State a Night Purge Mode StateCant Heat State State D Emergency Heat Mode Super StateFull Heat State State Heat State State Auto ModeHeat Mode Super State Cant Heat State State B Cool Mode Super StateLow Limit State State E Econ State State Cool mode super state diagramMech State State Econ Mech State StateCant Cool State State C Special Purpose Unit ModesDischarge Air DA Heat State State Low Limit State State FShutdown Mode Pressurize ModeDepressurize Mode Purge ModePriority result Unit Mode PrioritySpecial purpose UVC unit mode priority Normal UVC mode priorityOccupancy mode priority Occupied ModeUnoccupied Mode Standby ModeAdditional Occupancy Features Networked Set Point Offset Capability Space Temperature Set PointsNetworked Space Temperature Sensor Capability Networked Set Point CapabilityEffective Set Point Calculations Remote Wall-Mounted Sensor with +/-3F Adjustment optionalEffective set point calculations Set point calculation examplesExample a Example B Given PI loops Discharge Air Temperature ControlProportional Integral PI Control Loops PI loop listProportional Band PI Control ParametersOccupied, Standby, and Bypass Operation Indoor Air Fan OperationIntegral Time Outdoor Air Damper Operation OA temp sensor Space humidity Economizer enableEconomizer Networked Space CO2 Sensor Capability Networked Space Humidity Sensor CapabilityNetworked Outdoor Humidity Sensor Capability CO2 Demand Controlled Ventilation optionalCompressor Cooling Lockout Compressor OperationAshrae Cycle Compressor EnvelopeOutdoor Air Fan Operation Compressor Minimum On and Off TimersCompressor Start Delay Floating-Point Actuator Auto-Zero, Overdrive and SyncExternal Binary Inputs Unoccupied Input SignalRemote Shutdown Input Signal Ventilation Lockout Input SignalExternal Binary Outputs Exhaust Interlock Input SignalLights On/Off Signal Fault SignalStart/Stop Calculation Exhaust Fan ON/OFF SignalAuxiliary Heat Signal Auxiliary heat start/stop calculationExpansion board Inputs and outputs, software model 05-DX cooling onlyPriority Fault description Reset Keypad Alarm and Fault MonitoringAlarm and fault code summary Discharge Air DX Cooling Low Limit Indication F3 DX Pressure Fault F1Compressor Envelope Fault F2 Space Temp Sensor Failure F0Discharge Air Temp Sensor Failure F7 Condensate Overflow Indication optional F4Space Coil DX Temp Sensor Failure F5 Outdoor Temp Sensor Failure F6Troubleshooting Temperature Sensors Temperature versus resistance Troubleshooting Humidity SensorsRH % VDC mV Troubleshooting Carbon Dioxide CO2 SensorsHumidity versus voltage CO2 versus voltage tableConfiguration Parameter Name Abr Default LUI Menu UVC configuration parameters OMAbr Default LUI Menu OAD Stroke Time Warranty