American Standard UV05 manual ON/STOP Key and LED, FAN Key, Mode Key, Arrow Keys, Func Key

Page 8

Getting Started

Table 6: Keypad/display security levels

Level

Display

What is restricted?

Password

0

U0

Default level (access all)

10

 

 

Does not allow set point offset changes;

 

1

U1

also locks out keypad/display menu

21

 

 

access.

 

 

 

Does not allow set point offset changes

 

2

U2

nor MODE key changes; also locks out

32

 

 

keypad/display menu access.

 

3

 

Does not allow set point offset changes

 

U3

nor MODE and FAN key changes; also

43

 

 

locks out keypad/display menu access.

 

Figure 2: Changing keypad/display security levels

ON/STOP Key and LED

Use the ON/STOP key to toggle the UVC between OFF mode and running (Application Mode

Input). The ON/STOP LED is off when the UVC is in the OFF mode.

Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.

All other LEDs are switched off.

The UVC archives each change to the keypad/display FAN and MODE keys. When the ON/STOP key is used to bring the unit out of OFF mode, the UVC implements the last active fan and unit modes.

Each time the UVC power cycles, the UVC is in the auto fan and auto unit modes when power is returned.

WARNING

Off mode is a “stop” state for the unit ventilator. It is not a “power off” state. Power may still be provided to the unit.

FAN Key

Use the FAN key to toggle through each of the fan speeds (Fan Speed Command Input): Auto,

Low, Medium, and High.

MODE Key

Use the MODE key to toggle through the keypad/display accessible unit modes (Heat/Cool

Mode Input): Auto, Heat, Cool, and Fan Only.

Arrow Keys

Use the arrow keys to scroll between parameters and to adjust parameters.

FUNC Key

Use the Func key to view the actual space temperature or to confirm selection and changes to user-adjustable parameters.

8

McQuay OM 751

Image 8
Contents Date November DX Cooling Only Software Model UV05Group Applied Systems UVC Configuration Parameters IntroductionGetting Started Description of OperationDescription Manual # Model-specific unit ventilator installation literatureAccessory-specific installation literature Extreme temperature can damage system components Software program literatureDescription Acronym Abr Acronyms/AbbreviationsAcronyms and abbreviations OCS Using the Keypad/Display Display FormatKeypad Functions Security LevelsMode Key ON/STOP Key and LEDFAN Key Arrow KeysUsing the Keypad/Display Viewing Actual Indoor Air Temperature IATMenu Reference Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesOFF Mode State UVC state names and numbersNormal UVC modes State names DecimalNight Purge Mode State Fan Only Mode State aCant Heat State State D Emergency Heat Mode Super StateFull Heat State State Heat State State Auto ModeHeat Mode Super State Cant Heat State State B Cool Mode Super StateLow Limit State State E Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateSpecial Purpose Unit Modes Discharge Air DA Heat State StateLow Limit State State F Cant Cool State State CPressurize Mode Depressurize ModePurge Mode Shutdown ModeUnit Mode Priority Special purpose UVC unit mode priorityNormal UVC mode priority Priority resultOccupied Mode Unoccupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Space Temperature Set Points Networked Space Temperature Sensor CapabilityNetworked Set Point Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsEffective set point calculations Set point calculation examplesExample a Example B Given Discharge Air Temperature Control Proportional Integral PI Control LoopsPI loop list PI loopsPI Control Parameters Proportional BandOccupied, Standby, and Bypass Operation Indoor Air Fan OperationIntegral Time Outdoor Air Damper Operation OA temp sensor Space humidity Economizer enableEconomizer Networked Space Humidity Sensor Capability Networked Outdoor Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityCompressor Operation Ashrae CycleCompressor Envelope Compressor Cooling LockoutCompressor Minimum On and Off Timers Compressor Start DelayFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationUnoccupied Input Signal Remote Shutdown Input SignalVentilation Lockout Input Signal External Binary InputsExhaust Interlock Input Signal Lights On/Off SignalFault Signal External Binary OutputsExhaust Fan ON/OFF Signal Auxiliary Heat SignalAuxiliary heat start/stop calculation Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardPriority Fault description Reset Keypad Alarm and Fault MonitoringAlarm and fault code summary DX Pressure Fault F1 Compressor Envelope Fault F2Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Condensate Overflow Indication optional F4 Space Coil DX Temp Sensor Failure F5Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceTroubleshooting Carbon Dioxide CO2 Sensors Humidity versus voltageCO2 versus voltage table RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty