Diagnostics and Service
Diagnostics and Service
The most important aspect of troubleshooting unit ventilator controls is to isolate the source of the problem into one of two categories:
1The problem resides within the UVC.
2The problem is external to the UVC. Under most circumstances the problem is external to the UVC.
Alarm and Fault Monitoring
The UVC is programmed to monitor the unit for specific alarm conditions. If an alarm condition exists, a fault occurs. When a fault exists, the following occurs:
•The UVC indicates the fault condition by displaying the fault code on the keypad/display.
•The remote
•The fault signal binary output energizes.
•The fault performs the appropriate control actions as described for each fault.
Manual reset faults can be reset in one of three ways:
•By cycling the unit power.
•Via the keypad/display menu.
•Via the network interface.
Table 22: Alarm and fault code summary
Priority | Fault description | Reset | Keypad/ |
display fault | |||
|
|
| codes |
1 | Space Temp Sensor Failure | Auto | F0 |
2 | DX Pressure Fault | F1 | |
3 | Compressor Envelope Fault | F2 | |
| Manual* | ||
|
|
| |
4 | Discharge Air DX Cooling Low Limit Indication | Auto | F3 |
5 | Condensate Overflow Indication | Auto | F4 |
6 | Space Coil DX Temp Sensor Failure | Auto | F5 |
7 | Outdoor Temp Sensor Failure | Auto | F6 |
8 | Discharge Air Temp Sensor Failure | Auto | F7 |
9 | Water Coil DX Temp Sensor Failure | Auto | F8 |
10 | Auto | F9 | |
11 | Space Humidity Sensor Failure | Auto | FA |
12 | Outdoor Humidity Sensor Failure | Auto | Fb |
13 | Space CO2 Sensor Failure | Auto | FC |
14 | Not used |
| Fd |
15 | Not used |
| FE |
16 | Change Filter Indication | Manual | FF |
17 | EPROM Memory Indicator | Replace conroller board | EE |
18 | Configuration Display | Download file |
* Rev 1_27 has auto reset
McQuay OM 751 | 41 |