American Standard UV05 manual Alarm and Fault Monitoring, Alarm and fault code summary

Page 41

Diagnostics and Service

Diagnostics and Service

The most important aspect of troubleshooting unit ventilator controls is to isolate the source of the problem into one of two categories:

1The problem resides within the UVC.

2The problem is external to the UVC. Under most circumstances the problem is external to the UVC.

Alarm and Fault Monitoring

The UVC is programmed to monitor the unit for specific alarm conditions. If an alarm condition exists, a fault occurs. When a fault exists, the following occurs:

The UVC indicates the fault condition by displaying the fault code on the keypad/display.

The remote wall-mounted sensor (optional) LED flashes a pattern indicating that a fault condition exists.

The fault signal binary output energizes.

The fault performs the appropriate control actions as described for each fault.

Manual reset faults can be reset in one of three ways:

By cycling the unit power.

Via the keypad/display menu.

Via the network interface.

Table 22: Alarm and fault code summary

Priority

Fault description

Reset

Keypad/

display fault

 

 

 

codes

1

Space Temp Sensor Failure

Auto

F0

2

DX Pressure Fault

2-Auto in 7 days, then Manual

F1

3

Compressor Envelope Fault

2-Auto in 7 days, then

F2

 

Manual*

 

 

 

4

Discharge Air DX Cooling Low Limit Indication

Auto

F3

5

Condensate Overflow Indication

Auto

F4

6

Space Coil DX Temp Sensor Failure

Auto

F5

7

Outdoor Temp Sensor Failure

Auto

F6

8

Discharge Air Temp Sensor Failure

Auto

F7

9

Water Coil DX Temp Sensor Failure

Auto

F8

10

Water-out Temp Sensor Failure

Auto

F9

11

Space Humidity Sensor Failure

Auto

FA

12

Outdoor Humidity Sensor Failure

Auto

Fb

13

Space CO2 Sensor Failure

Auto

FC

14

Not used

 

Fd

15

Not used

 

FE

16

Change Filter Indication

Manual

FF

17

EPROM Memory Indicator

Replace conroller board

EE

18

Configuration Display

Download file

--

* Rev 1_27 has auto reset

McQuay OM 751

41

Image 41
Contents Date November DX Cooling Only Software Model UV05Group Applied Systems Introduction UVC Configuration ParametersGetting Started Description of OperationDescription Manual # Model-specific unit ventilator installation literatureAccessory-specific installation literature Software program literature Extreme temperature can damage system componentsDescription Acronym Abr Acronyms/AbbreviationsAcronyms and abbreviations OCS Display Format Using the Keypad/DisplayKeypad Functions Security LevelsON/STOP Key and LED Mode KeyFAN Key Arrow KeysViewing Actual Indoor Air Temperature IAT Using the Keypad/DisplayMenu Reference Changing Set PointsRW1 Abr Description DefaultChlo State Programming Description of OperationUVC Unit Modes Complete UVC-state diagramUVC state names and numbers OFF Mode StateNormal UVC modes State names DecimalFan Only Mode State a Night Purge Mode StateCant Heat State State D Emergency Heat Mode Super StateFull Heat State State Heat State State Auto ModeHeat Mode Super State Cant Heat State State B Cool Mode Super StateLow Limit State State E Econ State State Cool mode super state diagramMech State State Econ Mech State StateDischarge Air DA Heat State State Special Purpose Unit ModesLow Limit State State F Cant Cool State State CDepressurize Mode Pressurize ModePurge Mode Shutdown ModeSpecial purpose UVC unit mode priority Unit Mode PriorityNormal UVC mode priority Priority resultUnoccupied Mode Occupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Networked Space Temperature Sensor Capability Space Temperature Set PointsNetworked Set Point Capability Networked Set Point Offset CapabilityEffective Set Point Calculations Remote Wall-Mounted Sensor with +/-3F Adjustment optionalEffective set point calculations Set point calculation examplesExample a Example B Given Proportional Integral PI Control Loops Discharge Air Temperature ControlPI loop list PI loopsProportional Band PI Control ParametersOccupied, Standby, and Bypass Operation Indoor Air Fan OperationIntegral Time Outdoor Air Damper Operation OA temp sensor Space humidity Economizer enableEconomizer Networked Outdoor Humidity Sensor Capability Networked Space Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityAshrae Cycle Compressor OperationCompressor Envelope Compressor Cooling LockoutCompressor Start Delay Compressor Minimum On and Off TimersFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationRemote Shutdown Input Signal Unoccupied Input SignalVentilation Lockout Input Signal External Binary InputsLights On/Off Signal Exhaust Interlock Input SignalFault Signal External Binary OutputsAuxiliary Heat Signal Exhaust Fan ON/OFF SignalAuxiliary heat start/stop calculation Start/Stop CalculationExpansion board Inputs and outputs, software model 05-DX cooling onlyPriority Fault description Reset Keypad Alarm and Fault MonitoringAlarm and fault code summary Compressor Envelope Fault F2 DX Pressure Fault F1Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Space Coil DX Temp Sensor Failure F5 Condensate Overflow Indication optional F4Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Temperature versus resistance Troubleshooting Humidity SensorsHumidity versus voltage Troubleshooting Carbon Dioxide CO2 SensorsCO2 versus voltage table RH % VDC mVConfiguration Parameter Name Abr Default LUI Menu UVC configuration parameters OMAbr Default LUI Menu OAD Stroke Time Warranty