Diagnostics and Service

Space Humidity Sensor Failure (optional) (FA)

The Space Humidity Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.

Effect:

IA/OA Enthalpy comparison economizer (if used) is disabled.

Dehumidification function (optional) is disabled.

Fault is indicated.

Outdoor Humidity Sensor Failure (optional) (Fb)

The Outdoor Humidity Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.

Effect:

IA/OA Enthalpy comparison or OA Enthalpy economizer (if used) is disabled.

Fault is indicated.

Space CO2 Sensor Failure (optional) (FC)

The Space CO2 Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.

Effect:

CO2 Demand Controlled Ventilation function is disabled.

Fault is indicated.

Change Filter Indication (FF)

The Change Filter Indication fault occurs when the UVC calculates that the total fan run time has exceeded the allowed number of hours since the last filter change.

Effect:

Fault is indicated.

EPROM Memory Indicator (EE)

The EPROM Memory Indicator occurs when an unusual electrical event has scrambled the EPROM memory within the controller board. In the event that this happens, the controller board must be replaced.

Configuration Display (--)

The Configuration Display occurs when the display file “**.cfg” is incorrect or has not been downloaded with the appropriate file from service tools.

Troubleshooting Temperature Sensors

The UVC is configured to use passive positive temperature coefficient (PTC) sensor whose resistance increases with increasing temperature. The element has a reference resistance of 1035 ohms at 77°F (25°C). Each element is calibrated according to the tables shown.

Use the following procedure to troubleshoot a suspect sensor.

1Disconnect both sensor leads from the UVC.

2Using some other calibrated temperature sensing device, take a temperature reading at the sensor location.

44

McQuay OM 751

Image 44
Contents Date November DX Cooling Only Software Model UV05Group Applied Systems UVC Configuration Parameters IntroductionGetting Started Description of OperationDescription Manual # Model-specific unit ventilator installation literatureAccessory-specific installation literature Extreme temperature can damage system components Software program literatureDescription Acronym Abr Acronyms/AbbreviationsAcronyms and abbreviations OCS Using the Keypad/Display Display FormatKeypad Functions Security LevelsMode Key ON/STOP Key and LEDFAN Key Arrow KeysUsing the Keypad/Display Viewing Actual Indoor Air Temperature IATMenu Reference Changing Set PointsAbr Description Default RW1Chlo Description of Operation State ProgrammingComplete UVC-state diagram UVC Unit ModesOFF Mode State UVC state names and numbersNormal UVC modes State names DecimalNight Purge Mode State Fan Only Mode State aCant Heat State State D Emergency Heat Mode Super StateFull Heat State State Heat State State Auto ModeHeat Mode Super State Cant Heat State State B Cool Mode Super StateLow Limit State State E Cool mode super state diagram Econ State StateEcon Mech State State Mech State StateSpecial Purpose Unit Modes Discharge Air DA Heat State StateLow Limit State State F Cant Cool State State CPressurize Mode Depressurize ModePurge Mode Shutdown ModeUnit Mode Priority Special purpose UVC unit mode priorityNormal UVC mode priority Priority resultOccupied Mode Unoccupied ModeStandby Mode Occupancy mode priorityAdditional Occupancy Features Space Temperature Set Points Networked Space Temperature Sensor CapabilityNetworked Set Point Capability Networked Set Point Offset CapabilityRemote Wall-Mounted Sensor with +/-3F Adjustment optional Effective Set Point CalculationsEffective set point calculations Set point calculation examplesExample a Example B Given Discharge Air Temperature Control Proportional Integral PI Control LoopsPI loop list PI loopsPI Control Parameters Proportional BandOccupied, Standby, and Bypass Operation Indoor Air Fan OperationIntegral Time Outdoor Air Damper Operation OA temp sensor Space humidity Economizer enableEconomizer Networked Space Humidity Sensor Capability Networked Outdoor Humidity Sensor CapabilityCO2 Demand Controlled Ventilation optional Networked Space CO2 Sensor CapabilityCompressor Operation Ashrae CycleCompressor Envelope Compressor Cooling LockoutCompressor Minimum On and Off Timers Compressor Start DelayFloating-Point Actuator Auto-Zero, Overdrive and Sync Outdoor Air Fan OperationUnoccupied Input Signal Remote Shutdown Input SignalVentilation Lockout Input Signal External Binary InputsExhaust Interlock Input Signal Lights On/Off SignalFault Signal External Binary OutputsExhaust Fan ON/OFF Signal Auxiliary Heat SignalAuxiliary heat start/stop calculation Start/Stop CalculationInputs and outputs, software model 05-DX cooling only Expansion boardPriority Fault description Reset Keypad Alarm and Fault MonitoringAlarm and fault code summary DX Pressure Fault F1 Compressor Envelope Fault F2Space Temp Sensor Failure F0 Discharge Air DX Cooling Low Limit Indication F3Condensate Overflow Indication optional F4 Space Coil DX Temp Sensor Failure F5Outdoor Temp Sensor Failure F6 Discharge Air Temp Sensor Failure F7Troubleshooting Temperature Sensors Troubleshooting Humidity Sensors Temperature versus resistanceTroubleshooting Carbon Dioxide CO2 Sensors Humidity versus voltageCO2 versus voltage table RH % VDC mVUVC configuration parameters OM Configuration Parameter Name Abr Default LUI MenuAbr Default LUI Menu OAD Stroke Time Warranty