Bryant 580J*04--12 appendix Flue Gas Passageways, Combustion-Air Blower

Page 24

Table 6 – Liquid Propane Supply Line Pressure Ranges

580J SIZE

GAS

HEAT

MIN

MAX

HEAT OPT

LEVEL

 

 

 

 

 

 

 

 

All

A, C

All

11.0 in. wg

13.0 in. wg

(2740 Pa)

(3240 Pa)

 

 

 

 

 

 

 

 

All

B

All

NA

NA

 

 

 

 

 

Manifold pressure for LP fuel use must be adjusted to specified range. Follow instructions in the accessory kit to make initial readjustment.

Table 7 – Liquid Propane Manifold Pressure Ranges

 

 

GAS HEAT

HEAT LEVEL

HIGH FIRE

LOW FIRE

 

 

OPT

 

 

 

 

 

 

 

 

 

 

 

 

 

A, C

All

10.0 in. wg

5.0 in. wg

 

 

(2490 Pa)

(1245 Pa){

 

 

 

 

 

 

 

 

 

 

580J

B

All

NA

NA

NA: Not Available

 

 

 

 

 

 

 

 

{ 3 Phase models only

 

 

Supply Pressure Switch — The LP conversion kit includes a supply low pressure switch. The switch contacts (from terminal C to terminal NO) will open the gas valve power whenever the supply line pressure drops below the setpoint. See Fig. 29 and Fig. 30. If the low pressure remains open for 15 minutes during a call for heat, the IGC circuit will initiate a Ignition Fault (5 flashes) lockout. Reset of the low pressure switch is automatic on rise in supply line pressure. Reset of the IGC requires a recycle of unit power after the low pressure switch has closed.

C08238

Fig. 29 - LP Low Pressure Switch (Installed)

IGC

LP LPS

 

 

 

 

 

BRN

C

NO

BRN

J2-11

 

 

C

 

 

 

IGC

 

 

MGV

 

 

 

J2-12

GRA

 

 

 

 

 

TSTAT

 

 

 

W2

PNK

 

 

C08285

Fig. 30 - LP Supply Line Low Pressure Switch Wiring

This switch also prevents operation when the propane tank level is low which can result in gas with a high concentration of impurities, additives, and residues that have settled to the bottom of the tank. Operation under these conditions can cause harm to the heat exchanger system. Contact your fuel supplier if this condition is suspected.

Flue Gas Passageways

To inspect the flue collector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor as- sembly according to directions in Combustion-Air Blower section. See Fig. 31.

2.Remove the flue cover to inspect the heat exchanger.

3.Clean all surfaces as required using a wire brush.

Combustion-Air Blower

Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency.

To access burner section, slide the sliding burner partition out of the unit.

To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows:

1.Slide burner access panel out.

2.Remove the 7 screws that attach induced-draft motor housing to vestibule plate. (See Fig. 31.)

3.The blower wheel can be cleaned at this point. If ad- ditional cleaning is required, continue with Steps 4 and 5.

4.To remove blower from the motor shaft, remove 2 setscrews.

5.To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.

6.To reinstall, reverse the procedure outlined above.

24

Image 24
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceSeasonal Maintenance GeneralHeating Economizer or Outside Air DamperAir Filters and Screens Return Air FiltersAdjustable-Pitch Pulley on Motor Supply FAN Blower SectionSupply Fan Belt-Drive Electrical Shock HazardCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Remove Surface Loaded FibersPeriodic Clean Water Rinse Routine Cleaning of Coil SurfacesOne-Row Coil Two-Row CoilsRefrigerant System Pressure Access Ports Cleaning the Evaporator CoilEvaporator Coil Unit Damage HazardTo Use Cooling Charging Charts Puronr R410A RefrigerantRefrigerant Charge No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Troubleshooting Cooling System CompressorFilter Drier Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyConvenience Outlets Unit Connect Primary TransformerConnections Smoke Detectors SystemSensor ControllerCompleting Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionSensor Alarm Test Controller Alarm TestSensor and Controller Tests Dirty Controller TestRemote Test/Reset Station Dirty Sensor Test Detector CleaningChanging the Dirt Sensor Test Remote Station TestIndicators Detector IndicatorsAlarm State Control or Indicator DescriptionTroubleshooting Protective DevicesCompressor Protection Relief DeviceGAS Heating System Control CircuitFuel Types and Pressures Natural Gas Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerLiquid Propane Supply Line Pressure Ranges Liquid Propane Manifold Pressure RangesRemoval and Replacement of Gas Train Cleaning and AdjustmentBurners and Igniters Equipment Damage HazardCheck Unit Operation and Make Necessary Adjust- ments Limit SwitchBurner Ignition Spark Adjustment Orifice Replacement LED Error Code DescriptionLED Indication Error Code Description Integrated Gas Control IGC Board IGC Connections OutputsOrifice Sizes Altitude Compensation* 04-07 Small ChassisOrifice Bryant Drill Size Part NumberTroubleshooting Heating System Minimum heating entering air temperatureCont. Altitude Compensation* A08-A12 Altitude Compensation* 04-06 Low NOx UnitsHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes Economizer SystemsEconoMi$er2 Component Locations Inputs Outputs RUNSupply Air Temperature SAT Sensor EconoMi$erTemp Resistance Outdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Dry Bulb Changeover Differential Enthalpy Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Minimum Position ControlCO2 Sensor Configuration Damper MovementThermostats Occupancy ControlDCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams PRE-START-UPPersonal Injury Hazard START-UP, General Operating Sequences Fastener Torque Values Demand Controlled VentilationHeating With EconoMi$er Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberAppendix II. Physical Data Physical Data Cooling Tons Standard Refrigeration SystemPhysical Data Cooling 10 Tons Standard Refrigeration System Refrigeration System 580J*08 580J*09 580J*12Physical Data Heating 10 Tons Appendix III. FAN Performance General Fan Performance Notes580J*04 Ton Horizontal SupplyTon Vertical Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 Phase Ton Horizontal Supply 580J*05580J*05 Phase Ton Vertical Supply 14931506 1486580J*06 1482580J*06 Phase Ton Horizontal Supply 580J*06 Phase Ton Vertical Supply580J*07 580J*08 580J*09 580J*12 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data IFMRange RLA LRA TypeAppendix IV. Electrical Data FLA580J*08 Tons 580J*09 TonsIFM Range RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O Unbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 580J*04A, B, C Outdoor Circuiting580J*09/12A, C Outdoor Circuiting Catalog No. SM580J---01START-UP Checklist TemperaturesRemove and Store in Job File Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.