Bryant 580J*04--12 appendix Differential Enthalpy Control, Outdoor Enthalpy Changeover

Page 38

provided in the EconoMi$er IV wiring harness. (See Fig. 38.)

outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 39.) When the outdoor air enthalpy rises above the

580J

ECONOMI$ERIV

ECONOMI$ERIV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT (FIELD-PROVIDED)

C07085

outdoor enthalpy changeover setpoint, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. The setpoints are A, B, C, and D. (See Fig. 46.) The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller.

Differential Enthalpy Control

For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in

Fig. 48 - Return Air Temperature or Enthalpy Sensor

Mounting Location

In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. (See Fig. 45.)

Outdoor Enthalpy Changeover

For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard

outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. (See Fig. 39.) Mount the return air enthalpy sensor in the return air duct. (See Fig. 48.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 41.) The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

90

95

100

105

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(29)

(32)

(35)

(38)

(41)

(43)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46

 

 

 

 

 

 

 

 

 

CONTROL

CONTROL POINT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4

 

 

 

 

 

 

 

 

 

 

 

CURVE APPROX. deg. F (deg. C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

AT 50% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

73 (23)

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

(27)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

70 (21)

 

 

 

 

 

 

 

 

 

DRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

67 (19)

 

 

 

 

 

 

POUND

 

3

8

 

 

 

 

 

 

 

 

 

 

 

 

 

HUMIDITY

 

 

D

 

 

 

63 (17)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER

 

 

 

 

 

 

 

 

 

 

 

(24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELATIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(21)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTHALPY

 

 

 

 

 

 

 

 

 

 

 

1

0

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

65

 

9

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

 

 

 

 

 

 

 

 

 

 

 

 

(18)

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

0

 

 

 

 

 

 

 

 

 

 

 

(16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

4

0

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(13)

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

1

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

45

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

(7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

(4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D C

B

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURVE

 

 

 

 

 

35

 

40

45

 

 

50

 

55

 

60

65

 

 

 

70

 

75

80

85

90

95

100

105

110

 

 

 

 

 

(2)

 

(4)

(7)

 

 

(10)

(13)

(16)

(18)

 

 

(21)

 

(24)

(27)

(29)

(32)

(35)

(38)

(41)

(43)

 

 

 

 

 

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)

 

 

 

C06037

Fig. 49 - Enthalpy Changeover Setpoints

38

Image 38
Contents Table of Contents Safety ConsiderationsSeasonal Maintenance Unit Arrangement and AccessRoutine Maintenance GeneralAir Filters and Screens HeatingEconomizer or Outside Air Damper Return Air FiltersSupply Fan Belt-Drive Adjustable-Pitch Pulley on MotorSupply FAN Blower Section Electrical Shock HazardCondenser Coil Condenser Coil Maintenance and Cleaning RecommendationCooling Remove Surface Loaded FibersOne-Row Coil Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces Two-Row CoilsEvaporator Coil Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Unit Damage HazardRefrigerant Charge To Use Cooling Charging ChartsPuronr R410A Refrigerant No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Filter Drier Troubleshooting Cooling SystemCompressor Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyConnections Convenience OutletsUnit Connect Primary Transformer Sensor Smoke DetectorsSystem ControllerCompleting Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionSensor and Controller Tests Sensor Alarm TestController Alarm Test Dirty Controller TestChanging the Dirt Sensor Test Remote Test/Reset Station Dirty Sensor TestDetector Cleaning Remote Station TestAlarm State IndicatorsDetector Indicators Control or Indicator DescriptionCompressor Protection TroubleshootingProtective Devices Relief DeviceFuel Types and Pressures GAS Heating SystemControl Circuit Natural Gas Supply Line Pressure RangesLiquid Propane Supply Line Pressure Ranges Flue Gas PassagewaysCombustion-Air Blower Liquid Propane Manifold Pressure RangesBurners and Igniters Removal and Replacement of Gas TrainCleaning and Adjustment Equipment Damage HazardBurner Ignition Check Unit Operation and Make Necessary Adjust- mentsLimit Switch Spark Adjustment LED Indication Error Code Description Orifice ReplacementLED Error Code Description Integrated Gas Control IGC Board IGC Connections OutputsOrifice Bryant Orifice SizesAltitude Compensation* 04-07 Small Chassis Drill Size Part NumberCont. Altitude Compensation* A08-A12 Troubleshooting Heating SystemMinimum heating entering air temperature Altitude Compensation* 04-06 Low NOx UnitsHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes Economizer SystemsEconoMi$er2 Component Locations Inputs Outputs RUNTemp Resistance Supply Air Temperature SAT SensorEconoMi$er Outdoor Dry Bulb Changeover Outdoor Air Lockout SensorEconoMi$er IV Control Modes Differential Enthalpy Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Minimum Position ControlThermostats CO2 Sensor ConfigurationDamper Movement Occupancy ControlEconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyPersonal Injury Hazard Wiring DiagramsPRE-START-UP START-UP, General Operating Sequences Heating With EconoMi$er Fastener Torque ValuesDemand Controlled Ventilation Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Serial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position NumberAppendix II. Physical Data Physical Data Cooling Tons Standard Refrigeration SystemPhysical Data Cooling 10 Tons Standard Refrigeration System Refrigeration System 580J*08 580J*09 580J*12Physical Data Heating 10 Tons Appendix III. FAN Performance General Fan Performance NotesTon Vertical Supply 580J*04Ton Horizontal Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 Phase Ton Horizontal Supply 580J*051506 580J*05 Phase Ton Vertical Supply1493 1486580J*06 1482580J*06 Phase Ton Horizontal Supply 580J*06 Phase Ton Vertical Supply580J*07 580J*08 580J*09 580J*12 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboRange RLA LRA Appendix IV. Electrical DataIFM TypeAppendix IV. Electrical Data FLAIFM Range 580J*08 Tons580J*09 Tons RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O Unbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 580J*04A, B, C Outdoor Circuiting580J*09/12A, C Outdoor Circuiting Catalog No. SM580J---01Remove and Store in Job File START-UP ChecklistTemperatures Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.