Bryant 580J*04--12 appendix 580J*06 Phase Ton Horizontal Supply, 580J*06 Phase Ton Vertical Supply

Page 59

APPENDIX III. FAN PERFORMANCE (cont.)

580J*06

3 Phase

5 Ton Horizontal Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

 

0.6

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

Standard Static Option

 

 

Medium Static Option

1500

800

0.39

904

0.49

999

0.60

1087

0.72

1169

0.85

1625

849

0.48

947

0.59

1038

0.70

1122

0.83

1201

0.96

1750

899

0.59

992

0.70

1078

0.82

 

 

1235

1.08

1159

0.95

1875

950

0.70

1038

0.82

1120

0.95

1198

1.08

1271

1.22

2000

1001

0.84

1085

0.96

 

 

1.09

1238

1.23

1309

1.38

1163

 

2125

1053

0.99

1133

1.12

1208

1.26

1280

1.40

1348

1.55

2250

1106

1.16

 

 

1254

1.44

1323

1.59

1389

1.74

1182

1.29

2375

1159

1.34

1231

1.49

1300

1.64

1367

1.80

1430

1.96

2500

1212

1.55

1281

1.70

1348

1.86

1412

2.02

1473

2.19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

 

1.6

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

Medium Static Option

 

 

 

 

High Static Option

1500

1247

0.98

1320

1.13

1390

1.28

1457

1.44

1522

1.61

1625

1276

1.10

1348

1.24

1416

1.40

1481

1.56

1544

1.73

1750

1308

1.22

1377

1.38

1444

1.53

1507

1.70

1569

1.87

1875

1342

1.37

1409

1.52

1473

1.69

1536

1.86

1596

2.03

2000

1377

1.53

1442

1.69

 

 

1.86

1565

2.03

1624

2.21

1505

 

2125

1414

1.71

1477

1.87

1538

2.04

1597

2.22

1654

2.40

2250

1452

1.91

 

 

1573

2.25

1630

2.43

1686

2.62

1514

2.08

2375

1492

2.12

1551

2.30

1609

2.48

1665

2.66

1719

2.85

2500

1533

2.36

1591

2.54

1647

2.73

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 53.

Boldface indicates field--- supplied drive is required.

1.Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR30AE042).

580J*06

3 Phase

5 Ton Vertical Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

 

0.6

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Standard Static Option

 

 

 

Medium Static Option

1500

848

0.42

968

0.55

1069

0.68

1158

0.80

1238

0.94

1625

897

0.51

1013

0.65

1111

0.79

1198

0.93

1277

1.07

1750

947

0.61

1059

0.76

1155

0.91

1240

1.06

1318

1.21

1875

997

0.72

1105

0.89

1199

 

1.05

1283

1.21

1359

1.37

2000

1048

0.85

1153

1.03

1244

1.20

1326

1.37

1401

1.54

2125

1100

1.00

 

 

1290

1.37

1370

1.55

1444

1.73

1201

1.19

2250

1152

1.16

1250

1.36

1336

1.55

1415

1.75

1487

1.94

2375

1205

1.34

1299

1.55

1384

1.76

1460

1.96

1532

2.17

2500

1258

1.54

1349

1.76

1431

1.98

1506

2.20

1576

2.41

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

 

1.6

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Medium Static Option

 

 

 

 

High Static Option

 

1500

1312

1.07

1380

1.20

1445

1.34

1506

1.48

1564

1.62

1625

1350

1.21

1418

1.35

1482

 

1.50

1542

1.64

1600

1.79

1750

1390

1.36

1457

1.51

1520

1.67

1580

1.83

1637

1.98

1875

1430

1.53

 

 

1559

1.86

1618

2.02

1675

2.19

1496

1.69

2000

1471

1.72

1536

1.89

1598

2.06

1657

2.24

1713

2.41

2125

1513

1.92

1577

2.10

1638

2.28

1696

2.47

1752

2.65

2250

1555

2.13

1619

2.33

1679

2.52

1736

2.72

---

---

2375

1598

2.37

1661

2.57

1720

 

2.78

---

---

---

---

2500

1642

2.63

1704

2.84

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 53.

Boldface indicates field--- supplied drive is required.

1.Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number KR30AE042).

580J

59

Image 59
Contents Safety Considerations Table of ContentsGeneral Unit Arrangement and AccessRoutine Maintenance Seasonal MaintenanceReturn Air Filters HeatingEconomizer or Outside Air Damper Air Filters and ScreensElectrical Shock Hazard Adjustable-Pitch Pulley on MotorSupply FAN Blower Section Supply Fan Belt-DriveRemove Surface Loaded Fibers Condenser Coil Maintenance and Cleaning RecommendationCooling Condenser CoilTwo-Row Coils Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces One-Row CoilUnit Damage Hazard Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator CoilNo Charge To Use Cooling Charging ChartsPuronr R410A Refrigerant Refrigerant ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Condenser-Fan Location Troubleshooting Cooling SystemCompressor Filter DrierProblem Cause Remedy Cooling Service AnalysisConnections Convenience OutletsUnit Connect Primary Transformer Controller Smoke DetectorsSystem SensorSmoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseDirty Controller Test Sensor Alarm TestController Alarm Test Sensor and Controller TestsRemote Station Test Remote Test/Reset Station Dirty Sensor TestDetector Cleaning Changing the Dirt Sensor TestControl or Indicator Description IndicatorsDetector Indicators Alarm StateRelief Device TroubleshootingProtective Devices Compressor ProtectionNatural Gas Supply Line Pressure Ranges GAS Heating SystemControl Circuit Fuel Types and PressuresLiquid Propane Manifold Pressure Ranges Flue Gas PassagewaysCombustion-Air Blower Liquid Propane Supply Line Pressure RangesEquipment Damage Hazard Removal and Replacement of Gas TrainCleaning and Adjustment Burners and IgnitersBurner Ignition Check Unit Operation and Make Necessary Adjust- mentsLimit Switch Spark Adjustment LED Indication Error Code Description Orifice ReplacementLED Error Code Description Outputs Integrated Gas Control IGC Board IGC ConnectionsDrill Size Part Number Orifice SizesAltitude Compensation* 04-07 Small Chassis Orifice BryantAltitude Compensation* 04-06 Low NOx Units Troubleshooting Heating SystemMinimum heating entering air temperature Cont. Altitude Compensation* A08-A12Problem Cause Remedy Heating Service AnalysisEconomizer Systems IGC Board LED Alarm CodesEconoMi$er2 Component Locations RUN Inputs OutputsTemp Resistance Supply Air Temperature SAT SensorEconoMi$er Outdoor Dry Bulb Changeover Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Enthalpy Changeover Differential Enthalpy ControlMinimum Position Control Exhaust Setpoint AdjustmentOccupancy Control CO2 Sensor ConfigurationDamper Movement ThermostatsDifferential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage EconoMi$er IV PreparationPersonal Injury Hazard Wiring DiagramsPRE-START-UP START-UP, General Operating Sequences Torque Values Fastener Torque ValuesDemand Controlled Ventilation Heating With EconoMi$erC08308 580J Unit Wiring Diagram Control 06A, B, C Position Number Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Cooling Tons Standard Refrigeration System Appendix II. Physical DataRefrigeration System 580J*08 580J*09 580J*12 Physical Data Cooling 10 Tons Standard Refrigeration SystemPhysical Data Heating 10 Tons General Fan Performance Notes Appendix III. FAN PerformanceCFM RPM BHP 580J*04Ton Horizontal Supply Ton Vertical SupplyMedium Static Option High Static Option 580J*05 580J*05 Phase Ton Horizontal Supply1486 580J*05 Phase Ton Vertical Supply1493 15061482 580J*06580J*06 Phase Ton Vertical Supply 580J*06 Phase Ton Horizontal Supply580J*07 580J*08 580J*09 580J*12 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentType Appendix IV. Electrical DataIFM Range RLA LRAFLA Appendix IV. Electrical DataRLA LRA 580J*08 Tons580J*09 Tons IFM RangeMCA/MOCP Determination No C.O. or Unpwrd C.O NOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List580J*04A, B, C Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No. SM580J---01 580J*09/12A, C Outdoor CircuitingElectrical START-UP ChecklistTemperatures Remove and Store in Job File

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.