Bryant Understanding 580J Nomenclature for Air Conditioner Models

Page 40

580J

5. Carefully adjust the minimum position potentiometer until the measured mixed air temperature matches the calculated value.

6.Reconnect the supply air sensor to terminals T and T1.

Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part number S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location.

To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P1 terminals on the EconoMi$er IV controller. (See Fig. 41.)

Damper Movement

Damper movement from full open to full closed (or vice versa) takes 2-1/2 minutes.

Thermostats

The EconoMi$er IV control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.

Occupancy Control

The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied timeclock function in place of the jumper between TR and N. (See Fig. 41.) When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.

Demand Control Ventilation (DCV)

When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air.

Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.

A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause

the fresh air supplied to increase as the room CO2 level increases even though the CO2 setpoint has not been reached. By the time the CO2 level reaches the setpoint, the damper will be at maximum ventilation and should maintain the setpoint.

In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.

(TO x 100OA ) + (TR x 100RA ) =TM

TO = Outdoor-Air Temperature

OA = Percent of Outdoor Air

TR = Return-Air Temperature

RA = Percent of Return Air

TM = Mixed-Air Temperature

Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 51 to determine the maximum setting of the CO2 sensor. For example, an 1100 ppm setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 51 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels.

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 17.)

Use setting 1 or 2 for Bryant equipment. (See Table 17.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

40

Image 40
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceSeasonal Maintenance GeneralHeating Economizer or Outside Air DamperAir Filters and Screens Return Air FiltersAdjustable-Pitch Pulley on Motor Supply FAN Blower SectionSupply Fan Belt-Drive Electrical Shock HazardCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Remove Surface Loaded FibersPeriodic Clean Water Rinse Routine Cleaning of Coil SurfacesOne-Row Coil Two-Row CoilsRefrigerant System Pressure Access Ports Cleaning the Evaporator CoilEvaporator Coil Unit Damage HazardTo Use Cooling Charging Charts Puronr R410A RefrigerantRefrigerant Charge No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Troubleshooting Cooling System CompressorFilter Drier Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyUnit Connect Primary Transformer Convenience OutletsConnections Smoke Detectors SystemSensor ControllerCompleting Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionSensor Alarm Test Controller Alarm TestSensor and Controller Tests Dirty Controller TestRemote Test/Reset Station Dirty Sensor Test Detector CleaningChanging the Dirt Sensor Test Remote Station TestIndicators Detector IndicatorsAlarm State Control or Indicator DescriptionTroubleshooting Protective DevicesCompressor Protection Relief DeviceGAS Heating System Control CircuitFuel Types and Pressures Natural Gas Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerLiquid Propane Supply Line Pressure Ranges Liquid Propane Manifold Pressure RangesRemoval and Replacement of Gas Train Cleaning and AdjustmentBurners and Igniters Equipment Damage HazardLimit Switch Check Unit Operation and Make Necessary Adjust- mentsBurner Ignition Spark Adjustment LED Error Code Description Orifice ReplacementLED Indication Error Code Description Integrated Gas Control IGC Board IGC Connections OutputsOrifice Sizes Altitude Compensation* 04-07 Small ChassisOrifice Bryant Drill Size Part NumberTroubleshooting Heating System Minimum heating entering air temperatureCont. Altitude Compensation* A08-A12 Altitude Compensation* 04-06 Low NOx UnitsHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes Economizer SystemsEconoMi$er2 Component Locations Inputs Outputs RUNEconoMi$er Supply Air Temperature SAT SensorTemp Resistance EconoMi$er IV Control Modes Outdoor Air Lockout SensorOutdoor Dry Bulb Changeover Differential Enthalpy Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Minimum Position ControlCO2 Sensor Configuration Damper MovementThermostats Occupancy ControlDCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyPRE-START-UP Wiring DiagramsPersonal Injury Hazard START-UP, General Operating Sequences Fastener Torque Values Demand Controlled VentilationHeating With EconoMi$er Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberAppendix II. Physical Data Physical Data Cooling Tons Standard Refrigeration SystemPhysical Data Cooling 10 Tons Standard Refrigeration System Refrigeration System 580J*08 580J*09 580J*12Physical Data Heating 10 Tons Appendix III. FAN Performance General Fan Performance Notes580J*04 Ton Horizontal SupplyTon Vertical Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 Phase Ton Horizontal Supply 580J*05580J*05 Phase Ton Vertical Supply 14931506 1486580J*06 1482580J*06 Phase Ton Horizontal Supply 580J*06 Phase Ton Vertical Supply580J*07 580J*08 580J*09 580J*12 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data IFMRange RLA LRA TypeAppendix IV. Electrical Data FLA580J*08 Tons 580J*09 TonsIFM Range RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O Unbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 580J*04A, B, C Outdoor Circuiting580J*09/12A, C Outdoor Circuiting Catalog No. SM580J---01START-UP Checklist TemperaturesRemove and Store in Job File Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.