Bryant 580J*04--12 START-UP Checklist, Remove and Store in Job File, Electrical, Temperatures

Page 73

START-UP CHECKLIST

(Remove and Store in Job File)

I.PRELIMINARY INFORMATION

MODEL NO.:

 

SERIAL NO.:

 

DATE:

 

TECHNICIAN:

 

BUILDING LOCATION:

 

 

 

II.PRE-START-UP (insert checkmark in box as each item is completed)

jVERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT

jVERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS j VERIFY THAT FLUE HOOD IS INSTALLED

j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS

j CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHARP EDGES

jCHECK GAS PIPING FOR LEAKS

jCHECK THAT RETURN-AIR FILTER IS CLEAN AND IN PLACE j VERIFY THAT UNIT INSTALLATION IS LEVEL

jCHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT

jVERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT

III. START-UP

ELECTRICAL

 

 

 

 

 

SUPPLY VOLTAGE

L1-L2

 

L2-L3

 

L3-L1

COMPRESSOR AMPS

L1

 

L2

 

L2

 

 

INDOOR FAN AMPS

L1

 

L2

 

L2

 

 

 

 

 

 

 

 

TEMPERATURES

 

 

 

 

 

 

OUTDOOR-AIR TEMPERATURE

DB

WB

 

 

 

 

 

 

 

RETURN-AIR TEMPERATURE

 

DB

WB

 

 

 

 

 

 

 

COOLING SUPPLY AIR

 

DB

WB

 

 

 

 

 

 

 

GAS HEAT SUPPLY AIR

 

DB

 

 

 

PRESSURES

 

 

 

 

 

 

 

 

 

 

 

 

GAS INLET PRESSURE

 

IN. WG

 

 

 

GAS MANIFOLD PRESSURE

 

IN. WG (LOW FIRE)

 

 

IN. WG (HI FIRE)

 

 

 

REFRIGERANT SUCTION

 

PSIG

 

 

TEMP _F

 

 

 

REFRIGERANT DISCHARGE

 

PSIG

 

 

TEMP _F

 

 

 

 

 

 

 

 

 

 

jVERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT j VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS

j VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION

E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 07/08

Catalog No. SM580J---01

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Replaces: NEW

580J

73

Image 73
Contents Safety Considerations Table of ContentsRoutine Maintenance Unit Arrangement and AccessSeasonal Maintenance GeneralEconomizer or Outside Air Damper HeatingAir Filters and Screens Return Air FiltersSupply FAN Blower Section Adjustable-Pitch Pulley on MotorSupply Fan Belt-Drive Electrical Shock HazardCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil Remove Surface Loaded FibersRoutine Cleaning of Coil Surfaces Periodic Clean Water RinseOne-Row Coil Two-Row CoilsCleaning the Evaporator Coil Refrigerant System Pressure Access PortsEvaporator Coil Unit Damage HazardPuronr R410A Refrigerant To Use Cooling Charging ChartsRefrigerant Charge No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Compressor Troubleshooting Cooling SystemFilter Drier Condenser-Fan LocationProblem Cause Remedy Cooling Service AnalysisUnit Connect Primary Transformer Convenience OutletsConnections System Smoke DetectorsSensor ControllerSmoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor and Controller Tests Dirty Controller TestDetector Cleaning Remote Test/Reset Station Dirty Sensor TestChanging the Dirt Sensor Test Remote Station TestDetector Indicators IndicatorsAlarm State Control or Indicator DescriptionProtective Devices TroubleshootingCompressor Protection Relief DeviceControl Circuit GAS Heating SystemFuel Types and Pressures Natural Gas Supply Line Pressure RangesCombustion-Air Blower Flue Gas PassagewaysLiquid Propane Supply Line Pressure Ranges Liquid Propane Manifold Pressure RangesCleaning and Adjustment Removal and Replacement of Gas TrainBurners and Igniters Equipment Damage HazardLimit Switch Check Unit Operation and Make Necessary Adjust- mentsBurner Ignition Spark Adjustment LED Error Code Description Orifice ReplacementLED Indication Error Code Description Outputs Integrated Gas Control IGC Board IGC ConnectionsAltitude Compensation* 04-07 Small Chassis Orifice SizesOrifice Bryant Drill Size Part NumberMinimum heating entering air temperature Troubleshooting Heating SystemCont. Altitude Compensation* A08-A12 Altitude Compensation* 04-06 Low NOx UnitsProblem Cause Remedy Heating Service AnalysisEconomizer Systems IGC Board LED Alarm CodesEconoMi$er2 Component Locations RUN Inputs OutputsEconoMi$er Supply Air Temperature SAT SensorTemp Resistance EconoMi$er IV Control Modes Outdoor Air Lockout SensorOutdoor Dry Bulb Changeover Outdoor Enthalpy Changeover Differential Enthalpy ControlMinimum Position Control Exhaust Setpoint AdjustmentDamper Movement CO2 Sensor ConfigurationThermostats Occupancy ControlEconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyPRE-START-UP Wiring DiagramsPersonal Injury Hazard START-UP, General Operating Sequences Demand Controlled Ventilation Fastener Torque ValuesHeating With EconoMi$er Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position NumberPhysical Data Cooling Tons Standard Refrigeration System Appendix II. Physical DataRefrigeration System 580J*08 580J*09 580J*12 Physical Data Cooling 10 Tons Standard Refrigeration SystemPhysical Data Heating 10 Tons General Fan Performance Notes Appendix III. FAN PerformanceTon Horizontal Supply 580J*04Ton Vertical Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 580J*05 Phase Ton Horizontal Supply1493 580J*05 Phase Ton Vertical Supply1506 14861482 580J*06580J*06 Phase Ton Vertical Supply 580J*06 Phase Ton Horizontal Supply580J*07 580J*08 580J*09 580J*12 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentIFM Appendix IV. Electrical DataRange RLA LRA TypeFLA Appendix IV. Electrical Data580J*09 Tons 580J*08 TonsIFM Range RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O NOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List580J*04A, B, C Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No. SM580J---01 580J*09/12A, C Outdoor CircuitingTemperatures START-UP ChecklistRemove and Store in Job File Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.