Bryant 580J*04--12 Fastener Torque Values, Demand Controlled Ventilation, Heating With EconoMi$er

Page 45

During free cooling operation, a supply air temperature (SAT) above 50_F will cause the dampers to modulate between Minimum Position setpoint and 100% open. With SAT from 50_F to 45_F, the dampers will maintain at the Minimum Position setting. With SAT below 45_F, the outside air dampers will be closed. When SAT rises to 48_F, the dampers will re-open to Minimum Position setting.

Should 100% outside air not be capable of satisfying the space temperature, space temperature will rise until Y2 is closed. The economizer control will call for compressor operation. Dampers will modulate to maintain SAT at 50 to 55_F concurrent with compressor operation. The Low Ambient Lockout Thermostat will block compressor operation with economizer operation below 42_F outside air temperature.

When space temperature demand is satisfied (thermostat Y1 opens), the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off.

If accessory power exhaust is installed, the power exhaust fan motors will be energized by the economizer control as the dampers open above the PE-On setpoint and will be de-energized as the dampers close below the PE-On setpoint.

Damper movement from full closed to full open (or vice versa) will take between 1-1/2 and 2-1/2 minutes.

Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a DCV demand is received.

When the room temperature calls for heat (W1 closes), the heating controls are energized as described in Heating, Unit Without Economizer above.

Demand Controlled Ventilation

If a field-installed CO2 sensor is connected to the EconoMi$er IV control, a Demand Controlled Ventilation strategy will operate automatically. As the CO2 level in the space increases above the CO2 setpoint (on the EconoMi$er IV controller), the minimum position of the dampers will be increased proportionally, until the Maximum Ventilation setting is reached. As the space CO2 level decreases because of the increase in fresh air, the outdoor-damper will follow the higher demand condition from the DCV mode or from the free-cooling mode.

DCV operation is available in Occupied and Unoccupied periods with EconoMi$er IV. However, a control modification will be required on the 580J unit to implement the Unoccupied period function.

FASTENER TORQUE VALUES

See Table 18 for torque values.

580J

Heating With EconoMi$er IV

During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to

Table 18 – Torque Values

Supply fan motor mounting

120

+/

---

12 in---

lbs

Supply fan motor adjustment plate

120

+/

---

12 in---

lbs

Motor pulley setscrew

72+/---

5 in---

lbs

 

Fan pulley setscrew

72+/---

5 in---

lbs

 

Blower wheel hub setscrew

72+/---

5 in---

lbs

 

Bearing locking collar setscrew

65---

70 in

---lbs

 

Compressor mounting bolts

65---

75 in

---lbs

 

Condenser fan motor mounting bolts

20 +/---

2 in---

lbs

Condenser fan hub setscrew

84 +/---

12 in

--- lbs

45

Image 45
Contents Safety Considerations Table of ContentsRoutine Maintenance Unit Arrangement and AccessSeasonal Maintenance GeneralEconomizer or Outside Air Damper HeatingAir Filters and Screens Return Air FiltersSupply FAN Blower Section Adjustable-Pitch Pulley on MotorSupply Fan Belt-Drive Electrical Shock HazardCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil Remove Surface Loaded FibersRoutine Cleaning of Coil Surfaces Periodic Clean Water RinseOne-Row Coil Two-Row CoilsCleaning the Evaporator Coil Refrigerant System Pressure Access PortsEvaporator Coil Unit Damage HazardPuronr R410A Refrigerant To Use Cooling Charging ChartsRefrigerant Charge No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Compressor Troubleshooting Cooling SystemFilter Drier Condenser-Fan LocationProblem Cause Remedy Cooling Service AnalysisConvenience Outlets Unit Connect Primary TransformerConnections System Smoke DetectorsSensor ControllerSmoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor and Controller Tests Dirty Controller TestDetector Cleaning Remote Test/Reset Station Dirty Sensor TestChanging the Dirt Sensor Test Remote Station TestDetector Indicators IndicatorsAlarm State Control or Indicator DescriptionProtective Devices TroubleshootingCompressor Protection Relief DeviceControl Circuit GAS Heating SystemFuel Types and Pressures Natural Gas Supply Line Pressure RangesCombustion-Air Blower Flue Gas PassagewaysLiquid Propane Supply Line Pressure Ranges Liquid Propane Manifold Pressure RangesCleaning and Adjustment Removal and Replacement of Gas TrainBurners and Igniters Equipment Damage HazardCheck Unit Operation and Make Necessary Adjust- ments Limit SwitchBurner Ignition Spark Adjustment Orifice Replacement LED Error Code DescriptionLED Indication Error Code Description Outputs Integrated Gas Control IGC Board IGC ConnectionsAltitude Compensation* 04-07 Small Chassis Orifice SizesOrifice Bryant Drill Size Part NumberMinimum heating entering air temperature Troubleshooting Heating SystemCont. Altitude Compensation* A08-A12 Altitude Compensation* 04-06 Low NOx UnitsProblem Cause Remedy Heating Service AnalysisEconomizer Systems IGC Board LED Alarm CodesEconoMi$er2 Component Locations RUN Inputs OutputsSupply Air Temperature SAT Sensor EconoMi$erTemp Resistance Outdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Dry Bulb Changeover Outdoor Enthalpy Changeover Differential Enthalpy ControlMinimum Position Control Exhaust Setpoint AdjustmentDamper Movement CO2 Sensor ConfigurationThermostats Occupancy ControlEconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams PRE-START-UPPersonal Injury Hazard START-UP, General Operating Sequences Demand Controlled Ventilation Fastener Torque ValuesHeating With EconoMi$er Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position NumberPhysical Data Cooling Tons Standard Refrigeration System Appendix II. Physical DataRefrigeration System 580J*08 580J*09 580J*12 Physical Data Cooling 10 Tons Standard Refrigeration SystemPhysical Data Heating 10 Tons General Fan Performance Notes Appendix III. FAN PerformanceTon Horizontal Supply 580J*04Ton Vertical Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 580J*05 Phase Ton Horizontal Supply1493 580J*05 Phase Ton Vertical Supply1506 14861482 580J*06580J*06 Phase Ton Vertical Supply 580J*06 Phase Ton Horizontal Supply580J*07 580J*08 580J*09 580J*12 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentIFM Appendix IV. Electrical DataRange RLA LRA TypeFLA Appendix IV. Electrical Data580J*09 Tons 580J*08 TonsIFM Range RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O NOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List580J*04A, B, C Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No. SM580J---01 580J*09/12A, C Outdoor CircuitingTemperatures START-UP ChecklistRemove and Store in Job File Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.