Bryant 580J*04--12 appendix Operating Sequences

Page 44

580J

setting below the room temperature and verify that the burners and evaporator fan turn off.

Refer to Table 11 and Table 12 for the correct orifice to use at high altitudes.

Heating

1.Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.

2.Turn on electrical supply and manual gas valve.

3.Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temper- ature lever above room temperature.

4.The induced-draft motor will start.

5.After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1.

6.The evaporator-fan motor will turn on 45 seconds after burner ignition.

7.The evaporator-fan motor will turn off in 45 seconds after the thermostat temperature is satisfied.

8.Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.

NOTE: The default value for the evaporator-fan motor on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds. When one flash of the LED is observed, the evaporator-fan on/off delay has been modified.

If the limit switch trips at the start of the heating cycle during the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-fan on delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating.

The evaporator-fan off delay can also be modified. Once the call for heating has ended, there is a 10-minute period during which the modification can occur. If the limit switch trips during this period, the evaporator-fan off delay will increase by 15 seconds. A maximum of 9 trips can occur, extending the evaporator-fan off delay to 180 seconds.

To restore the original default value, reset the power to the unit.

To shut off unit, set system selector switch at OFF position. Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off.

OPERATING SEQUENCES

Cooling, Unit Without Economizer

When thermostat calls for cooling, terminals G and Y1 are energized. The indoor-fan contactor (IFC) and compressor contactor are energized and indoor-fan motor, compressor, and outdoor fan start. The outdoor fanmotor runs continuously while unit is cooling.

Heating, Unit Without Economizer

When the thermostat calls for heating, terminal W1 is energized. To prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay.

Cooling, Unit With EconoMi$er IV

For Occupied mode operation of EconoMi$er IV, there must be a 24-v signal at terminals TR and N (provided through PL6-3 from the unit’s IFC coil). Removing the signal at N places the EconoMi$er IV control in Unoccupied mode.

During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a Cooling (by free cooling) or DCV demand is received.

Integrated EconoMi$er IV operation on 580J single compressor model requires a 2-stage thermostat (Y1 and Y2 switches).

When free cooling using outside air is not available, the unit cooling sequence will be controlled directly by the space thermostat as described above as Cooling, Without Economizer. Outside air damper position will be closed or Minimum Position as determined by occupancy mode and fan signal.

When free cooling is available as determined by the appropriate changeover command (dry bulb, outdoor enthalpy, differential dry bulb or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature at 50 to 55_F. Compressor will not run.

44

Image 44
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access Routine MaintenanceSeasonal Maintenance GeneralHeating Economizer or Outside Air DamperAir Filters and Screens Return Air FiltersAdjustable-Pitch Pulley on Motor Supply FAN Blower SectionSupply Fan Belt-Drive Electrical Shock HazardCondenser Coil Maintenance and Cleaning Recommendation CoolingCondenser Coil Remove Surface Loaded FibersPeriodic Clean Water Rinse Routine Cleaning of Coil SurfacesOne-Row Coil Two-Row CoilsRefrigerant System Pressure Access Ports Cleaning the Evaporator CoilEvaporator Coil Unit Damage HazardTo Use Cooling Charging Charts Puronr R410A RefrigerantRefrigerant Charge No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Troubleshooting Cooling System CompressorFilter Drier Condenser-Fan LocationCooling Service Analysis Problem Cause RemedyConnections Convenience OutletsUnit Connect Primary Transformer Smoke Detectors SystemSensor ControllerCompleting Installation of Return Air Smoke Sensor Smoke Detector LocationsFiop Smoke Detector Wiring and Response Return Air Sensor Operating PositionSensor Alarm Test Controller Alarm TestSensor and Controller Tests Dirty Controller TestRemote Test/Reset Station Dirty Sensor Test Detector CleaningChanging the Dirt Sensor Test Remote Station TestIndicators Detector IndicatorsAlarm State Control or Indicator DescriptionTroubleshooting Protective DevicesCompressor Protection Relief DeviceGAS Heating System Control CircuitFuel Types and Pressures Natural Gas Supply Line Pressure RangesFlue Gas Passageways Combustion-Air BlowerLiquid Propane Supply Line Pressure Ranges Liquid Propane Manifold Pressure RangesRemoval and Replacement of Gas Train Cleaning and AdjustmentBurners and Igniters Equipment Damage HazardBurner Ignition Check Unit Operation and Make Necessary Adjust- mentsLimit Switch Spark Adjustment LED Indication Error Code Description Orifice ReplacementLED Error Code Description Integrated Gas Control IGC Board IGC Connections OutputsOrifice Sizes Altitude Compensation* 04-07 Small ChassisOrifice Bryant Drill Size Part NumberTroubleshooting Heating System Minimum heating entering air temperatureCont. Altitude Compensation* A08-A12 Altitude Compensation* 04-06 Low NOx UnitsHeating Service Analysis Problem Cause RemedyIGC Board LED Alarm Codes Economizer SystemsEconoMi$er2 Component Locations Inputs Outputs RUNTemp Resistance Supply Air Temperature SAT SensorEconoMi$er Outdoor Dry Bulb Changeover Outdoor Air Lockout SensorEconoMi$er IV Control Modes Differential Enthalpy Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Minimum Position ControlCO2 Sensor Configuration Damper MovementThermostats Occupancy ControlDCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyPersonal Injury Hazard Wiring DiagramsPRE-START-UP START-UP, General Operating Sequences Fastener Torque Values Demand Controlled VentilationHeating With EconoMi$er Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Appendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberAppendix II. Physical Data Physical Data Cooling Tons Standard Refrigeration SystemPhysical Data Cooling 10 Tons Standard Refrigeration System Refrigeration System 580J*08 580J*09 580J*12Physical Data Heating 10 Tons Appendix III. FAN Performance General Fan Performance Notes580J*04 Ton Horizontal SupplyTon Vertical Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 Phase Ton Horizontal Supply 580J*05580J*05 Phase Ton Vertical Supply 14931506 1486580J*06 1482580J*06 Phase Ton Horizontal Supply 580J*06 Phase Ton Vertical Supply580J*07 580J*08 580J*09 580J*12 Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboAppendix IV. Electrical Data IFMRange RLA LRA TypeAppendix IV. Electrical Data FLA580J*08 Tons 580J*09 TonsIFM Range RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O Unbalanced 3-Phase Supply Voltage NOMAppendix V. Wiring Diagram List Wiring DiagramsAppendix VI. Motormaster Sensor Locations 580J*04A, B, C Outdoor Circuiting580J*09/12A, C Outdoor Circuiting Catalog No. SM580J---01START-UP Checklist TemperaturesRemove and Store in Job File Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.