Bryant 580J*04--12 appendix Inputs Outputs, Run

Page 35

500 OHM RESISTOR

NOTE 1

RUN

NOTE 3

50HJ540573

ACTUATOR ASSEMBLY

DIRECT DRIVE

ACTUATOR

 

 

BLACK

4

 

 

 

 

 

 

3

 

 

 

5

 

 

BLUE

2

 

 

 

 

 

 

8

VIOLET

 

 

6

 

 

 

PINK

 

 

7

 

 

 

OAT SENSOR

 

RED

1

 

 

 

 

 

 

 

 

10

 

YELLOW

 

11

 

 

9

 

 

 

4-20mA SIGNAL

 

WHITE

12

 

 

 

 

 

TRANSFORMER GROUND

24 VAC

4-20 mA position input signal

580J

ECONOMISER2 PLUG

NOTES:

1.Switch on actuator must be in run position for economizer to operate.

2.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C08436

Fig. 42 - EconoMi$er2 with 4 to 20 mA Control Wiring

Table 15 – EconoMi$er IV Input/Output Logic

 

 

 

 

 

 

 

 

 

 

INPUTS

 

 

 

 

 

OUTPUTS

 

Demand Control

Enthalpy*

 

 

 

Compressor

N Terminal†

 

 

Y1

Y2

Stage

Stage

Occupied

Unoccupied

Ventilation (DCV)

Outdoor

Return

 

 

1

2

Damper

 

 

 

 

 

 

High

 

On

On

On

On

 

 

 

Low

On

Off

On

Off

Minimum position

Closed

 

(Free Cooling LED Off)

Below set

 

Off

Off

Off

Off

 

 

 

 

 

 

(DCV LED Off)

Low

 

On

On

On

Off

Modulating** (between min.

Modulating** (between

 

High

On

Off

Off

Off

position and full-open)

closed and full-open)

 

(Free Cooling LED On)

 

 

Off

Off

Off

Off

Minimum position

Closed

 

 

 

 

High

 

On

On

On

On

Modulating†† (between min.

Modulating†† (between

 

Low

On

Off

On

Off

position and DCV

closed and DCV

 

(Free Cooling LED Off)

 

 

 

 

 

 

maximum)

maximum)

Above set

 

Off

Off

Off

Off

 

 

(DCV LED On)

 

 

 

 

 

 

 

 

Low

 

On

On

On

Off

 

 

 

High

On

Off

Off

Off

Modulating***

Modulating†††

 

(Free Cooling LED On)

 

 

Off

Off

Off

Off

 

 

 

 

 

 

 

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.

Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). ** Modulation is based on the supply-air sensor signal.

†† Modulation is based on the DCV signal.

*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).

††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).

35

Image 35
Contents Safety Considerations Table of ContentsGeneral Unit Arrangement and AccessRoutine Maintenance Seasonal MaintenanceReturn Air Filters HeatingEconomizer or Outside Air Damper Air Filters and ScreensElectrical Shock Hazard Adjustable-Pitch Pulley on MotorSupply FAN Blower Section Supply Fan Belt-DriveRemove Surface Loaded Fibers Condenser Coil Maintenance and Cleaning RecommendationCooling Condenser CoilTwo-Row Coils Periodic Clean Water RinseRoutine Cleaning of Coil Surfaces One-Row CoilUnit Damage Hazard Refrigerant System Pressure Access PortsCleaning the Evaporator Coil Evaporator CoilNo Charge To Use Cooling Charging ChartsPuronr R410A Refrigerant Refrigerant ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Condenser-Fan Location Troubleshooting Cooling SystemCompressor Filter DrierProblem Cause Remedy Cooling Service AnalysisConnections Convenience OutletsUnit Connect Primary Transformer Controller Smoke DetectorsSystem SensorSmoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseDirty Controller Test Sensor Alarm TestController Alarm Test Sensor and Controller TestsRemote Station Test Remote Test/Reset Station Dirty Sensor TestDetector Cleaning Changing the Dirt Sensor TestControl or Indicator Description IndicatorsDetector Indicators Alarm StateRelief Device TroubleshootingProtective Devices Compressor ProtectionNatural Gas Supply Line Pressure Ranges GAS Heating SystemControl Circuit Fuel Types and PressuresLiquid Propane Manifold Pressure Ranges Flue Gas PassagewaysCombustion-Air Blower Liquid Propane Supply Line Pressure RangesEquipment Damage Hazard Removal and Replacement of Gas TrainCleaning and Adjustment Burners and IgnitersBurner Ignition Check Unit Operation and Make Necessary Adjust- mentsLimit Switch Spark Adjustment LED Indication Error Code Description Orifice ReplacementLED Error Code Description Outputs Integrated Gas Control IGC Board IGC ConnectionsDrill Size Part Number Orifice SizesAltitude Compensation* 04-07 Small Chassis Orifice BryantAltitude Compensation* 04-06 Low NOx Units Troubleshooting Heating SystemMinimum heating entering air temperature Cont. Altitude Compensation* A08-A12Problem Cause Remedy Heating Service AnalysisEconomizer Systems IGC Board LED Alarm CodesEconoMi$er2 Component Locations RUN Inputs OutputsTemp Resistance Supply Air Temperature SAT SensorEconoMi$er Outdoor Dry Bulb Changeover Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Enthalpy Changeover Differential Enthalpy ControlMinimum Position Control Exhaust Setpoint AdjustmentOccupancy Control CO2 Sensor ConfigurationDamper Movement ThermostatsDifferential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage EconoMi$er IV PreparationPersonal Injury Hazard Wiring DiagramsPRE-START-UP START-UP, General Operating Sequences Torque Values Fastener Torque ValuesDemand Controlled Ventilation Heating With EconoMi$erC08308 580J Unit Wiring Diagram Control 06A, B, C Position Number Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Cooling Tons Standard Refrigeration System Appendix II. Physical DataRefrigeration System 580J*08 580J*09 580J*12 Physical Data Cooling 10 Tons Standard Refrigeration SystemPhysical Data Heating 10 Tons General Fan Performance Notes Appendix III. FAN PerformanceCFM RPM BHP 580J*04Ton Horizontal Supply Ton Vertical SupplyMedium Static Option High Static Option 580J*05 580J*05 Phase Ton Horizontal Supply1486 580J*05 Phase Ton Vertical Supply1493 15061482 580J*06580J*06 Phase Ton Vertical Supply 580J*06 Phase Ton Horizontal Supply580J*07 580J*08 580J*09 580J*12 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentType Appendix IV. Electrical DataIFM Range RLA LRAFLA Appendix IV. Electrical DataRLA LRA 580J*08 Tons580J*09 Tons IFM RangeMCA/MOCP Determination No C.O. or Unpwrd C.O NOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List580J*04A, B, C Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No. SM580J---01 580J*09/12A, C Outdoor CircuitingElectrical START-UP ChecklistTemperatures Remove and Store in Job File

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.