Bryant 580J*04--12 EconoMi$er IV Sensor Usage, EconoMi$er IV Preparation, Differential Enthalpy

Page 41

Table 17 – EconoMi$er IV Sensor Usage

 

ECONOMI$ER IV WITH OUTDOOR AIR

APPLICATION

 

DRY BULB SENSOR

 

 

Accessories Required

Outdoor Air

None. The outdoor air dry bulb sensor

Dry Bulb

 

is factory installed.

 

 

 

 

 

 

 

Differential

 

CRTEMPSN002A00*

Dry Bulb

 

 

 

 

 

 

 

Single Enthalpy

 

 

HH57AC078

Differential

 

 

HH57AC078

 

 

 

 

and

Enthalpy

 

 

 

 

 

CRENTDIF004A00*

 

 

CO2 for DCV

 

 

 

 

 

 

Control using a

 

 

33ZCSENCO2

Wall-Mounted

 

 

 

 

 

 

 

 

CO2 Sensor

 

 

 

 

 

 

CO2 for DCV

33ZCSENCO2†

 

O

 

 

Control using a

and

 

 

 

CRCBDIOX005A00††

Duct-Mounted

 

 

R

 

33ZCASPCO2**

 

 

 

CO2 Sensor

 

 

 

 

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.

† 33ZCSENCO2 is an accessory CO2 sensor.

**33ZCASPCO2 is an accessory aspirator box required for duct- mounted applications.

††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.

3.Use the Up/Down button to select the preset number. (See Table 17.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV (Demand Controlled Ventilation) Control

If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

EconoMi$er IV Preparation

This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.

NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.

IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting.

1.Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.

2.Disconnect device at P and P1.

3.Jumper P to P1.

4.Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor across T and T1.

5.Jumper TR to 1.

6.Jumper TR to N.

7.If connected, remove sensor from terminals SO and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals SO and +.

8.Put 620-ohm resistor across terminals SR and +.

9.Set minimum position, DCV setpoint, and exhaust po- tentiometers fully CCW (counterclockwise).

10.Set DCV maximum position potentiometer fully CW (clockwise).

11.Set enthalpy potentiometer to D.

12.Apply power (24 vac) to terminals TR and TR1.

Differential Enthalpy

To check differential enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Place 620-ohm resistor across SO and +.

3.Place 1.2 kilo-ohm resistor across SR and +. The Free Cool LED should be lit.

4.Remove 620-ohm resistor across SO and +. The Free Cool LED should turn off.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

Single Enthalpy

To check single enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.

3.Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.

4.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

DCV (Demand Controlled Ventilation) and Power Exhaust

To check DCV and Power Exhaust:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.

3.Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.

4.Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the po- tentiometer is approximately 90%. The actuator should remain in position.

5.Turn the DCV setpoint potentiometer CW until the DCV LED turns off. The DCV LED should turn off

580J

41

Image 41
Contents Safety Considerations Table of ContentsRoutine Maintenance Unit Arrangement and AccessSeasonal Maintenance GeneralEconomizer or Outside Air Damper HeatingAir Filters and Screens Return Air FiltersSupply FAN Blower Section Adjustable-Pitch Pulley on MotorSupply Fan Belt-Drive Electrical Shock HazardCooling Condenser Coil Maintenance and Cleaning RecommendationCondenser Coil Remove Surface Loaded FibersRoutine Cleaning of Coil Surfaces Periodic Clean Water RinseOne-Row Coil Two-Row CoilsCleaning the Evaporator Coil Refrigerant System Pressure Access PortsEvaporator Coil Unit Damage HazardPuronr R410A Refrigerant To Use Cooling Charging ChartsRefrigerant Charge No ChargeCooling Charging Charts Cooling Charging ChartsCooling Charging Charts C08437 C08438 C08439 Compressor Troubleshooting Cooling SystemFilter Drier Condenser-Fan LocationProblem Cause Remedy Cooling Service AnalysisConnections Convenience OutletsUnit Connect Primary Transformer System Smoke DetectorsSensor ControllerSmoke Detector Locations Completing Installation of Return Air Smoke SensorReturn Air Sensor Operating Position Fiop Smoke Detector Wiring and ResponseController Alarm Test Sensor Alarm TestSensor and Controller Tests Dirty Controller TestDetector Cleaning Remote Test/Reset Station Dirty Sensor TestChanging the Dirt Sensor Test Remote Station TestDetector Indicators IndicatorsAlarm State Control or Indicator DescriptionProtective Devices TroubleshootingCompressor Protection Relief DeviceControl Circuit GAS Heating SystemFuel Types and Pressures Natural Gas Supply Line Pressure RangesCombustion-Air Blower Flue Gas PassagewaysLiquid Propane Supply Line Pressure Ranges Liquid Propane Manifold Pressure RangesCleaning and Adjustment Removal and Replacement of Gas TrainBurners and Igniters Equipment Damage HazardBurner Ignition Check Unit Operation and Make Necessary Adjust- mentsLimit Switch Spark Adjustment LED Indication Error Code Description Orifice ReplacementLED Error Code Description Outputs Integrated Gas Control IGC Board IGC ConnectionsAltitude Compensation* 04-07 Small Chassis Orifice SizesOrifice Bryant Drill Size Part NumberMinimum heating entering air temperature Troubleshooting Heating SystemCont. Altitude Compensation* A08-A12 Altitude Compensation* 04-06 Low NOx UnitsProblem Cause Remedy Heating Service AnalysisEconomizer Systems IGC Board LED Alarm CodesEconoMi$er2 Component Locations RUN Inputs OutputsTemp Resistance Supply Air Temperature SAT SensorEconoMi$er Outdoor Dry Bulb Changeover Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Enthalpy Changeover Differential Enthalpy ControlMinimum Position Control Exhaust Setpoint AdjustmentDamper Movement CO2 Sensor ConfigurationThermostats Occupancy ControlEconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyPersonal Injury Hazard Wiring DiagramsPRE-START-UP START-UP, General Operating Sequences Demand Controlled Ventilation Fastener Torque ValuesHeating With EconoMi$er Torque ValuesC08308 580J Unit Wiring Diagram Control 06A, B, C Model Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position NumberPhysical Data Cooling Tons Standard Refrigeration System Appendix II. Physical DataRefrigeration System 580J*08 580J*09 580J*12 Physical Data Cooling 10 Tons Standard Refrigeration SystemPhysical Data Heating 10 Tons General Fan Performance Notes Appendix III. FAN PerformanceTon Horizontal Supply 580J*04Ton Vertical Supply CFM RPM BHPMedium Static Option High Static Option 580J*05 580J*05 Phase Ton Horizontal Supply1493 580J*05 Phase Ton Vertical Supply1506 14861482 580J*06580J*06 Phase Ton Vertical Supply 580J*06 Phase Ton Horizontal Supply580J*07 580J*08 580J*09 580J*12 Unit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentIFM Appendix IV. Electrical DataRange RLA LRA TypeFLA Appendix IV. Electrical Data580J*09 Tons 580J*08 TonsIFM Range RLA LRAMCA/MOCP Determination No C.O. or Unpwrd C.O NOM Unbalanced 3-Phase Supply VoltageWiring Diagrams Appendix V. Wiring Diagram List580J*04A, B, C Outdoor Circuiting Appendix VI. Motormaster Sensor LocationsCatalog No. SM580J---01 580J*09/12A, C Outdoor CircuitingTemperatures START-UP ChecklistRemove and Store in Job File Electrical

580J*04--12 specifications

The Bryant 580J*04--12 is a notable unit in the realm of residential air conditioning, exemplifying efficiency and reliability. Designed to offer optimal cooling solutions, this model incorporates advanced technologies and features that cater to modern comfort needs.

One of the standout features of the Bryant 580J is its energy efficiency. With a high Seasonal Energy Efficiency Ratio (SEER) rating, this air conditioning unit is engineered to minimize energy consumption while maximizing cooling performance. This efficiency not only reduces monthly utility bills but also aligns with environmentally friendly practices by using less energy.

The 580J model is equipped with advanced compressor technology, which contributes to its smooth and quiet operation. This is particularly important for residential settings, where noise can be a significant concern. The unit consistently maintains comfortable indoor temperatures without disruptive sound levels, enhancing the overall living experience.

This air conditioning system is designed with durability in mind. Constructed from robust materials, it withstands the rigors of various weather conditions. Additionally, its components are engineered for longevity, reducing the need for frequent repairs and maintenance. The 580J also comes with a comprehensive warranty, which provides homeowners with peace of mind regarding their investment.

Smart technology integration is another key feature of the Bryant 580J. Homeowners can take advantage of programmable thermostats and compatibility with home automation systems. This allows for remote access and control, making it easier to manage indoor climates efficiently. Users can set schedules, adjust temperatures, and monitor energy usage from their smartphones, adding a layer of convenience to everyday living.

Furthermore, the Bryant 580J includes advanced air filtration systems that improve indoor air quality. By effectively trapping dust, allergens, and pollutants, this unit promotes a healthier living environment. This feature is particularly beneficial for individuals with allergies or respiratory issues.

In summary, the Bryant 580J*04--12 stands out for its energy efficiency, quiet operation, durability, smart technology integration, and air quality improvement capabilities. By blending advanced engineering with user-friendly features, this model continues to be a top choice for homeowners seeking reliable and efficient air conditioning solutions.