Emerson 3000/ITR manual Changing Operational Settings, Service, Contacts

Page 20

Liebert iCOM Display Components and Functions

4.2Changing Operational Settings

Changes to the Liebert Challenger 3000/Liebert Challenger ITR’s operation settings in the Set Alarms and Setpoints menus require a password.

1.From the home screen, press the Enter key to view the User Menu (see Figure 8).

2.Press Enter again to highlight the first icon.

3.Use the keyboard’s arrow keys to move to the icon for the data you wish to change.

4.Once that icon is highlighted, press Enter again to open that menu.

If a password is required, see 4.1.3 - Entering the Password.

5.After entering the password, use the Up and Down arrow keys to scroll to and highlight the operational setting to be changed.

6.Press Enter to highlight the values for that setting.

7.Use the Up and Down arrow keys to change the value.

8.Press Enter to accept the change. (The value will no longer be highlighted.)

9.Press ESC to deselect the operational setting. (The setting will no longer be highlighted.)

10.Press ESC again to move to previous screens.

Figure 8 Liebert iCOM User Menu icons

 

°C / °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

% RH

 

 

 

 

 

 

LOG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARMS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setpoints

Spare Parts List

 

Event Log

Graphic Data Record

 

 

View Network

 

Set Alarms

View and change

Contains spare

Lists last 400

Displays average room

 

Shows status of

Allows user to

operational

parts available on

 

events and

air temperature and

 

 

 

all connected

 

change settings for

 

setpoints

site; Large Display

 

alarms

supply refrigerant

 

units; View Only;

 

alarms

 

 

 

 

 

 

 

 

 

 

Only

 

View Only

temperature graphs;

 

 

Large Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data is View Only;

 

 

 

 

 

 

 

Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display scale is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

adjustable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!

 

 

 

1

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTIVE

9

 

 

3

 

 

1234h

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARMS

 

 

 

 

 

 

 

 

Sleep Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor Data

Active Alarms

Display Setup

Total Run Hours

 

 

 

Used to set

 

 

Service

 

operating period,

 

Shows readings

Lists all current

Change settings

Records the run time of

 

 

Contacts

 

including startup

 

of sensors; View

alarms; View Only

 

for display:

all components and

 

Contains key

 

 

 

and shutdown;

 

 

Only

 

 

 

 

 

language and

allows setting of limits on

 

 

contact information

 

 

 

 

 

 

 

 

 

Large Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

time

run time; View Only

 

 

 

 

for service

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.

14

Image 20
Contents Operation & Maintenance Manual 50 & 60Hz Page Table of Contents Component Operation and Maintenance Standard AlarmsFigures Tables Important Safety Instructions Page System Descriptions IntroductionCompressorized Systems Glycool Chilled Glycol Cooling SystemsStartup Procedure StartupStartup Large and Small Displays FeaturesOperation with Icom Control Liebert Icom Display Components and Functions Escape Key Down Arrow KeyKeyboard icons and functions Icon Key Name FunctionNavigating Through the Liebert iCOM Display Sensor Reading Next Maintenance Evaporator Fan Speed Time Most Recent AlarmsControl Interface-Three Main Menus Percent System or Unit Cooling On/Off DateAccessing Menus and Settings Viewing Data Entering the PasswordAfter highlighting the Password command line, press Password is factory-set atAccessing Submenus on Large Displays Accessing SubmenusAccessing Submenus on Small Displays Service Menu Unit Status Menu System ViewStatus Menu Unit 1 View User Menu Advanced Menu UnitContacts Changing Operational SettingsService Changing Liebert iCOM’s Display Settings Highlight the setting to be changed by pressing EnterNetwork Liebert iCOM Service Menu Icons and LegendGraphical Data Record Wiring for Unit-to-Unit Communications-U2U Wiring a Liebert iCOM U2U Network Small DisplaysSample Liebert iCOM network configurations Liebert iCOM U2U Ethernet NetworkCombining Large and Small Displays on a U2U Network Large DisplaysWall-Mount Large Display U2U network setup diagram Display Service/Network Liebert iCom Display MenuLiebert iCOM Display Components and Functions Liebert iCOM wiring-Unit as shipped 194273 194273 P65 P64 P61 P63 P67 P66Entering Network Setup Information Control board U2U network setup screenAdvanced Menu Unit # Service Menu Unit #Viewing Multiple Units with a Networked Large Display Single Unit Functions OperationUnit/Fan Control Start Stop Remote On / Off Display On / OffAutorestart Loss of Power AlarmFan Alarm / Fan Protection Settings High Pressure Alarm Digital Scroll High TemperaturePump Down-Air Cooled with Condenser Only Units Compressor TimingPI Control Control TypesProportional Control Intelligent Control Chilled Water Only Standard Alarms Alarm DescriptionsChange Filter Compressor OverloadHigh Temperature High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers High Head PressureLoss of Power Low TemperatureLoss of Air Flow Low HumidityOptional Alarms Set Alarms-User MenusSystem Testing Component Operation and MaintenanceFan Safety Switch Control Transformer and FusesHigh-Temp Sensor Smoke DetectorDistance From Unit, feet m Zone leak detection kit installation scenariosRemote Shutdown Filters Blower PackageFan Impellers and Bearings BeltRefrigeration System Air DistributionSuction Pressure Suction pressures R407cAdjustment Discharge PressureSuperheat Thermostatic Expansion Valve OperationAir Cooled Condenser Outdoor fan/condenser configuration Water/Glycol Cooled Condensers Coaxial CondenserMotorized Ball Valve-Digital Scroll Compressor ControlControl Method StartupAdjusting Collar Nut Valve spring guideCooling Type Glycool Glycol Flow Control Drycooler SettingsAquastat settings-two-fan through four-fan drycoolers Compressor Replacement Compressor OilBefore Replacing or Returning a Compressor Compressor Functional CheckElectrical Failure Standard Scroll Compressor ReplacementMechanical Failure Digital Scroll Compressor Replacement Procedure Glycol Solution MaintenanceCleaning the Pan HumidifierInfrared Humidifier Removing the PanAutoflush Infrared Humidifier Cleaning System Changing Humidifier LampsAutoflush Operation Humidifier LampsAutoflush Controls Steam Generating HumidifierControls Replacing the Canister Humidifier canister part numbersPart Capacity Number Voltage Lb/hr kg/hr 200-460Circuit Board Adjustments Drain Tempering FeatureTroubleshooting Blower troubleshootingChilled water troubleshooting Symptom Possible Cause Check or RemedyCompressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pump troubleshootingInfrared humidifier troubleshooting See 7.5.1 Compressor FunctionalSteam generating humidifier troubleshooting Reheat troubleshooting Monthly Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Semiannual Maintenance Inspection Checklist Page Ne t ItiPpor t Ti n That

3000/ITR specifications

The Emerson 3000/ITR is a powerful and versatile instrument designed for industrial automation and process control applications. This modular platform integrates advanced features and technologies tailored to meet the needs of diverse industries including oil and gas, pharmaceuticals, and manufacturing.

One of the main features of the Emerson 3000/ITR is its exceptional scalability. The system can be easily expanded to accommodate growing operational demands. With its modular architecture, operators can add or remove components without significant downtime, ensuring continuous productivity. This flexibility allows businesses to adapt their systems to changing environments and requirements seamlessly.

The Emerson 3000/ITR leverages state-of-the-art communication technologies to ensure reliable data exchange between devices. With support for various protocols, including Hart, Modbus, and Profibus, the system can easily integrate with existing infrastructure. This adaptability enhances interoperability and simplifies the communication between field devices and control systems, promoting efficient data handling.

Built with robust security features, the Emerson 3000/ITR guarantees the integrity of sensitive data. The platform incorporates advanced encryption techniques and user authentication protocols to protect against potential cyber threats. This focus on security is essential in today’s digitally connected industrial environments.

Another key characteristic of the Emerson 3000/ITR is its user-friendly interface. The system is designed with operators in mind, featuring intuitive controls and comprehensive dashboards that provide real-time visibility into process performance. The graphical user interface simplifies complex operations, enabling quick decision-making and minimizing human errors.

Additionally, the Emerson 3000/ITR supports advanced analytics capabilities that enhance operational efficiency. By leveraging predictive analytics and machine learning algorithms, the system can identify patterns and anomalies, allowing for proactive maintenance and reducing the risk of unexpected downtime. This predictive maintenance approach helps organizations optimize their resources and extend the lifecycle of their equipment.

In conclusion, the Emerson 3000/ITR stands out as an exemplary solution for modern industrial automation. Its modular design, robust communication support, strong security measures, user-friendly interface, and advanced analytics capabilities make it an ideal choice for businesses looking to enhance their operational efficiency and adaptability. As industries continue to evolve, the Emerson 3000/ITR remains at the forefront, facilitating smarter and more efficient automation processes.